| Date |
Text |
| 2006-09-10 00:00:00 | *** UNSAT *** |
| | |
| | AMERICAN LUNG ASSC |
| | |
| | 1) NOTE: PLEASE SEE MISSING REQUIRED |
| | LICENSE INFORMATION ON TITLE BLOCKS. |
| | PLEASE SEE FAC 61G15-23.002 AND FS |
| | 471.023. |
| | PLEASE KNOW PER THE FLORIDA STATUES AS |
| | NOTED ABOVE AND PER THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS, ANY FIRM |
| | PRACTICING ENGINEERING AND OFFERING |
| | ENGINEERING SERVICES MUST ALSO OBTAIN A CERTIFICATE OF |
| | AUTHORIZATION NUMBER FOR |
| | THE ENGINEERING PART OF THE BUSINESS. |
| | PLEASE SEE THE FIRM NUMBER AS SHOWN IS |
| | ONLY LICENSED FOR THE ARCHITECTURAL |
| | FIRM. |
| | PLEASE ALSO SEE ADDRESS ON TITLE BLOCK |
| | DO NOT CORRELATE WITH THE ADDRESS AS |
| | LISTED ON THE STATE'S DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION. |
| | PLEASE SEE THE ATTACHED PRINT OUT |
| | ATTACHED TO ELECTRICAL NOTES. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND |
| | FOR ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE SEE MISSING THE PRINTED |
| | NAME AND LICENSE NUMBER FOR THE ENGINEER |
| | OF RECORDON SAID TITLE BLOCKS AS |
| | REQUIRED UNDER FAC 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE SEE A LETTER WAS |
| | ATTACHED FROM THE ENGINEER OF RECORD FOR VERIFICATION |
| | OF LEGAL SIGNATURE. PLEASE |
| | KNOW THE WORDING OF LETTER IS FINE, |
| | HOWEVER LETTER MUST BE ORIGINAL. |
| | (PHOTO-COPY SUBMITTED). MUST ALSO BE |
| | SIGNED, DATED AND SEALED BY SAID |
| | ENGINEER. |
| | PLEASE ALSO SEE THE STATUES IN WHICH |
| | STATE THE DOCUMENT IS BEING NOTARIZED, |
| | IF IN FLORIDA PLEASE SEE FS 117.05 AS IN |
| | THE STATE OF FLORIDA A STAMP AND |
| | SIGNATURE OF NOTARY IS NOT ALL THAT IS |
| | REQUIRED FOR A LEGAL DOCUMENT. |
| | |
| | 4) NOTE: PLEASE SEE SURVEY SUBMITTED IN |
| | INDEED A PHOTO-COPY OF THE SIGNATURE |
| | WITH A RAISED SEAL OVER PHOTO-COPIED |
| | SIGNATURE WHICH IS NOT PERMITTED UNDER |
| | FAC 61G17, FS 472.025 |
| | PLEASE ALSO SEE THAT THE RAISED SEAL |
| | MUST BE CLEAR AND VISIBLE WITH ALL |
| | INFORMATION ON SAID SEAL. (NOT VISIBLE AT |
| | THIS TIME). |
| | PLEASE CORRELATE THE SURVEY WITH THE |
| | ELECTRICAL PLANS, AS THE E-SHEETS |
| | INDICATE ANEW GENERATOR.(PLEASE SEE |
| | ZONING COMMENTS FOR THIS. |
| | |
| | 5) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS FOR THE NEW GENERATOR, |
| | NEW SUB-BASE FUEL TANK AND EACH OF THE |
| | PROPOSED ATS SWITCHES. |
| | PLEASE SEE THAT ALL SPEC SHEETS FOR THE |
| | ATS UNITS CONTAINS A LISTING FROM A |
| | (NRTL). NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | PLEASE ALSO BE SURE ALL AIC RATING FOR |
| | ALL ATS UNITS AND MAINS ARE INDICATED ON |
