Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-09 18:10:33 
 ** UNSAT3RD REVIEW **
  
 11) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE ENERGY
 CALCULATIONS HAS NOT BEEN MET.
 ** PLEASE SEE THAT THIS IS THE FIRST TIME THAT ENERGY
 CALCULATIONS ARE BEING SUBMITTED FOR REVIEW. PLEASE SEE
 THERE ARE SEVERAL ITEMS ON CALCULATIONS WHICH DO NOT
 CORRELATE WITH PLANS.
 PLEASE SEE THE WATTAGES FOR MANY OF THE SAME FIXTURES
 ON PLANS ARE BEING SHOWN ON ENERGY CALCULATIONS AS
 DIFFERENT WATTAGES EVEN THOUGH IT'S THE SAME FIXTURE.
 ONE FIXTURE IS SHOWN WITH AS MANY AS THREE DIFFERENT
 FIGURES FOR WATTAGE. 26, 55, AND 62.
 PLEASE CLARIFY MISSING AREAS ON PLANS, WHICH ARE NOT IN
 CALCULATIONS.
 PLEASE SEE SOME AREAS ON PLANS DO NOT CORRELATE WITH
 THE SAME AMOUNT OF FIXTURES ON CALCULATIONS. PLEASE SEE
 THE NUMBER OF LIGHT FIXTURES IN SOME ROOMS ON PLANS
 SHOW FOR EXAMPLE THREE FIXTURES AND ENERGY CALCULATIONS
 SHOW TWO OR TWO ON PLANS AND ONE IN CALCULATIONS ETC.
 PLEASE SEE STORAGE ROOMS, STAIRS, SOME OFFICES WHICH
 CONTAIN THE EXACT SAME FIXTURES, YET SHOWN WITH
 DIFFERENT FIGURES ON CALCULATIONS.
 PLEASE CLARIFY WATTAGE USE IN CALCULATIONS WITH THAT OF
 THE FIXTURES. PLEASE SEE THE PLANS AND FIXTURE LEGEND
 CONTAINS FIXTURES AT ONE LEVEL OF WATTAGE AND THE
 ENERGY CALCULATIONS INDICATE A DIFFERENT WATTAGE?
 PLEASE GO THROUGH ALL ENERGY CALCULATIONS AS THERE ARE
 MANY OF THESE ITEMS WHICH CAN NOT BE LISTED ONE FOR
 ONE.
  
 PLEASE SEE 2004 FBC CHAPTER 13, 13-415.1.AB.1.1,
 13-415.2
  
 2) NOTE: PLEASE SEE THE ELECTRICAL LIGHTING PLANSFOR
 FIRST AND SECOND FLOORS AND LIGHTING POWER DENSITY
 SHEETS DO NOT CORRELATE.
 PLEASE SEE SOME OF THE ROOM LAYOUTS AND LIGHTING
 LAYOUTS AND THE AMOUNT OF FIXTURES ON THESE SHEETS DO
 NOT CORRELATE.
 PLEASE SEE E1-01-101, E1-01-302, ETC.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE SOME SHEETS INDICATE THE ELECTRICAL
 ROOM ALSO BEING PART OF THE WATER METER ROOM IN THE
 SAME ROOM AND SOME SHEETS INDICATE THESE BEING IN TWO
 SEPARATE ROOMS?
 PLEASE SEE 110.26 AND ROOMS AND AREAS WHICH ARE
 REQUIRED TO BE DEDICATED ELECTRICAL SPACE.
 PLEASE COORDINATE SHEETS AND LAYOUTS FOR ROOMS/WALLS.
 PLEASE SEE E1-01-101, 302, 201 ETC
  
 4) NOTE: PLEASE SEE THE PHOTO-METRIC TABLES ON THE SITE
 PLANS WHICH ARE NOT READABLE AT THIS TIME, PLEASE
 ADJUST THE SCALE ON PLANS FOR THIS.
 106.1.2, 106.3.1
  
 5) NOTE:PLEASE SEE THE PANEL *A* IS BEING SHOWN WITH
 FEED-THRU LUGS TO PANEL *MA* WHICH INDICATES 200AMP
 OVER CURRENT PROTECTION ON 2/0 WHICH ARE ONLY RATED FOR
 175AMPS.
 PLEASE SEE 310.16, 240.4.
 PLEASE SEE THE RISER SEEMS TO INDICATE THE CORRECT SIZE
 TO LEGEND ON PLANS.
  
