| Date |
Text |
| 2007-04-09 18:10:33 | |
| | ** UNSAT3RD REVIEW ** |
| | |
| | 11) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE ENERGY |
| | CALCULATIONS HAS NOT BEEN MET. |
| | ** PLEASE SEE THAT THIS IS THE FIRST TIME THAT ENERGY |
| | CALCULATIONS ARE BEING SUBMITTED FOR REVIEW. PLEASE SEE |
| | THERE ARE SEVERAL ITEMS ON CALCULATIONS WHICH DO NOT |
| | CORRELATE WITH PLANS. |
| | PLEASE SEE THE WATTAGES FOR MANY OF THE SAME FIXTURES |
| | ON PLANS ARE BEING SHOWN ON ENERGY CALCULATIONS AS |
| | DIFFERENT WATTAGES EVEN THOUGH IT'S THE SAME FIXTURE. |
| | ONE FIXTURE IS SHOWN WITH AS MANY AS THREE DIFFERENT |
| | FIGURES FOR WATTAGE. 26, 55, AND 62. |
| | PLEASE CLARIFY MISSING AREAS ON PLANS, WHICH ARE NOT IN |
| | CALCULATIONS. |
| | PLEASE SEE SOME AREAS ON PLANS DO NOT CORRELATE WITH |
| | THE SAME AMOUNT OF FIXTURES ON CALCULATIONS. PLEASE SEE |
| | THE NUMBER OF LIGHT FIXTURES IN SOME ROOMS ON PLANS |
| | SHOW FOR EXAMPLE THREE FIXTURES AND ENERGY CALCULATIONS |
| | SHOW TWO OR TWO ON PLANS AND ONE IN CALCULATIONS ETC. |
| | PLEASE SEE STORAGE ROOMS, STAIRS, SOME OFFICES WHICH |
| | CONTAIN THE EXACT SAME FIXTURES, YET SHOWN WITH |
| | DIFFERENT FIGURES ON CALCULATIONS. |
| | PLEASE CLARIFY WATTAGE USE IN CALCULATIONS WITH THAT OF |
| | THE FIXTURES. PLEASE SEE THE PLANS AND FIXTURE LEGEND |
| | CONTAINS FIXTURES AT ONE LEVEL OF WATTAGE AND THE |
| | ENERGY CALCULATIONS INDICATE A DIFFERENT WATTAGE? |
| | PLEASE GO THROUGH ALL ENERGY CALCULATIONS AS THERE ARE |
| | MANY OF THESE ITEMS WHICH CAN NOT BE LISTED ONE FOR |
| | ONE. |
| | |
| | PLEASE SEE 2004 FBC CHAPTER 13, 13-415.1.AB.1.1, |
| | 13-415.2 |
| | |
| | 2) NOTE: PLEASE SEE THE ELECTRICAL LIGHTING PLANSFOR |
| | FIRST AND SECOND FLOORS AND LIGHTING POWER DENSITY |
| | SHEETS DO NOT CORRELATE. |
| | PLEASE SEE SOME OF THE ROOM LAYOUTS AND LIGHTING |
| | LAYOUTS AND THE AMOUNT OF FIXTURES ON THESE SHEETS DO |
| | NOT CORRELATE. |
| | PLEASE SEE E1-01-101, E1-01-302, ETC. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE SOME SHEETS INDICATE THE ELECTRICAL |
| | ROOM ALSO BEING PART OF THE WATER METER ROOM IN THE |
| | SAME ROOM AND SOME SHEETS INDICATE THESE BEING IN TWO |
| | SEPARATE ROOMS? |
| | PLEASE SEE 110.26 AND ROOMS AND AREAS WHICH ARE |
| | REQUIRED TO BE DEDICATED ELECTRICAL SPACE. |
| | PLEASE COORDINATE SHEETS AND LAYOUTS FOR ROOMS/WALLS. |
| | PLEASE SEE E1-01-101, 302, 201 ETC |
| | |
| | 4) NOTE: PLEASE SEE THE PHOTO-METRIC TABLES ON THE SITE |
| | PLANS WHICH ARE NOT READABLE AT THIS TIME, PLEASE |
| | ADJUST THE SCALE ON PLANS FOR THIS. |
| | 106.1.2, 106.3.1 |
| | |
| | 5) NOTE:PLEASE SEE THE PANEL *A* IS BEING SHOWN WITH |
