| 2006-10-17 14:25:52 | ***DENIED*** |
| | |
| | 1) FIREAND SMOKE DAMPER INSTALLATIONS TO BE DROP |
| | TESTED PRIOR TO FINAL INSPECTION. |
| | |
| | 2) FIRE DEPARTMENT CONNECTIONS SHALL BE SECURED WITH |
| | KNOX LOCKING CAPS. |
| | |
| | 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEMS. |
| | |
| | 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR |
| | GENERATOR AND EQUIPMENT. PLEASE SUBMIT MANUFACTURER |
| | SPEC SHEETS. |
| | |
| | 5) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY |
| | WITH NFPA 241. |
| | |
| | 6) PLEASE PROVIDE MINIMUM INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILING. |
| | |
| | 7) PLANS SHOW ACCESS TO ROOF. PLEASE PROVIDE FURTHER |
| | INFORMATION REGARDING THIS ARRANGEMENT. |
| | |
| | 8) AN ADDRESS IS REQUIRED ON BUILDING AND SHALL BE |
| | MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND CONTRASTING TO |
| | BACKGROUND. PLEASE SHOW ON ELEVATIONS. |
| | |
| | 9) PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENT FOR |
| | HANDRAILS AND GUARDS. |
| | |
| | 10) STAIRS TO COMPLY WITH NFPA 101, SECTION 7.2.2.2.1 |
| | (A). |
| | |
| | 11) PLEASE ILLUSTRATE FIRE RATING OF DOORS IN MINUTES. |
| | SHT A-800-101 (DOOR SCHEDULE). |
| | |
| | 12) FIRE RATED DOORS SHALL CLOSE AND LATCH UTILIZING UL |
| | LISTED CLOSERS. |
| | |
| | 13) FIRE PROTECTION SHEETS SHOW THE FDC AT SOUTH SIDE |
| | OF BUILDING AND E SHEETS SHOW THE CONNECTION AT NORTH |
| | SIDE OF BUILDING. PLEASE CLARIFY CORRECT LOCATION. |
| | |
| | 14) FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW (561) 805-6722 |