Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop P
Sequence Number 2
Notes
Date Text
2007-02-07 10:22:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. DELETED
 2. OK
 3. OK
 4. OK
 5. OK
 6. DELETED
 7. OK
  
 8. SHT A7-01-101 ELEVATION 1 KITCHEN
 SINK TO COMPLY WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. SHOW ON DETAIL.
 ****RESPONSE NOTED, INFORMATION STILL REQUIRED. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED. SHOW ON THE FLOOR PLAN OF SHT A9-03-101 TO
 SEE IF FURNITURE WILL CONFLICT WITH THE CLEAR FLOOR
 SPACE.
 E. 11-4.24.7 FAUCETS.
  
 9.OK
 10. OK
  
 11. SHT A7-02-101 ELEVATION 13, STAFF
 SINK SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. SUBMIT INFORMATION
 ON DETAIL.
 ****RESPONSE NOTED, BUT SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED. SHOW ON THE FLOOR PLAN OF SHT A9-03-101 TO
 SEE IF FURNITURE WILL CONFLICT WITH THE CLEAR FLOOR
 SPACE.
 D. 11-4.24.7 FAUCETS.
  
 12. SHTS A9-01-201 & AP-02-201 ROOMS
 108, 126, 127, 205, 206, 214. TOILET
 ROOM FLOORS & WALLS SHALL BE SMOOTH,
 HARD AND NONABSORBENT PER SECTIONS
 1210.1 & 1210.2. THE BASE IS INDICATED
 AS T2 WHICH IS NOT SHOWN UNDER THE BASE INFORMATION,
 BUT AS "TBD" UNDER THE
 FLOOR INFORMATION. WALLS ARE INDICATED
 AS P5 OR P6. PLEASE SUBMIT INFORMATION
 SHOWING HOW A PAINTED WALL CAN COMPLY
 WITH REQUIREMENTS OF "HARD &
 NONABSORBENT". SHOW BASE MATERIAL.
 ****RESPONSE NOTED, BUT ROOM 108 STILL SHOWS PAINT ON
 THE EAST WALL. SECTION 1210.2 STATES "WALLS WITHIN 2'
 OF URINALS AND WATER CLOSETS".--THE FINISH SCHEDULE
 DOES NOT SHOW T1 IN THE BASE INFORMATION, NOR DOES IT
 SHOW T1/T3 IN THE WALL INFORMATION.--ROOM 205 SHOWS
 T1/T3 ON THE NORTH & SOUTH WALLS, BUT IT IS REQUIRED ON
 THE SOUTH, EAST, & WEST WALLS.--ROOM 206 SHOWS
 T1/T3 ON THE NORTH & SOUTH WALLS, BUT IT IS REQUIRED ON
 THE NORTH, EAST & WEST WALLS.--ROOM 214 SHOWS T1/T3
 ON THE EAST WALL ONLY, BUT IT IS ALSO REQUIRED ON THE
 SOUTH WALL. PLEASE INDICATE THE REQUIRED FINISH ON THE
 REQUIRED WALLS.--PLEASE UPDATE THE FINISH SCHEDULES
 TO INCLUDE THE FINISH SHOWN ON THE BASE & WALLS.
  
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
  
 **************NEW COMMENT*************
  
 1B. SHT P1-01-101 INDICATES A SHOWER TRAP IN THE
 CEILING OF THE ELECTRIC METER ROOM. THIS IS NOT
 APPROVED PER NFPA 70 SECTION 110.26.--THIS SHEET
 ALSO INDICATES A DRAIN PAN UNDER THE PIPING DISCHARGING
 TO THE GARAGE. THIS WILL BE WASTE WATER AND CAN NOT
 DRAIN TO THE GARAGE. ALL PLUMBING FIXTURES, DRAINS,
 APPURTENANCES AND APPLIANCES USED TO RECEIVE OR
 DISCHARGE LIQUID WASTES OR SEWAGE SHALL BE DIRECTLY
 CONNCETED TO THE SANITARY DRAINAGE SYSTEM. SECTION
 301.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731