| | FEED-THRU LUGS TO PANEL *MA* WHICH INDICATES 200AMP |
| | OVER CURRENT PROTECTION ON 2/0 WHICH ARE ONLY RATED FOR |
| | 175AMPS. |
| | PLEASE SEE 310.16, 240.4. |
| | PLEASE SEE THE RISER SEEMS TO INDICATE THE CORRECT SIZE |
| | TO LEGEND ON PLANS. |
| | |
| | 6) NOTE: PLEASE SEE THAT LOAD CALCULATIONS ARE NOW |
| | BEING SUBMITTED FOR REVIEW FOR THE FIRST TIME. THESE |
| | COMPLETED CALCULATIONS WERE NOT SUBMITTED ON PREVIOUS |
| | PLANS. THE GENERAL VA PER SQ FT FOR RECEPTACLES MAY |
| | ONLY BE USED WHEN THE KNOWN NUMBER OF DEVICES IS NOT |
| | KNOWN. PLEASE SEE THAT THE PLANS DO HOWEVER INDICATE |
| | THE TOTAL NUMBER OF DEVICES THEREFORE THE MINIMUM |
| | REQUIRED VA IS TO BE BASED ON THE AMOUNT OF RECEPTACLES |
| | AT 180VA PER DEVICE. |
| | PLEASE SEE 220.13 AND ADJUST CALCULATIONS. |
| | |
| | 7) NOTE: PLEASE SEE THE LOADS SHOWN ON THE PANEL |
| | SCHEDULES FOR *Q, H AND A*ARE NOT THAT OF THE CONNECTED |
| | LOAD BEING SHOWN IN THE LOAD CALCULATIONS ON SHEET |
| | E0-00-01. |
| | PLEASE SEE THE LOAD ON THE *A* PANEL SEEMS TO BE VERY |
| | CLOSE TO LOAD PERMITTED ON THIS PANEL AND MAINS. PLEASE |
| | SEE 90.8 AS THERE DOES NOT SEEM TO BE MUSH ROOM FOR |
| | FUTURE LOADS OR CHANGES IN DESIGN. PLEASE REVIEW LOADS |
| | AND BE SURE LOADS DO NOT EXCEED RATING OF SERVICE AND |
| | CONSIDERATION IS TAKEN FOR ANY FUTURE LOADS. PLEASE |
| | ALSO SEE THE LOAD CALCULATIONS FOR WHAT APPEARS TO BE |
| | THE LOAD FOR THE ENTIRE SERVICE AS THESE ARE BEING |
| | LABELED FOR THE *QUANTUM* SERVICE. |
| | THIS SEEMS TO BE A MISPRINT FOR SERVICE. |
| | PLEASE SEE NEC 220. |
| | FBC 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE PANEL SCHEDULES WILL BE |
| | REQUIRED TO BE SPECIFIC TO LIST ALL CIRCUITS TO ROOMS |
| | AND AREAS IN WHICH THEY FEED. |
| | PLEASE SEE THE USE OF *GENERAL LIGHTING OR GENERAL |
| | RECEPTACLES* IS NOT ACCEPTABLE ANDWILL BE REQUIRED TO |
| | LIST ROOMS OR AREAS FOR WHICH THEY FEED. THIS MAY BE |
| | DONE BY OFFICE DESIGNATION BY NAME OR NUMERICAL |
| | IDENTIFICATION. |
| | A *PROVISO* (CONDITION OF ISSUANCE) MAY BE SET UP FOR |
| | THIS ITEM OR THIS MAY BE ADDRESSED AT THIS TIME. PLEASE |
| | SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE CODE |
| | COMMENTARY* |
| | *PROVISO* (CONDITION OF ISSUANCE) MAY BE SET UP FOR |
| | THIS ITEM. |
| | |
| | *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4, |
| | 310.16, 240.4 ETC |
| | |
| | 9) NOTE: PLEASE SEE THAT ONE SET OF ELECTRICAL PLANS |
| | AND ENERGY CALCULATIONS ARE BEING RETAINED BY THIS |
| | OFFICE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-04-08 13:59:49 | IN ELEC FOR REVIEW |