 6) NOTE: PLEASE SEE THAT LOAD CALCULATIONS ARE NOW
 BEING SUBMITTED FOR REVIEW FOR THE FIRST TIME. THESE
 COMPLETED CALCULATIONS WERE NOT SUBMITTED ON PREVIOUS
 PLANS. THE GENERAL VA PER SQ FT FOR RECEPTACLES MAY
 ONLY BE USED WHEN THE KNOWN NUMBER OF DEVICES IS NOT
 KNOWN. PLEASE SEE THAT THE PLANS DO HOWEVER INDICATE
 THE TOTAL NUMBER OF DEVICES THEREFORE THE MINIMUM
 REQUIRED VA IS TO BE BASED ON THE AMOUNT OF RECEPTACLES
 AT 180VA PER DEVICE.
 PLEASE SEE 220.13 AND ADJUST CALCULATIONS.
  
 7) NOTE: PLEASE SEE THE LOADS SHOWN ON THE PANEL
 SCHEDULES FOR *Q, H AND A*ARE NOT THAT OF THE CONNECTED
 LOAD BEING SHOWN IN THE LOAD CALCULATIONS ON SHEET
 E0-00-01.
 PLEASE SEE THE LOAD ON THE *A* PANEL SEEMS TO BE VERY
 CLOSE TO LOAD PERMITTED ON THIS PANEL AND MAINS. PLEASE
 SEE 90.8 AS THERE DOES NOT SEEM TO BE MUSH ROOM FOR
 FUTURE LOADS OR CHANGES IN DESIGN. PLEASE REVIEW LOADS
 AND BE SURE LOADS DO NOT EXCEED RATING OF SERVICE AND
 CONSIDERATION IS TAKEN FOR ANY FUTURE LOADS. PLEASE
 ALSO SEE THE LOAD CALCULATIONS FOR WHAT APPEARS TO BE
 THE LOAD FOR THE ENTIRE SERVICE AS THESE ARE BEING
 LABELED FOR THE *QUANTUM* SERVICE.
 THIS SEEMS TO BE A MISPRINT FOR SERVICE.
 PLEASE SEE NEC 220.
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SEE THE PANEL SCHEDULES WILL BE
 REQUIRED TO BE SPECIFIC TO LIST ALL CIRCUITS TO ROOMS
 AND AREAS IN WHICH THEY FEED.
 PLEASE SEE THE USE OF *GENERAL LIGHTING OR GENERAL
 RECEPTACLES* IS NOT ACCEPTABLE ANDWILL BE REQUIRED TO
 LIST ROOMS OR AREAS FOR WHICH THEY FEED. THIS MAY BE
 DONE BY OFFICE DESIGNATION BY NAME OR NUMERICAL
 IDENTIFICATION.
 A *PROVISO* (CONDITION OF ISSUANCE) MAY BE SET UP FOR
 THIS ITEM OR THIS MAY BE ADDRESSED AT THIS TIME. PLEASE
 SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE CODE
 COMMENTARY*
 *PROVISO* (CONDITION OF ISSUANCE) MAY BE SET UP FOR
 THIS ITEM.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
  
 9) NOTE: PLEASE SEE THAT ONE SET OF ELECTRICAL PLANS
 AND ENERGY CALCULATIONS ARE BEING RETAINED BY THIS
 OFFICE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II