| | PLANS/SPECS.700.5, 701.6,702.5 NFPA-110 |
| | 6.5 |
| | 110.3,90.7 |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 6) NOTE: PLEASE SEE 225.31-225.39 FOR |
| | MISSING REQUIRED MEANS OF DISCONNECT FOR |
| | THE FEEDERS FROM THE GENERATOR UNIT. |
| | PLEASE SEE GROUPING ETC AS REQUIRED. |
| | |
| | |
| | 7) NOTE: PLEASE SEE A NOTE FOR SIGNAGE |
| | IS REQUIRED INCLUDING SIGNAL DEVICES. |
| | 700.7,700.8,701.8,701.9 |
| | |
| | 8) NOTE: PLEASE SEE 700.1 AND 701.1 |
| | EMERGENCY AND LEGALLY REQUIRED SYSTEMS |
| | MAY NOT OCCUPY THE SAME ELECTRICAL |
| | DISTRIBUTION EQUIPMENT RACEWAYS ETC. |
| | PLEASE SEE PANEL "E" IS THE SAME DIST |
| | EQUIPMENT WHICH FEEDS EM/LEGALLY AND |
| | OPTIONAL STAND-BY SYSTEMS.700.9, |
| | 701.10ETC |
| | ** PLEASE CLARIFY SYSTEMS AS SHOWN AS IT |
| | IS UNCLEAR WHY ALL ARE BEING SHOWN AS |
| | REQUIRED LS OR EM SYSTEM. |
| | |
| | 9) NOTE: PLEASEKNOW THAT ALL CODES |
| | RELEVANT TO THE DESIGN AND SCOPE PF WORK |
| | SHALL BE STATED ON PLANS. PLEASE SEE |
| | THAT THE FOLLOWING IS REQUIRED AT A |
| | MINIMUM. PLEASE KNOW AS OF JULY 1ST 2003 |
| | THE 2002 NEC WAS ADOPTED BY THE STATE. |
| | PLEASE SEE "A" SHEET WHICH SHOWS 99. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101, 2002 NFPA-110, 2004 FBC |
| | |
| | 10) NOTE: PLEASE SEE NFPA-110 7.2.2.1 AS |
| | TWICE THECLEARANCE DISTANCE FOR ATS |
| | IS REQUIRED IN MAIN ELECTRICAL ROOM AS |
| | REQUIRED PER 110.26 |
| | |
| | 11) NOTE: PLEASE SEE NFPA-110 CHAPTER 7 |
| | AS THE ELEVATION OF THE GENERATOR IS NOT |
| | STATED. PLEASE SEE MOUNTING ETC AS |
| | REQUIRED. PLEASE SEE THE ELEVATION IS |
| | REQUIRED AT A MIN OF 6" ABOVE THE |
| | FLOODING LEVEL (BFE) IF IN A FLOOD ZONE. |
| | PLEASE SEE 7.4 AND BUILDING REVIEW |
| | COMMENTS FOR REQUIRED SLAB DETAIL. |
| | |
| | 12) NOTE: PLEASE SEE MISSING DISCONNECTS |
| | FOR RTU'S WHICH COULD NOT BE LOCATED ON |
| | PLANS. CAN BE TYPICAL IF THE SAME. |
| | 440.11 |
| | PLEASE ALSO SEE MISSING ROOF TOP GFI'S |
| | WHICH COULD NOT BE LOCATED ON PLANS FOR |
| | ROOF. |
| | 230.63, 210.8 |
| | |
| | 13) NOTE: PLEASE SEE MISSING THE |
| | REQUIRED DEDICATED CIRCUITS FOR THE |
| | ELEVATOR MACHINE ROOM. |
| | 620.23,620.24 |
| | |
| | 14) NOTE: PLEASE SEE THAT AN EMERGENCY |
| | LT FIXTURE OF SOME SORT WITH BATTERY |
| | BACK UP WILL BE REQUIRED IN THE MAIN |
| | ELECTRICAL ROOM AND THE ELEVATOR MACHINE |
| | ROOM. |
| | 7.9.2.2, 700.16, 90.4 |
| | |
| | 15) NOTE: PLEASE SPECIFY THE MAX OVER |
| | RIDE TIMES FOR THE OCCUPANT SENSORS. |
| | 30MIN MAX FOR SENSORS AND 4HRS MAX FOR |
| | TIMER TYPE OVER RIDES. |
| | PLEASE ALSO SEE SEPARATE SPACES/ROOMS |
| | WHICH SEEM TO BE MISSING OVER RIDE |
| | CONTROLS. |
| | PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, |
| | .1.3 |
| | |
| | 16) NOTE: PLEASE VERIFY HOW THE ENERGY CALCULATIONS |
| | SUBMITTED ALL MENTIONS AND |
| | CONTAIN "MANUAL ON/OFF" CONTROLS FOR |
| | LIGHTING?? |
| | PLEASE SEE METHODS REQUIRED PER |
| | 13-415.1.AB.1. |
| | |
| | 17) NOTE: PLEASE SUBMIT LIGHTING POWER |
| | DENSITY CALCULATIONS AS REQUIRED. |
| | 13-415.1.AB.1,13.415.2.ABC.1 AND TABLES |
| | 415.2.C.1 AND 415.2.B.1 |
| | |
| | 18) NOTE: PLEASE SEE MISSING GROUNDING |
| | ELECTRODE DETAIL FOR THE GROUNDING |
| | ELECTRODE SYSTEM. PLEASE SEE MISSING NEW |
| | FOOTER STEEL ETC |
| | 250.50 |
| | |
| | 20) NOTE: PLEASE SEE 250.66 FOR MIN |
| | SIZING OF THE GEC. APPEARS THIS SHOULD |
| | BE 2/0 MIN. |
| | |
| | 21) NOTE: PLEASE CLARIFY THE SEPARATION |
| | OF TENANTS. PLEASE SEE PLANS AS SHOWN |
| | HAS CIRCUITING FROM EACH TENANT SERVICE |
| | CROSSING OVER INTO OTHER TENANT'S AREAS |
| | AND ROOMS. IF THEBUILDINGS GOING TO |
| | HAVE "HOUSE" POWER THESE MAY NOT FEED |
| | INTO TENANT SPACES. PLEASE ALSO SEE |
| | CIRCUITS FOR UPPER TENANT MAY NOT FEED |
| | AREAS IN LOWER TENANTS. PLEASE SEE PROPER |
| | TENANT SEPARATION AND CROSSING OVER OF |
| | CIRCUITS AND COMMON AREAS. PLEASE ADJUST CIRCUITING ON |
| | PLANS. |
| | PLEASE SEE "HOUSE" PANELS LOCATED ON |
| | FIRST FLR TENANTS SPACE? |
| | THIS IS UNCLEAR WHAT IS BEING PROPOSED |
| | IN THIS DESIGN |
| | |
| | 22) NOTE: PLEASE SEE AS KNOW "SCHEDULE |
| | WAS SUBMITTED FOR THE 800A |
| | BUS/METER CENTER, PLEASE INDICATE THE |
| | CONDUCTORS FROM THE MAIN BUS TO EACH OF |
| | THE ATS UNITS. |
| | 215.5, 240.4,310.16 |
| | |
| | 23) NOTE: PLEASE KNOW , DEPENDING ON |
| | OUTCOME OF SERVICE, PLEASE BE SURE TO |
| | LABEL MAINS. |
| | 230.2E ETC |
| | |
| | 24) NOTE: PLEASE VERIFY NEW OR EXISTING |
| | REQUIRED SIGN CIRCUIT PER 600.5 |
| | |
| | 25) NOTE: PLEASE VERIFY AND SHOW LOAD |
| | CALCULATIONS FOR SERVICE AND GENERATOR. |
| | PLEASE SEE 220.3,220.10,220.11,220.13, |
| | ETC |
| | PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.215.3,230.42 |
| | |
| | 26) NOTE: PLEASE INDICATE THE GROUNDING |
| | ELECTRODE SYSTEM AT THE GENERATOR. |
| | 250.30,250.20, 250.50 |
| | |
| | 27) NOTE: PLEASE INDICATE THE OCP AT THE GENERATOR. |
| | 106.1.2, 700,701, 702 |
| | |
| | 28) NOTE: PLEASE SEE POSSIBLE FIRE AND |
| | BUILDING REVIEW COMMENTS AS IT DID NOT |
| | SEEM PLANS WERE SUBMITTED FOR ANY |
| | BUILDING FIRE ALARM SYSTEM? |
| | |
| | ** PLEASE BE AWARE OF ANY COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE KNOW AS THERE ARE ITEMS WHICH |
| | WERE NOT SUBMITTED FOR REVIEW AND |
| | POSSIBLE CHANGES IN DESIGN, THERE MAY BE |
| | OTHER COMMENTS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |