Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-15 14:25:18 
  
 *** UNSAT 2ND REVIEW***
  
 AMERICAN LUNG ASSOCIATION
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS BASED
 ON CHANGES MADE TO PLANS.
 PLEASE KNOW THAT THERE NEW COMMENTS BASED ON PLANS AND
 CHANGES MADE.
  
 ** PLEASE KNOW THAT BASED ON THE LAST MEETING HELD, THE
 ARCHITECT WAS PRESENT HOWEVER NO CONTACT TO DATE HAS
 BEEN MADE BY THE ENGINEERING DESIGNER(S) TO GO OVER
 COMMENTS.
  
 ** PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY
 FROM PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER. THEY
 WILL CONTAIN A NO, OK, OR NO/OK.
 A) NO WILL BE FOLLOWED BY FURTHER EXPLANATION OF THE
 PREVIOUS COMMENT.
 B) OK, MAY REFERENCE TO ANY NEW NOTES, HOWEVER WILL
 HAVE PREVIOUS NOTE REMOVED.
 C) NO/OK, WILL BE FOLLOWED BY FURTHER EXPLANATION AS
 PART OF THE COMMENT MAY NOT HAVE BEEN ADDRESSED FULLY
 AND PART OF THE PREVIOUS COMMENT MAY BE OK.
 D) OK/N/A, AS THE PREVIOUS NOTE DOES NOT APPLY ANY
 FURTHER AS PLANS HAVE DELETED OR CHANGED.
  
 ** ANY NEW NOTES WILL BE AT THE BOTTOM AND IDENTIFIED
 AS *** NEW NOTES ***.
  
  
  
  
 1) NOTE: NO/OK. PLEASE SEE THE ENGINEERING BUSINESS
 NUMBER WAS VERIFIED WITH THE STATE, HOWEVER PLEASE SEE
 THE ADDRESS FOR FIRM ON THE STATE'S WEBSITE AND PLANS
 DIFFER. A FAR AS WE HAVE BEEN INFORMED FROM THE STATE,
 THIS INFORMATION IS REQUIRED TO MATCH.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED LICENSE INFORMATION ON
 TITLE BLOCKS.
 PLEASE SEE FAC 61G15-23.002 AND FS
 471.023.
 PLEASE KNOW PER THE FLORIDA STATUES AS NOTED ABOVE AND
 PER THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS, ANY
 FIRM PRACTICING ENGINEERING AND OFFERING ENGINEERING
 SERVICES MUST ALSO OBTAIN A CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING PART OF THE
 BUSINESS.
 PLEASE SEE THE FIRM NUMBER AS SHOWN IS ONLY LICENSED
 FOR THE ARCHITECTURAL FIRM.
 PLEASE ALSO SEE ADDRESS ON TITLE BLOCK DO NOT CORRELATE
 WITH THE ADDRESS AS LISTED ON THE STATE'S DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 PLEASE SEE THE ATTACHED PRINT OUT ATTACHED TO
 ELECTRICAL NOTES.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2) NOTE: OK/NO, PLEASE SEE THIS WAS DONE HOWEVER THIS
 INFORMATION WAS HAND WRITTEN ON SHEETS WHICH IS OK. THE
 COMMENT WILL REMAIN AS NEW SHEETS WILL ALSO BE REQUIRED
 TO CONTAIN THIS INFORMATION. THIS IS SOMETHING THAT
 SHOULD BE ADDED INTO THE FIRMS CADD OR COMPUTER SYSTEMS
 SO THAT THIS INFORMATION DOES NOT HAVE TO BE
 HANDWRITTEN ON ALL SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 FOR THE ENGINEER OF RECORD ON SAID TITLE BLOCKS AS
 REQUIRED UNDER FAC 61G15-23.002
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK, N/A
  
 6) NOTE: OK, AS THE GEN HAS BEEN REMOVED AND NOTES
 BEING DONE AS FUTURE, HOWEVER PLEASE SEE THESE SECTIONS
 AND PREVIOUS NOTES ARE BEING LEFT FOR INFORMATIONAL
 REASONS FOR THE PANEL E WHICH IS BEING SHOWN AS FUTURE
 WHICH DOES NOT SEEM TO MEET THESE SECTIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 225.31-225.39 FOR MISSING REQUIRED MEANS OF
 DISCONNECT FOR THE FEEDERS FROM THE GENERATOR UNIT.
 PLEASE SEE GROUPING ETC AS REQUIRED.
  
