| 2007-01-15 14:25:18 | |
| | |
| | *** UNSAT 2ND REVIEW*** |
| | |
| | AMERICAN LUNG ASSOCIATION |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS BASED |
| | ON CHANGES MADE TO PLANS. |
| | PLEASE KNOW THAT THERE NEW COMMENTS BASED ON PLANS AND |
| | CHANGES MADE. |
| | |
| | ** PLEASE KNOW THAT BASED ON THE LAST MEETING HELD, THE |
| | ARCHITECT WAS PRESENT HOWEVER NO CONTACT TO DATE HAS |
| | BEEN MADE BY THE ENGINEERING DESIGNER(S) TO GO OVER |
| | COMMENTS. |
| | |
| | ** PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY |
| | FROM PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER. THEY |
| | WILL CONTAIN A NO, OK, OR NO/OK. |
| | A) NO WILL BE FOLLOWED BY FURTHER EXPLANATION OF THE |
| | PREVIOUS COMMENT. |
| | B) OK, MAY REFERENCE TO ANY NEW NOTES, HOWEVER WILL |
| | HAVE PREVIOUS NOTE REMOVED. |
| | C) NO/OK, WILL BE FOLLOWED BY FURTHER EXPLANATION AS |
| | PART OF THE COMMENT MAY NOT HAVE BEEN ADDRESSED FULLY |
| | AND PART OF THE PREVIOUS COMMENT MAY BE OK. |
| | D) OK/N/A, AS THE PREVIOUS NOTE DOES NOT APPLY ANY |
| | FURTHER AS PLANS HAVE DELETED OR CHANGED. |
| | |
| | ** ANY NEW NOTES WILL BE AT THE BOTTOM AND IDENTIFIED |
| | AS *** NEW NOTES ***. |
| | |
| | |
| | |
| | |
| | 1) NOTE: NO/OK. PLEASE SEE THE ENGINEERING BUSINESS |
| | NUMBER WAS VERIFIED WITH THE STATE, HOWEVER PLEASE SEE |
| | THE ADDRESS FOR FIRM ON THE STATE'S WEBSITE AND PLANS |
| | DIFFER. A FAR AS WE HAVE BEEN INFORMED FROM THE STATE, |
| | THIS INFORMATION IS REQUIRED TO MATCH. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING REQUIRED LICENSE INFORMATION ON |
| | TITLE BLOCKS. |
| | PLEASE SEE FAC 61G15-23.002 AND FS |
| | 471.023. |
| | PLEASE KNOW PER THE FLORIDA STATUES AS NOTED ABOVE AND |
| | PER THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS, ANY |
| | FIRM PRACTICING ENGINEERING AND OFFERING ENGINEERING |
| | SERVICES MUST ALSO OBTAIN A CERTIFICATE OF |
| | AUTHORIZATION NUMBER FOR THE ENGINEERING PART OF THE |
| | BUSINESS. |
| | PLEASE SEE THE FIRM NUMBER AS SHOWN IS ONLY LICENSED |
| | FOR THE ARCHITECTURAL FIRM. |
| | PLEASE ALSO SEE ADDRESS ON TITLE BLOCK DO NOT CORRELATE |
| | WITH THE ADDRESS AS LISTED ON THE STATE'S DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION. |
| | PLEASE SEE THE ATTACHED PRINT OUT ATTACHED TO |
| | ELECTRICAL NOTES. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2) NOTE: OK/NO, PLEASE SEE THIS WAS DONE HOWEVER THIS |
| | INFORMATION WAS HAND WRITTEN ON SHEETS WHICH IS OK. THE |
| | COMMENT WILL REMAIN AS NEW SHEETS WILL ALSO BE REQUIRED |
| | TO CONTAIN THIS INFORMATION. THIS IS SOMETHING THAT |
| | SHOULD BE ADDED INTO THE FIRMS CADD OR COMPUTER SYSTEMS |
| | SO THAT THIS INFORMATION DOES NOT HAVE TO BE |
| | HANDWRITTEN ON ALL SHEETS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| | FOR THE ENGINEER OF RECORD ON SAID TITLE BLOCKS AS |
| | REQUIRED UNDER FAC 61G15-23.002 |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK, N/A |
| | |
| | 6) NOTE: OK, AS THE GEN HAS BEEN REMOVED AND NOTES |
