| 2007-05-15 16:39:48 | ** PROVISO/REVISIONS REQUIRED ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | ** PLEASE SEE THE BELOW COMMENTS ARE BASED ON CHANGES |
| | ON PLANS. THERE ARE ITEMS ON THE ELECTRICAL RISER |
| | DIAGRAM/PANELS WHICH WERE CHANGED FROM PREVIOUS PLANS |
| | AND NOT PART OF PREVIOUS REVIEWED PLANS. NEW COMMENTS |
| | ARE NOW BASED ON THESE CHANGES. |
| | |
| | 1) NOTE:PLEASE SEE THE ELECTRICAL RISER. PLEASE |
| | COORDINATE FEEDERS/CONDUCTORS WITH THAT OF THE FEEDER |
| | LEGEND AND THE PANEL(S). |
| | A) PLEASE SEE RISER SHOWS 250MCM FROM PANEL *H* TO |
| | *MH*, HOWEVER PANEL *MH* INDICATES 500MCM. |
| | ** THIS FEEDER WAS REVISED FROM PREVIOUS PLANS. |
| | |
| | B) PLEASE SEE THE FEEDERS FROM *QQ* TO *MQ* WHICH NOW |
| | INDICATE 4/300, WHICH TRANSLATED TO THE FEEDER SCHEDULE |
| | SHOULD BE 4-350MCM AND EQUIPMENT GROUND, HOWEVER THE |
| | FEEDER LEGEND ONLY INDICATES 3-350MCM AND EQUIPMENT |
| | GROUND WHICH IS MISSING ONE PHASE OR NEUTRAL CONDUCTOR. |
| | |
| | ( 4-WIRE COLUMN CONTAINS OTHERS NOTED AS 3-WIRE, |
| | HOWEVER THESE DO NOT APPLY TO RISER) |
| | **THIS FEEDER WAS REVISED FROM PREVIOUS PLANS. |
| | |
| | C) PLEASE SEE THE NEW METER CENTER ELEVATION WHICH DOES |
| | NOT COORDINATE WITH THE RISER BELOW ELEVATION AS |
| | SHOWN. |
| | PLEASE SEE THE ELEVATION SHOWS 225AMP MAIN CIRCUIT |
| | BREAKERS FOR MAIN FOR THE HOUSE AND AMERICAN LUNG |
| | HOWEVER THE ELECTRICAL RISER SHOWS 250AMP MAIN CIRCUIT |
| | BREAKERS WHICH DO NOT CORRELATE. |
| | **THIS ELECTRICAL RISER AND METER CENTER ELEVATION WAS |
| | REVISED FROM PREVIOUS PLANS. |
| | |
| | 2) NOTE: PLEASE SEE RISER, AS THE TAPPED CONDUCTORS ARE |
| | NOT SHOWN FROM GUTTER TO EACH METER OR FIRST MEANS OF |
| | DISCONNECT, THE RISER WAS REDLINED TO NOTE THAT *NO |
| | EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS |
| | OF DISCONNECT. |
| | |
| | 3) NOTE: PLEASE COORDINATE THE SHEET DESIGNATION OF |
| | E1-01-301 AS THE FIRST FLOOR IS CALLED LIGHT DENSITY |
| | AND SECOND FLOOR IS PHOTO-METRICS. |
| | |
| | 4) NOTE:PLEASE KNOW THE ABOVE CORRECTIONS MUST BE |
| | SUBMITTED FOR REVIEW BEFORE ANY ROUGH ELECTRICAL |
| | INSPECTION IS CALLED IN OR 30DAYS WHICH EVER COMES |
| | FIRST. THIS CONDITION OF ISSUANCE WILL PLACE PERMIT ON |
| | HOLD WITHIN 30DAYS IF REVISIONS ARE NOT SUBMITTED. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |