Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL CIVIL SHEETS, THE BUSINESS NUMBER (CERTIFICATE
 OF AUTHORIZATION) IS
 REQUIRED IN THE TITLE BLOCK ON EACH
 SHEET. FAC 61G1-16.004(2), FAC
 61G15-23.002(2), FS 481.219. & FS
 481.2055. BOTH CA#'S ARE REQIRED FOR THE ENGINEERING
 AND THE SURVEYO PORTION OF
 THE BUSINESS IN THE TITLE BLOCK PER
 DBPR.
  
 2. ALL ARCHITECTURAL SHEETS. THE TITLE
 BLOCK SHALL SHOW THE DATE PREPARED,
 DATED SEAL, PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT.
 61G1-16.004(4)(5)(6) & FS 481.2055.
  
 3. SHT A0-00-001 THE FOLLOWING
 INFORMATION IS REQUIRED TO SHOW
 COMPLIANCE WITH ACCABILITY REQUIREMENTS:
 A. 11-4.18.2 HEIGHT (SHOWS 19")
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.19.5 FAUCETS (LAV)
  
 4. SHT A0-01-301 DEMO KEY NOTES #3.
 INDICATE THAT DEAD ENDS ARE PROHIBITED
 PER SECTION 704.5.
  
 5. SHT A1-0R-001 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SQUARE FOOTAGE
 BEING DRAINED BY EACH ROOF DRAIN.
 CALCULATIONS SHALL SHOW ROOF AREA PLUS
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, ALONG WITH ALL AREAS OF ROOF
 THAT DRAIN ONTO THE ROOF FROM ABOVE.
  
 6. SHT A2-02-001 DETAIL #4 SHOWS THE
 COUNTERTOP AT 36". MAX 34" TO SINK PER
 11-4.24.2.
  
 7. SHT A5-00-103 DETAIL #7 OVERFLOW
 SCUPPERS TO BE 2" TO 4" ABOVE THE ROOF
 TO THE FLOW LINE. (SHOW AS EVEN WITH
 ROOF). ALSO THE MINIMUM HEIGHT IS 4".
 (SHOWN AS 3"). SECTION 1503.4.3 AND
 SECTION 1107.3.
  
 8. SHT A7-01-101 ELEVATION 1 KITCHEN
 SINK TO COMPLY WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. SHOW ON DETAIL.
  
 9. SHT A7-01-101 ELEVATIONS 7, 13, 17.
 FLUSH CONTROLS TO BE LOCATED ON THE WIDE
 SIDE TO THE W/C TANK. SECTION 11-4.16.5.
  
 10. SHT A7-02-101 ELEVATIONS 2, 8 , 11
 FLUSH CONTROLS SHALL BE LOCATED ON THE
 WIDE SIDE OF THE W/C TANK. SECTION
 11-4.16.5.
  
 11. SHT A7-02-101 ELEVATION 13, STAFF
 SINK SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. SUBMIT INFORMATION
 ON DETAIL.
  
 12. SHTS A9-01-201 & AP-02-201 ROOMS
 108, 126, 127, 205, 206, 214. TOILET
 ROOM FLOORS & WALLS SHALL BE SMOOTH,
 HARD AND NONABSORBENT PER SECTIONS
 1210.1 & 1210.2. THE BASE IS INDICATED
 AS T2 WHICH IS NOT SHOWN UNDER THE BASE INFORMATION,
 BUT AS "TBD" UNDER THE
 FLOOR INFORMATION. WALLS ARE INDICATED
 AS P5 OR P6. PLEASE SUBMIT INFORMATION
 SHOWING HOW A PAINTED WALL CAN COMPLY
 WITH REQUIREMENTS OF "HARD &
 NONABSORBENT". SHOW BASE MATERIAL.
  
 13. SHTP1-01-101 ELEVATOR SUMP PUMPS.
 PLUMBING SYSTEMS SHALL NOT BE LOCATED IN
 AN ELEVATOR SHAFT, OR IN AN ELEVATOR
 EQUIPMENT ROOM. SECTION 301.6. OIL FROM
 THE ELEVATOR SHAFT SHALL NOT BE
 DEPOSITED INTO THE SEWER SYSTEM. SECTION
 302.1. THIS IS CONSIDERED HAZARDOUS
 MATERIAL AND SHALL BE CONTAINED AND
 RECYCLED.
  
 14. SHT P1-01-101 DEAD ENDS ARE
 PROHIBITED PER SECTION 704.5. ALL
 SANITARY PIPING SHALL BE DEMO'D AT THE
 MAIN LINE. ALL CAPPED PIPING SHALL BE
 INSPECTED PRIOR TO COVERING.
  
 15. SHT P1-01-101 INDICATE WHAT "SW"
 FIXTURE IS. DESIGNATION NOT SHOWN ON THE
 PLUMBING CONNECTION FIXTURE SCHEDULE.
  
 16. SHT P7-00-001 SUBMIT THE SANITARY
 RISER DIAGRAM IN ISOMETRIC FORM THAT
 REFLECTS THE FLOOR PLAN. SHOW ALL DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM.
 SECTIONS 106.1.1 AND 106.3.5.1.3. (SEE
 ATTACHED SHEET FOR AN EXAMPLE OF A
 PORTION OF THE SANT. RISER ISOMETRIC
 DIAGRAM THAT REFLECTS THE FLOOR PLAN).
 RISER DIAGRAMS AS DRAWN ARE NOT
 ACCEPTABLE AND DO NOT REFLECT THE FLOOR
 PLAN.
  
 17. SHT P7-00-001 W/C NOT VENTED AS
 DRAWN. (TOILET ROOM BY OFFICE ROOM 107).
 (SEE ATTACHED EXAMPLE OF ISOMETRIC FOR
 CORRECT VENTING OF W/C).
  
 18. SHT P7-00-002 DETAIL #2 WATER HEATER
 PAN REQUIRES A PAN DRAIN. SECTION
 504.7.1.
  
 19. SHT P7-00-002 DETAIL #3 SUBMIT
 MANUF. SPECIFICATION SHEETS FOR TANKLESS
 WATER HEATER. MUST SHOW LISTING. SECTION
 303.4.
  
 20 ALL PME SHEETS ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. SEAL
 HAS NOT BEEN DATED (WHEN SEAL IS AFFIXED
 TO PLANS), NOR IS THE PRINTED NAME OF
 THE ENGINEER INDICATED. FAC
 61G15-23.002(2) AND FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]