| | BEING DONE AS FUTURE, HOWEVER PLEASE SEE THESE SECTIONS |
| | AND PREVIOUS NOTES ARE BEING LEFT FOR INFORMATIONAL |
| | REASONS FOR THE PANEL E WHICH IS BEING SHOWN AS FUTURE |
| | WHICH DOES NOT SEEM TO MEET THESE SECTIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 225.31-225.39 FOR MISSING REQUIRED MEANS OF |
| | DISCONNECT FOR THE FEEDERS FROM THE GENERATOR UNIT. |
| | PLEASE SEE GROUPING ETC AS REQUIRED. |
| | |
| | |
| | 7) NOTE: OK, HOWEVER SEE NEW NOTES WITH RESPECT TO GAP, |
| | FACP AND FAAP. |
| | |
| | 8) NOTE: OK, N/A. SEE NEW NOTES HOWEVER FOR PANEL H. |
| | |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK, N/A. |
| | |
| | 11) NOTE: OK, N/A. |
| | |
| | 12) NOTE: OK/NO, PLEASE SEE THESE ITEMS WERE ADDED, |
| | HOWEVER PLEASE SEE MISSING CIRCUITING FOR THE ROOF TOP |
| | GFI'S. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING DISCONNECTS FOR RTU'S WHICH COULD |
| | NOT BE LOCATED ON PLANS. CAN BE TYPICAL IF THE SAME. |
| | 440.11 |
| | PLEASE ALSO SEE MISSING ROOF TOP GFI'S WHICH COULD NOT |
| | BE LOCATED ON PLANS FOR ROOF. |
| | 230.63, 210.8 |
| | |
| | 13) NOTE: NO, PLEASE SEE PLANS AS THE INTENTION SEEMS |
| | TO HAVE BEEN MADE, BUT PLEASE SEE THAT THERE ARE LINES |
| | FOR CIRCUITING WHICH STILL PLACES THE LIGHTING ON WITH |
| | OTHER HOUSE CIRCUITS AND OTHER AREAS WHICH IS NOT |
| | PERMITTED. PLEASE SEE SECTIONS AS NOTED REQUIRE |
| | DEDICATED CIRCUITS WHICH MAY NOT FEED OTHER AREAS. |
| | PLEASE SEE NOTE FOR CONTROL OF PIT LTS. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE MISSING THE REQUIRED DEDICATED CIRCUITS FOR |
| | THE ELEVATOR MACHINE ROOM. |
| | 620.23, 620.24 |
| | |
| | 14) NOTE:OK, HOWEVER SEE NEW NOTES FOR EMERGENCY |
| | LIGHTING. |
| | |
| | 15) NOTE:NO, PLEASE SEE ALL DEVICES AS NOTED AND |
| | SHOWN ON PLANS SHALL INDICATE ALL OF THE MAXIMUM TIMES. |
| | ONLY ONE SYMBOL ON LEGEND CONTAINS THE INFORMATION AS |
| | NEEDED. |
| | PLEASE SEE ELEVATOR PIT LIGHTS WHICH APPEAR TO BE |
| | MISSING CONTROL(S). |
| | PLEASE CALL F THERE ARE ANY QUESTIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SPECIFY THE MAX OVER RIDE TIMES FOR THE OCCUPANT |
| | SENSORS. |
| | 30MIN MAX FOR SENSORS AND 4HRS MAX FOR TIMER TYPE OVER |
| | RIDES. |
| | PLEASE ALSO SEE SEPARATE SPACES/ROOMS WHICH SEEM TO BE |
| | MISSING OVER RIDE CONTROLS. |
| | PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, |
| | .1.3 |
| | |
| | 16) NOTE:NO, PLEASE SEE THAT IT APPEARS BASED ON THE |
| | RESPONSE FROM THE DESIGN TEAM THAT THIS COMMENT WAS NOT |
| | UNDERSTOOD. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED SHOWING |
| | METHOD A, INDICATES ALL LIGHTING BEING CONTROLLED AS |
| | "MANUAL ON/OFF". THIS IS NOT POSSIBLE IF THERE ARE |
| | AUTOMATED CONTROL LIGHTING SYSTEMS AND AUTOMATED |
| | DEVICES/OCCUPANCY SENSORS ETC. |
| | 13-415.1.ABC.1.1, .1.2, AND .1.3. 13-415.2. ETC. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY HOW THE ENERGY CALCULATIONS SUBMITTED ALL |