  
 7) NOTE: OK, HOWEVER SEE NEW NOTES WITH RESPECT TO GAP,
 FACP AND FAAP.
  
 8) NOTE: OK, N/A. SEE NEW NOTES HOWEVER FOR PANEL H.
  
  
 9) NOTE: OK.
  
 10) NOTE: OK, N/A.
  
 11) NOTE: OK, N/A.
  
 12) NOTE: OK/NO, PLEASE SEE THESE ITEMS WERE ADDED,
 HOWEVER PLEASE SEE MISSING CIRCUITING FOR THE ROOF TOP
 GFI'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DISCONNECTS FOR RTU'S WHICH COULD
 NOT BE LOCATED ON PLANS. CAN BE TYPICAL IF THE SAME.
 440.11
 PLEASE ALSO SEE MISSING ROOF TOP GFI'S WHICH COULD NOT
 BE LOCATED ON PLANS FOR ROOF.
 230.63, 210.8
  
 13) NOTE: NO, PLEASE SEE PLANS AS THE INTENTION SEEMS
 TO HAVE BEEN MADE, BUT PLEASE SEE THAT THERE ARE LINES
 FOR CIRCUITING WHICH STILL PLACES THE LIGHTING ON WITH
 OTHER HOUSE CIRCUITS AND OTHER AREAS WHICH IS NOT
 PERMITTED. PLEASE SEE SECTIONS AS NOTED REQUIRE
 DEDICATED CIRCUITS WHICH MAY NOT FEED OTHER AREAS.
 PLEASE SEE NOTE FOR CONTROL OF PIT LTS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE MISSING THE REQUIRED DEDICATED CIRCUITS FOR
 THE ELEVATOR MACHINE ROOM.
 620.23, 620.24
  
 14) NOTE:OK, HOWEVER SEE NEW NOTES FOR EMERGENCY
 LIGHTING.
  
 15) NOTE:NO, PLEASE SEE ALL DEVICES AS NOTED AND
 SHOWN ON PLANS SHALL INDICATE ALL OF THE MAXIMUM TIMES.
 ONLY ONE SYMBOL ON LEGEND CONTAINS THE INFORMATION AS
 NEEDED.
 PLEASE SEE ELEVATOR PIT LIGHTS WHICH APPEAR TO BE
 MISSING CONTROL(S).
 PLEASE CALL F THERE ARE ANY QUESTIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SPECIFY THE MAX OVER RIDE TIMES FOR THE OCCUPANT
 SENSORS.
 30MIN MAX FOR SENSORS AND 4HRS MAX FOR TIMER TYPE OVER
 RIDES.
 PLEASE ALSO SEE SEPARATE SPACES/ROOMS WHICH SEEM TO BE
 MISSING OVER RIDE CONTROLS.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2,
 .1.3
  
 16) NOTE:NO, PLEASE SEE THAT IT APPEARS BASED ON THE
 RESPONSE FROM THE DESIGN TEAM THAT THIS COMMENT WAS NOT
 UNDERSTOOD.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED SHOWING
 METHOD A, INDICATES ALL LIGHTING BEING CONTROLLED AS
 "MANUAL ON/OFF". THIS IS NOT POSSIBLE IF THERE ARE
 AUTOMATED CONTROL LIGHTING SYSTEMS AND AUTOMATED
 DEVICES/OCCUPANCY SENSORS ETC.
 13-415.1.ABC.1.1, .1.2, AND .1.3. 13-415.2. ETC.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY HOW THE ENERGY CALCULATIONS SUBMITTED ALL
 MENTIONS AND CONTAIN "MANUAL ON/OFF" CONTROLS FOR
 LIGHTING??
 PLEASE SEE METHODS REQUIRED PER 13-415.1.AB.1.
  
 17) NOTE:NO, PLEASE SEE BASED ON THE RESPONSE IT
 MENTIONS TO SEE LIGHTING PHOTO-METRICS?? PLEASE KNOW
 THAT PHOTO-METRICS AND LIGHTING POWER DENSITIES AND
 PERFORMANCE CALCULATIONS A RE COMPLETELY DIFFERENT
 ITEMS.
 PLEASE SUBMIT PER SECTIONS GIVEN IN PREVIOUS REVIEW
 NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT LIGHTING POWER DENSITY CALCULATIONS AS
 REQUIRED. 13-415.1.AB.1,13 ,415.2.ABC.1 AND TABLES
 415.2.C.1 AND 415.2.B.1 (WHERE APPLICABLE)
  
 18) NOTE: OK.
  
 20) NOTE: OK, HOWEVER THIS NOTE WILL REMAIN AS BASED ON
 THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS, THE LOAD
 CALCULATIONS SUBMITTED THIS MAY BE CHANGED AND/OR
 INCREASED. SEE COMMENTS AS THIS PREVIOUS NOTE WILL
 REMAIN AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.66 FOR MIN SIZING OF THE GEC. APPEARS
 THIS SHOULD BE 2/0 MIN.
  
 21) NOTE: NO, PLEASE SEE AS NOTED ABOVE THIS STILL
 SEEMS TO BE IN QUESTION. PLEASE SEE SOME COMMON AREAS
 WHICH ARE NOT FED FROM HOUSE PANELS, PLEASE SEE OTHER
 AREAS LIKE THE ROOF TOP WHICH IS BEING FED FROM HOUSE
 PANEL AND QQ PANELS FOR STAIRS. PLEASE SEE NOTES FOR
 ELEVATOR ROOMS WHICH ARE BEING FED FROM HOUSE AND
 TENANT PANELS.
 THIS SCENARIO ON PLANS AS SHOWN IS NOT CLEAR. PLEASE
 SEE THERE SEEMS TO BE AN ELECTRICAL ROOM ON FIRST FLOOR
 WHICH REVIEW OF 240.24 SHOULD BE NOTED AND ADJUST PLANS
 AS NEEDED.
 PLEASE MAKE OTHER ADJUSTMENTS AS ROOF TOP ACCESS SEEMS
 TO BE ONLY ACCESSIBLE THROUGH WHAT IT BEING SHOWN AS
 STAIRWAYS FOR THE 2ND FLR TENANT ONLY. IF THESE
 STAIRWAYS OR A STAIRWAY IS BEING USED FOR COMMON USE,
 THEN THE ONE OR MORE BEING USED SHALL BE CIRCUITED FORM
 THE HOUSE COMMON AREA PANEL/EQUIPMENT.
 PLEASE ALSO SEE BOLLARDS BEING SHOWN ON ROOF?, AND
 BEING SHOWN FROM HOUSE WHICH IS OK, HOWEVER NOT CLEAR
 WHY THERE ARE BOLLARD TYPE FIXTURES ON ROOF? PLEASE
 KNOW THAT AS PLANS ARE NOT CLEAR AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE SEPARATION OF TENANTS. PLEASE SEE
 PLANS AS SHOWN HAS CIRCUITING FROM EACH TENANT SERVICE
 CROSSING OVER INTO OTHER TENANT'S AREAS AND ROOMS. IF
 THE BUILDINGS GOING TO HAVE "HOUSE" POWER THESE MAY NOT
 FEED INTO TENANT SPACES. PLEASE ALSO SEE
 CIRCUITS FOR UPPER TENANT MAY NOT FEED AREAS IN LOWER
 TENANTS. PLEASE SEE PROPER TENANT SEPARATION AND
 CROSSING OVER OF CIRCUITS AND COMMON AREAS. PLEASE
 ADJUST CIRCUITING ON PLANS.
 PLEASE SEE "HOUSE" PANELS LOCATED ON FIRST FLR TENANTS
 SPACE?
 THIS IS UNCLEAR WHAT IS BEING PROPOSED IN THIS DESIGN
  
 22) NOTE: NO, PLEASE SEE NEW COMMENTS AS THE RISER HAS
 COMPLETELY CHANGED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE AS KNOW "SCHEDULE WAS SUBMITTED FOR THE
 800A BUS/METER CENTER, PLEASE INDICATE THE CONDUCTORS
 FROM THE MAIN BUS TO EACH OF THE ATS UNITS.
 215.5, 240.4,310.16
  
