Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop B
Sequence Number 19
Notes
Date Text
2008-05-27 15:05:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PER FBPE, ALL ENGINEERS' SIGNATURES ARE TO BE
 ORIGINAL, "WET" SIGNATURES (CANNOT BE A STAMP).
 HOWEVER, IT APPEARS THAT ALL DOCUMENTS WITHIN THE
 BINDER SUBMITTED ARE REPORTS RATHER THAN
 SPECIFICATIONS, PLANS, PRINTS, OR CALCULATIONS.IF ALL
 OF THE DOCUMENTS ARE REPORTS, THE FOLLOWING MAY APPLY
 PER FAC61G15-23.002(2):ENGINEERING REPORTS MUST BE
 SIGNED, SEALED AND DATED ON A SIGNATURE PAGE OR COVER
 LETTER BY EACH PROFESSIONAL ENGINEER WHO IS IN
 RESPONSIBLE CHARGE OF ANY PORTION OF THE REPORT.
  
 THIS MAY BE ACCOMPLISHED BY PROVIDING A SIGNED, SEALED,
 AND DATED COVER LETTER TO BE INCORPORATED INTO THE
 BINDER OF REPORTS.
  
 IF THE DOCUMENTS SUBMITTED INCLUDE SPECIFICATIONS OR
 PLANS (ANYTHING OTHER THAN A REPORT), A SIGNED, SEALED,
 AND DATED INDEX SHEET MAY BE PROVIDED IN LIEU OF
 PROVIDING AN ORIGINAL SIGNATURE FOR EACH SEALED SHEET.
  
 OTHER OPTIONS MAY ALSO BE ACCEPTABLE (SUCH AS SIGNING
 EACH SEALED SHEET) PROVIDED THAT WHATEVER OPTION
 PROPOSED IS IN COMPLIANCE WITH FAC61G15-23.I HAVE
 SUGGESTED THE OPTION WHICH APPEARS TO BE THE SIMPLEST
 BUT THE DECISION AS TO HOW TO COMPLY IS ENTIRELY THE
 ENGINEER'S DECISION.ANY COMPLIANT METHOD IS
 ACCEPTABLE.
  
 2.PLEASE HAVE THE DESIGNER OF RECORD (EITHER
 ARCHITECT OR ENGINEER) REVIEW THE DOCUMENTS PRIOR TO
 RESUBMITTAL.THIS IS REQUIRED FOR ALL SUBMITTALS AND
 MAY BE DONE BY EITHER A SHOP DRAWING REVIEW STAMP OR BY
 LETTER.
  
 3.PLEASE INCLUDE THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING BUSINESS, ECS FLORIDA LLC,
 ON EACH SHEET WHICH IS REQUIRED TO BE SIGNED AND SEALED
 (INCORPORATED AS TITLE BLOCK INFORMATION).
  
 4.PLEASE NOTE THAT THE REPAIR DETAIL (SHEETS
 SK4.10-05 AND -03) PREPARED BY BLISS & NYITRAY, INC. IS
 A SPECIFICATION, AND BASED ON PREVIOUS PLAN REVIEW
 NOTES, ARE NOT INCORPORATED INTO OUR PLAN SET.PLEASE
 PROVIDE ORIGINALS AS A REVISION UNLESS THIS HAS ALREADY
 BEEN DONE.THIS COMMENT APPLIES TO ANY OTHER SHEETS
 WHICH MAY HAVE BEEN INCLUDED WHICH HAVE THE SAME
 SITUATION BUT WERE NOT SPECIFICALLY LISTED IN THIS
 COMMENT.
  
 5.AS THIS DOCUMENT IS A SUBMITTAL (PER BUILDING
 INSPECTOR'S REQUREST), PLEASE NOTE THAT A COMPLETE PLAN
 REVIEW OF EACH SHEET WAS NOT PERFORMED.THE REPORTS
 SUBMITTED WERE SPOT CHECKED FOR GENERAL COMPLIANCE WITH
 THE CODE AND DESIGNERS' INTENT (ADVISORY, NO ACTION
 REQUIRED).
  
 6.SOME SHEETS REFER TO NONCOMPLIANCE, OTHERS APPEAR
 NONCOMPLIANT.IT APPEARS THAT ALL REPORTS WERE
 SUBMITTED, AND THE NONCOMPLIANCE ADDRESSED IN
 SUBSEQUENT INSPECTIONS.PLEASE PROVIDE A LETTER FROM
 BOTH THE ENGINEERING COMPANY AND THE CONTRACTOR WHICH
 ATTEST GENERALLY TO THE FACT THAT ANY NON COMPLIANCE
 NOTED IN ANY OF THE REPORTS HAS BEEN ADDRESSED.