| | MENTIONS AND CONTAIN "MANUAL ON/OFF" CONTROLS FOR |
| | LIGHTING?? |
| | PLEASE SEE METHODS REQUIRED PER 13-415.1.AB.1. |
| | |
| | 17) NOTE:NO, PLEASE SEE BASED ON THE RESPONSE IT |
| | MENTIONS TO SEE LIGHTING PHOTO-METRICS?? PLEASE KNOW |
| | THAT PHOTO-METRICS AND LIGHTING POWER DENSITIES AND |
| | PERFORMANCE CALCULATIONS A RE COMPLETELY DIFFERENT |
| | ITEMS. |
| | PLEASE SUBMIT PER SECTIONS GIVEN IN PREVIOUS REVIEW |
| | NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT LIGHTING POWER DENSITY CALCULATIONS AS |
| | REQUIRED. 13-415.1.AB.1,13 ,415.2.ABC.1 AND TABLES |
| | 415.2.C.1 AND 415.2.B.1 (WHERE APPLICABLE) |
| | |
| | 18) NOTE: OK. |
| | |
| | 20) NOTE: OK, HOWEVER THIS NOTE WILL REMAIN AS BASED ON |
| | THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS, THE LOAD |
| | CALCULATIONS SUBMITTED THIS MAY BE CHANGED AND/OR |
| | INCREASED. SEE COMMENTS AS THIS PREVIOUS NOTE WILL |
| | REMAIN AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 250.66 FOR MIN SIZING OF THE GEC. APPEARS |
| | THIS SHOULD BE 2/0 MIN. |
| | |
| | 21) NOTE: NO, PLEASE SEE AS NOTED ABOVE THIS STILL |
| | SEEMS TO BE IN QUESTION. PLEASE SEE SOME COMMON AREAS |
| | WHICH ARE NOT FED FROM HOUSE PANELS, PLEASE SEE OTHER |
| | AREAS LIKE THE ROOF TOP WHICH IS BEING FED FROM HOUSE |
| | PANEL AND QQ PANELS FOR STAIRS. PLEASE SEE NOTES FOR |
| | ELEVATOR ROOMS WHICH ARE BEING FED FROM HOUSE AND |
| | TENANT PANELS. |
| | THIS SCENARIO ON PLANS AS SHOWN IS NOT CLEAR. PLEASE |
| | SEE THERE SEEMS TO BE AN ELECTRICAL ROOM ON FIRST FLOOR |
| | WHICH REVIEW OF 240.24 SHOULD BE NOTED AND ADJUST PLANS |
| | AS NEEDED. |
| | PLEASE MAKE OTHER ADJUSTMENTS AS ROOF TOP ACCESS SEEMS |
| | TO BE ONLY ACCESSIBLE THROUGH WHAT IT BEING SHOWN AS |
| | STAIRWAYS FOR THE 2ND FLR TENANT ONLY. IF THESE |
| | STAIRWAYS OR A STAIRWAY IS BEING USED FOR COMMON USE, |
| | THEN THE ONE OR MORE BEING USED SHALL BE CIRCUITED FORM |
| | THE HOUSE COMMON AREA PANEL/EQUIPMENT. |
| | PLEASE ALSO SEE BOLLARDS BEING SHOWN ON ROOF?, AND |
| | BEING SHOWN FROM HOUSE WHICH IS OK, HOWEVER NOT CLEAR |
| | WHY THERE ARE BOLLARD TYPE FIXTURES ON ROOF? PLEASE |
| | KNOW THAT AS PLANS ARE NOT CLEAR AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY THE SEPARATION OF TENANTS. PLEASE SEE |
| | PLANS AS SHOWN HAS CIRCUITING FROM EACH TENANT SERVICE |
| | CROSSING OVER INTO OTHER TENANT'S AREAS AND ROOMS. IF |
| | THE BUILDINGS GOING TO HAVE "HOUSE" POWER THESE MAY NOT |
| | FEED INTO TENANT SPACES. PLEASE ALSO SEE |
| | CIRCUITS FOR UPPER TENANT MAY NOT FEED AREAS IN LOWER |
| | TENANTS. PLEASE SEE PROPER TENANT SEPARATION AND |
| | CROSSING OVER OF CIRCUITS AND COMMON AREAS. PLEASE |
| | ADJUST CIRCUITING ON PLANS. |
| | PLEASE SEE "HOUSE" PANELS LOCATED ON FIRST FLR TENANTS |
| | SPACE? |
| | THIS IS UNCLEAR WHAT IS BEING PROPOSED IN THIS DESIGN |
| | |
| | 22) NOTE: NO, PLEASE SEE NEW COMMENTS AS THE RISER HAS |
| | COMPLETELY CHANGED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE AS KNOW "SCHEDULE WAS SUBMITTED FOR THE |
| | 800A BUS/METER CENTER, PLEASE INDICATE THE CONDUCTORS |
| | FROM THE MAIN BUS TO EACH OF THE ATS UNITS. |
| | 215.5, 240.4,310.16 |
| | |
| | 23) NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | 24) NOTE: OK/NO, CIRCUITS ARE BEING SHOWN, HOWEVER |
| | COMING FROM HOUSE PANEL? PLEASE SEE 600.5 AND THE |
| | REQUIRED DEDICATED CIRCUITS. THIS CIRCUIT AS SHOWN ON |
| | PLANS COMES NOT ONLY FROM THE HOUSE PANEL; IT IS ALSO |
| | SHOWN FEEDING OTHER AREAS OF LIGHTING. PLEASE SEE 600.5 |
| | REFERENCES TO 220.3(B)6 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY NEW OR EXISTING REQUIRED SIGN CIRCUIT PER |
| | 600.5 |
| | |
| | 25) NOTE: NO, PLEASE SEE LOAD CALCULATIONS ARE NOT |
| | COMPLETE PER NEC AND CODE SECTIONS GIVEN. |
| | PLEASE ALSO SEE NEW NOTES BASED ON THE LOADS ALREADY |
| | SHOWN WHICH EXCEED THE RATING OF THE SERVICE ENTRANCE |
| | CONDUCTORS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY AND SHOW LOAD CALCULATIONS FOR SERVICE |
| | AND GENERATOR. |
| | PLEASE SEE 220.3,220.10,220.11,220.13, ETC |
| | PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.215.3,230.42 |
| | |
| | 26) NOTE: OK,N/A. |
| | |
| | 27) NOTE: OK, N/A. |
| | |
| | 28) NOTE: NO, SEE NEW NOTES FROM THIS REVIEWER. |
| | |
| | PLEASE SEE POSSIBLE FIRE AND BUILDING REVIEW COMMENTS |
| | AS IT DID NOT SEEM PLANS WERE SUBMITTED FOR ANY |
| | BUILDING FIRE ALARM SYSTEM? |
| | |
| | **** NEW NOTES ****** |
| | |
| | |
| | 29) NOTE: PLEASE SEE PANELS MH, MA, H, MQ ETC ALL LIST |
| | FEEDS TO AUTOMATIC TRANSFER SWITCHES WHICH ARE NOT ON |
| | RISER. THESE ARE NOT THE ATS DEVICES WHICH ARE SHOWN ON |
| | RISER WHICH ARE NOTED AS FUTURE ON THE LINE SIDE OF |
| | THESE PANELS. |
| | PLEASE ALSO SEE ONE IS STILL BEING SHOWN AS LS /ATS FOR |
| | LIFE SAFETY. PLEASE SEE IF THERE ARE LEGALLY REQUIRED |
| | SYSTEMS OR LIFE SAFETY SYSTEMS, PLEASE REVISE PLANS. |
| | PLEASE CLARIFY ALL OF THESE. REVIEW FOR ANY CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME AS PLANS ARE |
| | CONFUSING AND ARE NOT CLEAR OF INTENTIONS, CODES AND |
| | DESIGNS AS SHOWN. |
| | PLEASE SUBMIT ALL MANUFACTURE'S SPEC/CUT SHEETS FOR ANY |
| | PROPOSED SWITCHES TO BE INSTALLED AT THIS TIME. 110.3, |
| | 90.7. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | 30) NOTE: PLEASE SEE THAT THE MEN'S AND WOMEN'S |
| | BATHROOM WHICH ARE NOT SINGLE OCCUPANT OR SINGLE POINT |
| | OF USE SHALL CONTAIN A BATTERY BACK UP LIGHT FIXTURE OF |
| | SOME KIND. |
| | PLEASE ALSO SEE UPPER STAIRS WHICH DO NOT INDICATE |
| | BATTERY BACK UP FIXTURES. |
| | PLEASE SEE PARKING GARAGE AREA FOR EGRESS TO THE PUBLIC |
| | RIGHT OF WAY. |
| | PLEASE SEE LS 101 7.8.1.3, AND 7.9.2.2. |
| | PLEASE KNOW THE LIGHTING LEVELS ON STAIRS SHALL MEET |
| | 10FT UNDER NORMAL AND 1FT CANDLED UNDER EM. |
| | |
| | 31) NOTE: PLEASE SEE THAT THESE PLANS SHALL CONTAIN A |
| | BASE LAYOUT FOR ALL FIRE ALARM DEVICES TO REVIEW FOR |
| | ADA COMPLIANCE. PLEASE SEE THE NOTE BEING PLACED ON THE |
