| 2007-02-07 10:22:54 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. DELETED |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. DELETED |
| | 7. OK |
| | |
| | 8. SHT A7-01-101 ELEVATION 1 KITCHEN |
| | SINK TO COMPLY WITH SECTION 11-4.24 AND |
| | ALL SUBSECTIONS. SHOW ON DETAIL. |
| | ****RESPONSE NOTED, INFORMATION STILL REQUIRED. SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | A. 11-4.24.2 HEIGHT |
| | B. 11-4.24.3 KNEE CLEARANCE |
| | C. 11-4.24.4 SINK DEPTH |
| | D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH |
| | REQUIRED. SHOW ON THE FLOOR PLAN OF SHT A9-03-101 TO |
| | SEE IF FURNITURE WILL CONFLICT WITH THE CLEAR FLOOR |
| | SPACE. |
| | E. 11-4.24.7 FAUCETS. |
| | |
| | 9.OK |
| | 10. OK |
| | |
| | 11. SHT A7-02-101 ELEVATION 13, STAFF |
| | SINK SHALL COMPLY WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. SUBMIT INFORMATION |
| | ON DETAIL. |
| | ****RESPONSE NOTED, BUT SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. SHOW COMPLIANCE WITH THE FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH |
| | REQUIRED. SHOW ON THE FLOOR PLAN OF SHT A9-03-101 TO |
| | SEE IF FURNITURE WILL CONFLICT WITH THE CLEAR FLOOR |
| | SPACE. |
| | D. 11-4.24.7 FAUCETS. |
| | |
| | 12. SHTS A9-01-201 & AP-02-201 ROOMS |
| | 108, 126, 127, 205, 206, 214. TOILET |
| | ROOM FLOORS & WALLS SHALL BE SMOOTH, |
| | HARD AND NONABSORBENT PER SECTIONS |
| | 1210.1 & 1210.2. THE BASE IS INDICATED |
| | AS T2 WHICH IS NOT SHOWN UNDER THE BASE INFORMATION, |
| | BUT AS "TBD" UNDER THE |
| | FLOOR INFORMATION. WALLS ARE INDICATED |
| | AS P5 OR P6. PLEASE SUBMIT INFORMATION |
| | SHOWING HOW A PAINTED WALL CAN COMPLY |
| | WITH REQUIREMENTS OF "HARD & |
| | NONABSORBENT". SHOW BASE MATERIAL. |
| | ****RESPONSE NOTED, BUT ROOM 108 STILL SHOWS PAINT ON |
| | THE EAST WALL. SECTION 1210.2 STATES "WALLS WITHIN 2' |
| | OF URINALS AND WATER CLOSETS".--THE FINISH SCHEDULE |
| | DOES NOT SHOW T1 IN THE BASE INFORMATION, NOR DOES IT |
| | SHOW T1/T3 IN THE WALL INFORMATION.--ROOM 205 SHOWS |
| | T1/T3 ON THE NORTH & SOUTH WALLS, BUT IT IS REQUIRED ON |
| | THE SOUTH, EAST, & WEST WALLS.--ROOM 206 SHOWS |
| | T1/T3 ON THE NORTH & SOUTH WALLS, BUT IT IS REQUIRED ON |
| | THE NORTH, EAST & WEST WALLS.--ROOM 214 SHOWS T1/T3 |
| | ON THE EAST WALL ONLY, BUT IT IS ALSO REQUIRED ON THE |
| | SOUTH WALL. PLEASE INDICATE THE REQUIRED FINISH ON THE |
| | REQUIRED WALLS.--PLEASE UPDATE THE FINISH SCHEDULES |
| | TO INCLUDE THE FINISH SHOWN ON THE BASE & WALLS. |
| | |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | |
| | **************NEW COMMENT************* |
| | |
| | 1B. SHT P1-01-101 INDICATES A SHOWER TRAP IN THE |
| | CEILING OF THE ELECTRIC METER ROOM. THIS IS NOT |
| | APPROVED PER NFPA 70 SECTION 110.26.--THIS SHEET |
| | ALSO INDICATES A DRAIN PAN UNDER THE PIPING DISCHARGING |
| | TO THE GARAGE. THIS WILL BE WASTE WATER AND CAN NOT |
| | DRAIN TO THE GARAGE. ALL PLUMBING FIXTURES, DRAINS, |
| | APPURTENANCES AND APPLIANCES USED TO RECEIVE OR |
| | DISCHARGE LIQUID WASTES OR SEWAGE SHALL BE DIRECTLY |
| | CONNCETED TO THE SANITARY DRAINAGE SYSTEM. SECTION |
| | 301.3. |
| | |