 23) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 24) NOTE: OK/NO, CIRCUITS ARE BEING SHOWN, HOWEVER
 COMING FROM HOUSE PANEL? PLEASE SEE 600.5 AND THE
 REQUIRED DEDICATED CIRCUITS. THIS CIRCUIT AS SHOWN ON
 PLANS COMES NOT ONLY FROM THE HOUSE PANEL; IT IS ALSO
 SHOWN FEEDING OTHER AREAS OF LIGHTING. PLEASE SEE 600.5
 REFERENCES TO 220.3(B)6
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY NEW OR EXISTING REQUIRED SIGN CIRCUIT PER
 600.5
  
 25) NOTE: NO, PLEASE SEE LOAD CALCULATIONS ARE NOT
 COMPLETE PER NEC AND CODE SECTIONS GIVEN.
 PLEASE ALSO SEE NEW NOTES BASED ON THE LOADS ALREADY
 SHOWN WHICH EXCEED THE RATING OF THE SERVICE ENTRANCE
 CONDUCTORS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY AND SHOW LOAD CALCULATIONS FOR SERVICE
 AND GENERATOR.
 PLEASE SEE 220.3,220.10,220.11,220.13, ETC
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.215.3,230.42
  
 26) NOTE: OK,N/A.
  
 27) NOTE: OK, N/A.
  
 28) NOTE: NO, SEE NEW NOTES FROM THIS REVIEWER.
  
 PLEASE SEE POSSIBLE FIRE AND BUILDING REVIEW COMMENTS
 AS IT DID NOT SEEM PLANS WERE SUBMITTED FOR ANY
 BUILDING FIRE ALARM SYSTEM?
  
 **** NEW NOTES ******
  
  
 29) NOTE: PLEASE SEE PANELS MH, MA, H, MQ ETC ALL LIST
 FEEDS TO AUTOMATIC TRANSFER SWITCHES WHICH ARE NOT ON
 RISER. THESE ARE NOT THE ATS DEVICES WHICH ARE SHOWN ON
 RISER WHICH ARE NOTED AS FUTURE ON THE LINE SIDE OF
 THESE PANELS.
 PLEASE ALSO SEE ONE IS STILL BEING SHOWN AS LS /ATS FOR
 LIFE SAFETY. PLEASE SEE IF THERE ARE LEGALLY REQUIRED
 SYSTEMS OR LIFE SAFETY SYSTEMS, PLEASE REVISE PLANS.
 PLEASE CLARIFY ALL OF THESE. REVIEW FOR ANY CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME AS PLANS ARE
 CONFUSING AND ARE NOT CLEAR OF INTENTIONS, CODES AND
 DESIGNS AS SHOWN.
 PLEASE SUBMIT ALL MANUFACTURE'S SPEC/CUT SHEETS FOR ANY
 PROPOSED SWITCHES TO BE INSTALLED AT THIS TIME. 110.3,
 90.7.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 30) NOTE: PLEASE SEE THAT THE MEN'S AND WOMEN'S
 BATHROOM WHICH ARE NOT SINGLE OCCUPANT OR SINGLE POINT
 OF USE SHALL CONTAIN A BATTERY BACK UP LIGHT FIXTURE OF
 SOME KIND.
 PLEASE ALSO SEE UPPER STAIRS WHICH DO NOT INDICATE
 BATTERY BACK UP FIXTURES.
 PLEASE SEE PARKING GARAGE AREA FOR EGRESS TO THE PUBLIC
 RIGHT OF WAY.
 PLEASE SEE LS 101 7.8.1.3, AND 7.9.2.2.
 PLEASE KNOW THE LIGHTING LEVELS ON STAIRS SHALL MEET
 10FT UNDER NORMAL AND 1FT CANDLED UNDER EM.
  
 31) NOTE: PLEASE SEE THAT THESE PLANS SHALL CONTAIN A
 BASE LAYOUT FOR ALL FIRE ALARM DEVICES TO REVIEW FOR
 ADA COMPLIANCE. PLEASE SEE THE NOTE BEING PLACED ON THE
 PLANS CAN NOT BE ACCEPTED. PLEASE KNOW THAT EVEN THOUGH
 THE FIRE ALARM AND ANY FIRE SPRINKLER WILL BE REQUIRED
 UNDER A SEPARATE PERMIT THESE BASE SYSTEMS ARE STILL
 REQUIRED ON BASE BUILDING PLANS.
 THIS WAS NOT A COMMENT ON THIS REVIEWER'S PREVIOUS
 REVIEW; HOWEVER IT HAS NOW BECOME PART OF THE
 ELECTRICAL REVIEW SINCE THESE PLANS WERE PREVIOUSLY
 REVIEWED. PLEASE SEE COMPLIANCE FOR MINIMUM STROBE AND
 SOUNDING DEVICE LEVELS SHALL BE STATED AND LOCATIONS
 SHOWN.
 PLEASE SEE 11-4.28.1, .2, AND.3(4).
 FBC ADMIN SECTION 106.3.5.1.2
  
