Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop E
Sequence Number 4
Notes
Date Text
2007-05-15 16:39:48** PROVISO/REVISIONS REQUIRED **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SEE THE BELOW COMMENTS ARE BASED ON CHANGES
 ON PLANS. THERE ARE ITEMS ON THE ELECTRICAL RISER
 DIAGRAM/PANELS WHICH WERE CHANGED FROM PREVIOUS PLANS
 AND NOT PART OF PREVIOUS REVIEWED PLANS. NEW COMMENTS
 ARE NOW BASED ON THESE CHANGES.
  
 1) NOTE:PLEASE SEE THE ELECTRICAL RISER. PLEASE
 COORDINATE FEEDERS/CONDUCTORS WITH THAT OF THE FEEDER
 LEGEND AND THE PANEL(S).
 A) PLEASE SEE RISER SHOWS 250MCM FROM PANEL *H* TO
 *MH*, HOWEVER PANEL *MH* INDICATES 500MCM.
 ** THIS FEEDER WAS REVISED FROM PREVIOUS PLANS.
  
 B) PLEASE SEE THE FEEDERS FROM *QQ* TO *MQ* WHICH NOW
 INDICATE 4/300, WHICH TRANSLATED TO THE FEEDER SCHEDULE
 SHOULD BE 4-350MCM AND EQUIPMENT GROUND, HOWEVER THE
 FEEDER LEGEND ONLY INDICATES 3-350MCM AND EQUIPMENT
 GROUND WHICH IS MISSING ONE PHASE OR NEUTRAL CONDUCTOR.
  
 ( 4-WIRE COLUMN CONTAINS OTHERS NOTED AS 3-WIRE,
 HOWEVER THESE DO NOT APPLY TO RISER)
 **THIS FEEDER WAS REVISED FROM PREVIOUS PLANS.
  
 C) PLEASE SEE THE NEW METER CENTER ELEVATION WHICH DOES
 NOT COORDINATE WITH THE RISER BELOW ELEVATION AS
 SHOWN.
 PLEASE SEE THE ELEVATION SHOWS 225AMP MAIN CIRCUIT
 BREAKERS FOR MAIN FOR THE HOUSE AND AMERICAN LUNG
 HOWEVER THE ELECTRICAL RISER SHOWS 250AMP MAIN CIRCUIT
 BREAKERS WHICH DO NOT CORRELATE.
 **THIS ELECTRICAL RISER AND METER CENTER ELEVATION WAS
 REVISED FROM PREVIOUS PLANS.
  
 2) NOTE: PLEASE SEE RISER, AS THE TAPPED CONDUCTORS ARE
 NOT SHOWN FROM GUTTER TO EACH METER OR FIRST MEANS OF
 DISCONNECT, THE RISER WAS REDLINED TO NOTE THAT *NO
 EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS
 OF DISCONNECT.
  
 3) NOTE: PLEASE COORDINATE THE SHEET DESIGNATION OF
 E1-01-301 AS THE FIRST FLOOR IS CALLED LIGHT DENSITY
 AND SECOND FLOOR IS PHOTO-METRICS.
  
 4) NOTE:PLEASE KNOW THE ABOVE CORRECTIONS MUST BE
 SUBMITTED FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN OR 30DAYS WHICH EVER COMES
 FIRST. THIS CONDITION OF ISSUANCE WILL PLACE PERMIT ON
 HOLD WITHIN 30DAYS IF REVISIONS ARE NOT SUBMITTED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]