| 2006-09-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL CIVIL SHEETS, THE BUSINESS NUMBER (CERTIFICATE |
| | OF AUTHORIZATION) IS |
| | REQUIRED IN THE TITLE BLOCK ON EACH |
| | SHEET. FAC 61G1-16.004(2), FAC |
| | 61G15-23.002(2), FS 481.219. & FS |
| | 481.2055. BOTH CA#'S ARE REQIRED FOR THE ENGINEERING |
| | AND THE SURVEYO PORTION OF |
| | THE BUSINESS IN THE TITLE BLOCK PER |
| | DBPR. |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. THE TITLE |
| | BLOCK SHALL SHOW THE DATE PREPARED, |
| | DATED SEAL, PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT. |
| | 61G1-16.004(4)(5)(6) & FS 481.2055. |
| | |
| | 3. SHT A0-00-001 THE FOLLOWING |
| | INFORMATION IS REQUIRED TO SHOW |
| | COMPLIANCE WITH ACCABILITY REQUIREMENTS: |
| | A. 11-4.18.2 HEIGHT (SHOWS 19") |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.5 FAUCETS (LAV) |
| | |
| | 4. SHT A0-01-301 DEMO KEY NOTES #3. |
| | INDICATE THAT DEAD ENDS ARE PROHIBITED |
| | PER SECTION 704.5. |
| | |
| | 5. SHT A1-0R-001 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS. SHOW THE SQUARE FOOTAGE |
| | BEING DRAINED BY EACH ROOF DRAIN. |
| | CALCULATIONS SHALL SHOW ROOF AREA PLUS |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS, ALONG WITH ALL AREAS OF ROOF |
| | THAT DRAIN ONTO THE ROOF FROM ABOVE. |
| | |
| | 6. SHT A2-02-001 DETAIL #4 SHOWS THE |
| | COUNTERTOP AT 36". MAX 34" TO SINK PER |
| | 11-4.24.2. |
| | |
| | 7. SHT A5-00-103 DETAIL #7 OVERFLOW |
| | SCUPPERS TO BE 2" TO 4" ABOVE THE ROOF |
| | TO THE FLOW LINE. (SHOW AS EVEN WITH |
| | ROOF). ALSO THE MINIMUM HEIGHT IS 4". |
| | (SHOWN AS 3"). SECTION 1503.4.3 AND |
| | SECTION 1107.3. |
| | |
| | 8. SHT A7-01-101 ELEVATION 1 KITCHEN |
| | SINK TO COMPLY WITH SECTION 11-4.24 AND |
| | ALL SUBSECTIONS. SHOW ON DETAIL. |
| | |
| | 9. SHT A7-01-101 ELEVATIONS 7, 13, 17. |
| | FLUSH CONTROLS TO BE LOCATED ON THE WIDE |
| | SIDE TO THE W/C TANK. SECTION 11-4.16.5. |
| | |
| | 10. SHT A7-02-101 ELEVATIONS 2, 8 , 11 |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE |
| | WIDE SIDE OF THE W/C TANK. SECTION |
| | 11-4.16.5. |
| | |
| | 11. SHT A7-02-101 ELEVATION 13, STAFF |
| | SINK SHALL COMPLY WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. SUBMIT INFORMATION |
| | ON DETAIL. |
| | |
| | 12. SHTS A9-01-201 & AP-02-201 ROOMS |
| | 108, 126, 127, 205, 206, 214. TOILET |
| | ROOM FLOORS & WALLS SHALL BE SMOOTH, |
| | HARD AND NONABSORBENT PER SECTIONS |
| | 1210.1 & 1210.2. THE BASE IS INDICATED |
| | AS T2 WHICH IS NOT SHOWN UNDER THE BASE INFORMATION, |
| | BUT AS "TBD" UNDER THE |
| | FLOOR INFORMATION. WALLS ARE INDICATED |
| | AS P5 OR P6. PLEASE SUBMIT INFORMATION |
| | SHOWING HOW A PAINTED WALL CAN COMPLY |
| | WITH REQUIREMENTS OF "HARD & |
| | NONABSORBENT". SHOW BASE MATERIAL. |
| | |
| | 13. SHTP1-01-101 ELEVATOR SUMP PUMPS. |
| | PLUMBING SYSTEMS SHALL NOT BE LOCATED IN |
| | AN ELEVATOR SHAFT, OR IN AN ELEVATOR |
| | EQUIPMENT ROOM. SECTION 301.6. OIL FROM |
| | THE ELEVATOR SHAFT SHALL NOT BE |
| | DEPOSITED INTO THE SEWER SYSTEM. SECTION |
| | 302.1. THIS IS CONSIDERED HAZARDOUS |
| | MATERIAL AND SHALL BE CONTAINED AND |
| | RECYCLED. |
| | |
| | 14. SHT P1-01-101 DEAD ENDS ARE |
| | PROHIBITED PER SECTION 704.5. ALL |
| | SANITARY PIPING SHALL BE DEMO'D AT THE |
| | MAIN LINE. ALL CAPPED PIPING SHALL BE |
| | INSPECTED PRIOR TO COVERING. |
| | |
| | 15. SHT P1-01-101 INDICATE WHAT "SW" |
| | FIXTURE IS. DESIGNATION NOT SHOWN ON THE |
| | PLUMBING CONNECTION FIXTURE SCHEDULE. |
| | |
| | 16. SHT P7-00-001 SUBMIT THE SANITARY |
| | RISER DIAGRAM IN ISOMETRIC FORM THAT |
| | REFLECTS THE FLOOR PLAN. SHOW ALL DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM. |
| | SECTIONS 106.1.1 AND 106.3.5.1.3. (SEE |
| | ATTACHED SHEET FOR AN EXAMPLE OF A |
| | PORTION OF THE SANT. RISER ISOMETRIC |
| | DIAGRAM THAT REFLECTS THE FLOOR PLAN). |
| | RISER DIAGRAMS AS DRAWN ARE NOT |
| | ACCEPTABLE AND DO NOT REFLECT THE FLOOR |
| | PLAN. |
| | |
| | 17. SHT P7-00-001 W/C NOT VENTED AS |
| | DRAWN. (TOILET ROOM BY OFFICE ROOM 107). |
| | (SEE ATTACHED EXAMPLE OF ISOMETRIC FOR |
| | CORRECT VENTING OF W/C). |
| | |
| | 18. SHT P7-00-002 DETAIL #2 WATER HEATER |
| | PAN REQUIRES A PAN DRAIN. SECTION |
| | 504.7.1. |
| | |
| | 19. SHT P7-00-002 DETAIL #3 SUBMIT |
| | MANUF. SPECIFICATION SHEETS FOR TANKLESS |
| | WATER HEATER. MUST SHOW LISTING. SECTION |
| | 303.4. |
| | |
| | 20 ALL PME SHEETS ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME, ADDRESS, |
| | AND LICENSE NUMBER ON EACH SHEET. SEAL |
| | HAS NOT BEEN DATED (WHEN SEAL IS AFFIXED |
| | TO PLANS), NOR IS THE PRINTED NAME OF |
| | THE ENGINEER INDICATED. FAC |
| | 61G15-23.002(2) AND FS 471.025. |
| | |