 32) NOTE: PLEASE CLARIFY PANELS H, A AND Q AS BEING
 NOTED AS SERVICE ENTRANCE RATED. HOW IS THIS POSSIBLE
 WHEN THESE ARE ALL BEING SHOWN AS MLO?
 PLEASE ALSO EXPLAIN.
 106.1.2, 106.3.5.1.2, NEC 230.70, 110.3, 90.7
  
 33) NOTE: PLEASE SUBMIT MANUFACTURE'S SPEC/CUT SHEETS
 ON THE PROPOSED SERVICE AS SHOWN ON RISER. THIS 800A
 RATED BUS WHICH SHOWS NO MAIN, YET SHOWS SEPARATE
 METERS AND MAINS FOR EACH TENANT AND HOUSE IS NOT
 CLEAR.
 IT MAY SEEM THAT THIS EQUIPMENT MAY BE REQUIRED TO
 CONTAIN A MAIN? (IF APPLICABLE)
 PLEASE SUBMIT MORE INFORMATION. FBC 106.1.2,
 106.3.5.1.2
 NEC 110.3, 90.7, 230.70, ETC
  
 34) NOTE: PLEASE SEE BASED ON THE LOAD CALCULATIONS
 SUBMITTED AND NOTED ABOVE IN NOTE #25, THE SEC'S ARE
 NOT LARGE ENOUGH FOR THE LOADS AS SHOWN. PLEASE ALSO
 KNOW BASED ON THESE LOADS SHOWN AND SOME LOADS WHICH
 ARE REQUIRED WHICH HAVE NOT YET BEEN ADDED OR SHOWN THE
 SIZING OF THESE CAN NOT BE VERIFIED FOR CODE COMPLIANCE
 AT THIS TIME.
 PLEASE ALSO SEE NOTE ABOVE AS IF THE EQUIPMENT CHANGES
 SOME OTHER CODE SECTIONS MAY ALSO APPLY FOR DEVICES
 RATED OVER 800AMPS.
 PLEASE SEE 240.4, 310.16, 230.70, 230.76, 230.79,
 230.90, 230.91 ETC
  
 35) NOTE: PLEASE SUBMIT WIND LOADS FOR NEW SITE
 LIGHTING POLES AS SHOWN. THESE SHALL INDICATE THE
 MINIMUM LEVELS PER FBC 140MPH 3-SEC GUST (120
 SUSTAINED) AND INDICATE THE EPA OF FIXTURES FOR THE
 POLE BEING STATED.
 PLEASE KNOW THIS WILL BE REVIEWED FURTHER BY THE
 BUILDING REVIEWER.
  
 36) NOTE: PLEASE KNOW CONTACT WITH THE FIRE MARSHAL'S
 OFFICE SHOULD BE MADE FOR COORDINATION OF THE LOCATIONS
 OF THE FACP, GAP(FUTURE) AND FAAP.
  
 37) NOTE: PLEASE KNOW THIS IS BEING NOTED ONLY AS PANEL
 E IS NOT UNDER THIS PERMIT. THE BREAKER IS BEING SHOWN
 FOR ATS-LS.?
 THIS IS ONLY BEING NOTED.
  
 38) NOTE: PLEASE SEE ATTACHED REFERENCE TO FS
 553.80(2)(B) WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE KNOW AS THERE MAY BE COMMENTS ON THE NEXT
 REVIEW BASED ON INFORMATION NOT SHOWN OR CHANGES WHICH
 WILL BE TAKING PLACE ON PLANS.
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-15 11:23:552007-01-15 11:23:55
 REVIEW IN PROGRESS
2007-01-14 19:10:49PLANS REMOVED FROM INCOMING TABLE. IN ELEC FOR REVIEW.