Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-10 00:00:00*** UNSAT ***
  
 AMERICAN LUNG ASSC
  
 1) NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCKS.
 PLEASE SEE FAC 61G15-23.002 AND FS
 471.023.
 PLEASE KNOW PER THE FLORIDA STATUES AS
 NOTED ABOVE AND PER THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS, ANY FIRM
 PRACTICING ENGINEERING AND OFFERING
 ENGINEERING SERVICES MUST ALSO OBTAIN A CERTIFICATE OF
 AUTHORIZATION NUMBER FOR
 THE ENGINEERING PART OF THE BUSINESS.
 PLEASE SEE THE FIRM NUMBER AS SHOWN IS
 ONLY LICENSED FOR THE ARCHITECTURAL
 FIRM.
 PLEASE ALSO SEE ADDRESS ON TITLE BLOCK
 DO NOT CORRELATE WITH THE ADDRESS AS
 LISTED ON THE STATE'S DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 PLEASE SEE THE ATTACHED PRINT OUT
 ATTACHED TO ELECTRICAL NOTES.
 ** THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE MISSING THE PRINTED
 NAME AND LICENSE NUMBER FOR THE ENGINEER
 OF RECORDON SAID TITLE BLOCKS AS
 REQUIRED UNDER FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE A LETTER WAS
 ATTACHED FROM THE ENGINEER OF RECORD FOR VERIFICATION
 OF LEGAL SIGNATURE. PLEASE
 KNOW THE WORDING OF LETTER IS FINE,
 HOWEVER LETTER MUST BE ORIGINAL.
 (PHOTO-COPY SUBMITTED). MUST ALSO BE
 SIGNED, DATED AND SEALED BY SAID
 ENGINEER.
 PLEASE ALSO SEE THE STATUES IN WHICH
 STATE THE DOCUMENT IS BEING NOTARIZED,
 IF IN FLORIDA PLEASE SEE FS 117.05 AS IN
 THE STATE OF FLORIDA A STAMP AND
 SIGNATURE OF NOTARY IS NOT ALL THAT IS
 REQUIRED FOR A LEGAL DOCUMENT.
  
 4) NOTE: PLEASE SEE SURVEY SUBMITTED IN
 INDEED A PHOTO-COPY OF THE SIGNATURE
 WITH A RAISED SEAL OVER PHOTO-COPIED
 SIGNATURE WHICH IS NOT PERMITTED UNDER
 FAC 61G17, FS 472.025
 PLEASE ALSO SEE THAT THE RAISED SEAL
 MUST BE CLEAR AND VISIBLE WITH ALL
 INFORMATION ON SAID SEAL. (NOT VISIBLE AT
 THIS TIME).
 PLEASE CORRELATE THE SURVEY WITH THE
 ELECTRICAL PLANS, AS THE E-SHEETS
 INDICATE ANEW GENERATOR.(PLEASE SEE
 ZONING COMMENTS FOR THIS.
  
 5) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR THE NEW GENERATOR,
 NEW SUB-BASE FUEL TANK AND EACH OF THE
 PROPOSED ATS SWITCHES.
 PLEASE SEE THAT ALL SPEC SHEETS FOR THE
 ATS UNITS CONTAINS A LISTING FROM A
 (NRTL). NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 PLEASE ALSO BE SURE ALL AIC RATING FOR
 ALL ATS UNITS AND MAINS ARE INDICATED ON
 PLANS/SPECS.700.5, 701.6,702.5 NFPA-110
 6.5
 110.3,90.7
 FBC 106.1.2 ADMIN SECT.
  
 6) NOTE: PLEASE SEE 225.31-225.39 FOR
 MISSING REQUIRED MEANS OF DISCONNECT FOR
 THE FEEDERS FROM THE GENERATOR UNIT.
 PLEASE SEE GROUPING ETC AS REQUIRED.
  
