2006-10-16 17:20:01-------------------DENIED-------------------
 1. PG.M1-02-101 SHOWS 1 HOUR RATED SHAFT WITH DUCTS TO
 FIRST FLOOR. PLEASE PROVIDE DETAIL FOR SHAFT
 TERMINATION AT 2ND FLOOR LEVEL IN COMPLIANCE WITH FBC
 707.11
  
 2. PG.M1-02-101 PENETRATIONS INTO A MEANS-OF-EGRESS
 STAIRWELL ARE PROHIBITED PER FBC 1019.1.2
  
 3. PG.M1-02-101 SHAFT ENCLOSURES PERMITTED TO BE
 PENETRATED BY DUCTS SHALL BE PROTECTED BY APPROVED FIRE
 AND SMOKE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING PER FBC,M 607.5.5.1
  
 4. PG M1-01-101 ROOMS 121 AND EM2 SHOW FIRE DAMPERS ON
 TRANSFER OPENINGS BUT NOT AT SUPPLY DUCTS. DUCT
 PENETRATIONS IN FIRE BARRIERS SHALL BE PROTECTED WITH
 APPROVED FIRE DAMPERS IN ACCORDANCE WITH THEI RLISTING
 PER FBC,M 607.5.2
  
 5. PG.M7-00-101 DETAIL #8 FIRE DAMPERS ARE TO BE UL555
 LISTED AND INSTALLED PER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBC,M 607.2
  
 6. PG M1-0R-101 PLEASE SHOW MEANS OF CONDENSATE
 DISPOSAL TO BE IN COMPLIANCE WITH FBC,M 307.2.1 AND FBC
 1503.6.AUXILIARY DRAIN PROTECTION IS ALSO REQUIRED
 PER FBC,M 307.2.3
  
 7. PG.M7-00-101 ROOFTOP EQUIPMENT REQUIRES AN
 ENGINEERED SYSTEM TO SHOW COMPLIANCE WITH WIND LOAD
 REQUIREMENTS PER FBC,M 301.13. PLEASE PROVIDE DETAIL
 SHOWING ROOF-TO-CURB AND CURB-TO-EQUIPMENT ATTACHMENTS.
 NOTE: THE CITY OF WEST PALM BEACH IS IN THE 140MPH WIND
 ZONE PER FBC CHAPTER 16.
  
 8. PG.M1-01-101 SEE BUILDING PLAN REVIEW COMMENT #11
 REGARDING DUCT PENETRATIONS INTO GARAGE. THERE ARE ALSO
 TWO DUCTS PENETRATING RATED WALL AT ROOM EM1.
  