| | PLANS CAN NOT BE ACCEPTED. PLEASE KNOW THAT EVEN THOUGH |
| | THE FIRE ALARM AND ANY FIRE SPRINKLER WILL BE REQUIRED |
| | UNDER A SEPARATE PERMIT THESE BASE SYSTEMS ARE STILL |
| | REQUIRED ON BASE BUILDING PLANS. |
| | THIS WAS NOT A COMMENT ON THIS REVIEWER'S PREVIOUS |
| | REVIEW; HOWEVER IT HAS NOW BECOME PART OF THE |
| | ELECTRICAL REVIEW SINCE THESE PLANS WERE PREVIOUSLY |
| | REVIEWED. PLEASE SEE COMPLIANCE FOR MINIMUM STROBE AND |
| | SOUNDING DEVICE LEVELS SHALL BE STATED AND LOCATIONS |
| | SHOWN. |
| | PLEASE SEE 11-4.28.1, .2, AND.3(4). |
| | FBC ADMIN SECTION 106.3.5.1.2 |
| | |
| | 32) NOTE: PLEASE CLARIFY PANELS H, A AND Q AS BEING |
| | NOTED AS SERVICE ENTRANCE RATED. HOW IS THIS POSSIBLE |
| | WHEN THESE ARE ALL BEING SHOWN AS MLO? |
| | PLEASE ALSO EXPLAIN. |
| | 106.1.2, 106.3.5.1.2, NEC 230.70, 110.3, 90.7 |
| | |
| | 33) NOTE: PLEASE SUBMIT MANUFACTURE'S SPEC/CUT SHEETS |
| | ON THE PROPOSED SERVICE AS SHOWN ON RISER. THIS 800A |
| | RATED BUS WHICH SHOWS NO MAIN, YET SHOWS SEPARATE |
| | METERS AND MAINS FOR EACH TENANT AND HOUSE IS NOT |
| | CLEAR. |
| | IT MAY SEEM THAT THIS EQUIPMENT MAY BE REQUIRED TO |
| | CONTAIN A MAIN? (IF APPLICABLE) |
| | PLEASE SUBMIT MORE INFORMATION. FBC 106.1.2, |
| | 106.3.5.1.2 |
| | NEC 110.3, 90.7, 230.70, ETC |
| | |
| | 34) NOTE: PLEASE SEE BASED ON THE LOAD CALCULATIONS |
| | SUBMITTED AND NOTED ABOVE IN NOTE #25, THE SEC'S ARE |
| | NOT LARGE ENOUGH FOR THE LOADS AS SHOWN. PLEASE ALSO |
| | KNOW BASED ON THESE LOADS SHOWN AND SOME LOADS WHICH |
| | ARE REQUIRED WHICH HAVE NOT YET BEEN ADDED OR SHOWN THE |
| | SIZING OF THESE CAN NOT BE VERIFIED FOR CODE COMPLIANCE |
| | AT THIS TIME. |
| | PLEASE ALSO SEE NOTE ABOVE AS IF THE EQUIPMENT CHANGES |
| | SOME OTHER CODE SECTIONS MAY ALSO APPLY FOR DEVICES |
| | RATED OVER 800AMPS. |
| | PLEASE SEE 240.4, 310.16, 230.70, 230.76, 230.79, |
| | 230.90, 230.91 ETC |
| | |
| | 35) NOTE: PLEASE SUBMIT WIND LOADS FOR NEW SITE |
| | LIGHTING POLES AS SHOWN. THESE SHALL INDICATE THE |
| | MINIMUM LEVELS PER FBC 140MPH 3-SEC GUST (120 |
| | SUSTAINED) AND INDICATE THE EPA OF FIXTURES FOR THE |
| | POLE BEING STATED. |
| | PLEASE KNOW THIS WILL BE REVIEWED FURTHER BY THE |
| | BUILDING REVIEWER. |
| | |
| | 36) NOTE: PLEASE KNOW CONTACT WITH THE FIRE MARSHAL'S |
| | OFFICE SHOULD BE MADE FOR COORDINATION OF THE LOCATIONS |
| | OF THE FACP, GAP(FUTURE) AND FAAP. |
| | |
| | 37) NOTE: PLEASE KNOW THIS IS BEING NOTED ONLY AS PANEL |
| | E IS NOT UNDER THIS PERMIT. THE BREAKER IS BEING SHOWN |
| | FOR ATS-LS.? |
| | THIS IS ONLY BEING NOTED. |
| | |
| | 38) NOTE: PLEASE SEE ATTACHED REFERENCE TO FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN PROFESSIONALS AND |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | ** PLEASE KNOW AS THERE MAY BE COMMENTS ON THE NEXT |
| | REVIEW BASED ON INFORMATION NOT SHOWN OR CHANGES WHICH |
| | WILL BE TAKING PLACE ON PLANS. |
| | |
| | ** PLEASE BE AWARE OF ANY COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |