Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-17 14:25:52***DENIED***
  
 1) FIREAND SMOKE DAMPER INSTALLATIONS TO BE DROP
 TESTED PRIOR TO FINAL INSPECTION.
  
 2) FIRE DEPARTMENT CONNECTIONS SHALL BE SECURED WITH
 KNOX LOCKING CAPS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 GENERATOR AND EQUIPMENT. PLEASE SUBMIT MANUFACTURER
 SPEC SHEETS.
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241.
  
 6) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 7) PLANS SHOW ACCESS TO ROOF. PLEASE PROVIDE FURTHER
 INFORMATION REGARDING THIS ARRANGEMENT.
  
 8) AN ADDRESS IS REQUIRED ON BUILDING AND SHALL BE
 MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND CONTRASTING TO
 BACKGROUND. PLEASE SHOW ON ELEVATIONS.
  
 9) PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENT FOR
 HANDRAILS AND GUARDS.
  
 10) STAIRS TO COMPLY WITH NFPA 101, SECTION 7.2.2.2.1
 (A).
  
 11) PLEASE ILLUSTRATE FIRE RATING OF DOORS IN MINUTES.
 SHT A-800-101 (DOOR SCHEDULE).
  
 12) FIRE RATED DOORS SHALL CLOSE AND LATCH UTILIZING UL
 LISTED CLOSERS.
  
 13) FIRE PROTECTION SHEETS SHOW THE FDC AT SOUTH SIDE
 OF BUILDING AND E SHEETS SHOW THE CONNECTION AT NORTH
 SIDE OF BUILDING. PLEASE CLARIFY CORRECT LOCATION.
  
 14) FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722