| 2006-10-16 17:20:01 | -------------------DENIED------------------- |
| | 1. PG.M1-02-101 SHOWS 1 HOUR RATED SHAFT WITH DUCTS TO |
| | FIRST FLOOR. PLEASE PROVIDE DETAIL FOR SHAFT |
| | TERMINATION AT 2ND FLOOR LEVEL IN COMPLIANCE WITH FBC |
| | 707.11 |
| | |
| | 2. PG.M1-02-101 PENETRATIONS INTO A MEANS-OF-EGRESS |
| | STAIRWELL ARE PROHIBITED PER FBC 1019.1.2 |
| | |
| | 3. PG.M1-02-101 SHAFT ENCLOSURES PERMITTED TO BE |
| | PENETRATED BY DUCTS SHALL BE PROTECTED BY APPROVED FIRE |
| | AND SMOKE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR |
| | LISTING PER FBC,M 607.5.5.1 |
| | |
| | 4. PG M1-01-101 ROOMS 121 AND EM2 SHOW FIRE DAMPERS ON |
| | TRANSFER OPENINGS BUT NOT AT SUPPLY DUCTS. DUCT |
| | PENETRATIONS IN FIRE BARRIERS SHALL BE PROTECTED WITH |
| | APPROVED FIRE DAMPERS IN ACCORDANCE WITH THEI RLISTING |
| | PER FBC,M 607.5.2 |
| | |
| | 5. PG.M7-00-101 DETAIL #8 FIRE DAMPERS ARE TO BE UL555 |
| | LISTED AND INSTALLED PER MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS AND LISTING PER FBC,M 607.2 |
| | |
| | 6. PG M1-0R-101 PLEASE SHOW MEANS OF CONDENSATE |
| | DISPOSAL TO BE IN COMPLIANCE WITH FBC,M 307.2.1 AND FBC |
| | 1503.6.AUXILIARY DRAIN PROTECTION IS ALSO REQUIRED |
| | PER FBC,M 307.2.3 |
| | |
| | 7. PG.M7-00-101 ROOFTOP EQUIPMENT REQUIRES AN |
| | ENGINEERED SYSTEM TO SHOW COMPLIANCE WITH WIND LOAD |
| | REQUIREMENTS PER FBC,M 301.13. PLEASE PROVIDE DETAIL |
| | SHOWING ROOF-TO-CURB AND CURB-TO-EQUIPMENT ATTACHMENTS. |
| | NOTE: THE CITY OF WEST PALM BEACH IS IN THE 140MPH WIND |
| | ZONE PER FBC CHAPTER 16. |
| | |
| | 8. PG.M1-01-101 SEE BUILDING PLAN REVIEW COMMENT #11 |
| | REGARDING DUCT PENETRATIONS INTO GARAGE. THERE ARE ALSO |
| | TWO DUCTS PENETRATING RATED WALL AT ROOM EM1. |
| | |
| | REVIEWED BY: |
| | RONALD J REGUEIRO |
| | 561.805.6734 |
| | [email protected] |