Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop M
Sequence Number 3
Notes
Date Text
2007-04-26 07:51:34*************PROVISO************
  
 EF-5: AIR REMOVED BY MECHANICAL EXHAUST SHALL BE
 DISCHARGED OUTDOORS (NOT INTO PARKING GARAGE) PER FBC,M
 501.2. ALSO, OPENING PROTECTIVE (FIRE DAMPER) IS
 REQUIRED AT WALL PENETRATION INTO GARAGE PER FBC,M
 607.5. REVISION REQUIRED TO SHOW THESE CORRECTIONS
 PRIOR TO ROUGH INSPECTION.
  