  
 7) NOTE: PLEASE SEE A NOTE FOR SIGNAGE
 IS REQUIRED INCLUDING SIGNAL DEVICES.
 700.7,700.8,701.8,701.9
  
 8) NOTE: PLEASE SEE 700.1 AND 701.1
 EMERGENCY AND LEGALLY REQUIRED SYSTEMS
 MAY NOT OCCUPY THE SAME ELECTRICAL
 DISTRIBUTION EQUIPMENT RACEWAYS ETC.
 PLEASE SEE PANEL "E" IS THE SAME DIST
 EQUIPMENT WHICH FEEDS EM/LEGALLY AND
 OPTIONAL STAND-BY SYSTEMS.700.9,
 701.10ETC
 ** PLEASE CLARIFY SYSTEMS AS SHOWN AS IT
 IS UNCLEAR WHY ALL ARE BEING SHOWN AS
 REQUIRED LS OR EM SYSTEM.
  
 9) NOTE: PLEASEKNOW THAT ALL CODES
 RELEVANT TO THE DESIGN AND SCOPE PF WORK
 SHALL BE STATED ON PLANS. PLEASE SEE
 THAT THE FOLLOWING IS REQUIRED AT A
 MINIMUM. PLEASE KNOW AS OF JULY 1ST 2003
 THE 2002 NEC WAS ADOPTED BY THE STATE.
 PLEASE SEE "A" SHEET WHICH SHOWS 99.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101, 2002 NFPA-110, 2004 FBC
  
 10) NOTE: PLEASE SEE NFPA-110 7.2.2.1 AS
 TWICE THECLEARANCE DISTANCE FOR ATS
 IS REQUIRED IN MAIN ELECTRICAL ROOM AS
 REQUIRED PER 110.26
  
 11) NOTE: PLEASE SEE NFPA-110 CHAPTER 7
 AS THE ELEVATION OF THE GENERATOR IS NOT
 STATED. PLEASE SEE MOUNTING ETC AS
 REQUIRED. PLEASE SEE THE ELEVATION IS
 REQUIRED AT A MIN OF 6" ABOVE THE
 FLOODING LEVEL (BFE) IF IN A FLOOD ZONE.
 PLEASE SEE 7.4 AND BUILDING REVIEW
 COMMENTS FOR REQUIRED SLAB DETAIL.
  
 12) NOTE: PLEASE SEE MISSING DISCONNECTS
 FOR RTU'S WHICH COULD NOT BE LOCATED ON
 PLANS. CAN BE TYPICAL IF THE SAME.
 440.11
 PLEASE ALSO SEE MISSING ROOF TOP GFI'S
 WHICH COULD NOT BE LOCATED ON PLANS FOR
 ROOF.
 230.63, 210.8
  
 13) NOTE: PLEASE SEE MISSING THE
 REQUIRED DEDICATED CIRCUITS FOR THE
 ELEVATOR MACHINE ROOM.
 620.23,620.24
  
 14) NOTE: PLEASE SEE THAT AN EMERGENCY
 LT FIXTURE OF SOME SORT WITH BATTERY
 BACK UP WILL BE REQUIRED IN THE MAIN
 ELECTRICAL ROOM AND THE ELEVATOR MACHINE
 ROOM.
 7.9.2.2, 700.16, 90.4
  
 15) NOTE: PLEASE SPECIFY THE MAX OVER
 RIDE TIMES FOR THE OCCUPANT SENSORS.
 30MIN MAX FOR SENSORS AND 4HRS MAX FOR
 TIMER TYPE OVER RIDES.
 PLEASE ALSO SEE SEPARATE SPACES/ROOMS
 WHICH SEEM TO BE MISSING OVER RIDE
 CONTROLS.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2,
 .1.3
  
 16) NOTE: PLEASE VERIFY HOW THE ENERGY CALCULATIONS
 SUBMITTED ALL MENTIONS AND
 CONTAIN "MANUAL ON/OFF" CONTROLS FOR
 LIGHTING??
 PLEASE SEE METHODS REQUIRED PER
 13-415.1.AB.1.
  
 17) NOTE: PLEASE SUBMIT LIGHTING POWER
 DENSITY CALCULATIONS AS REQUIRED.
 13-415.1.AB.1,13.415.2.ABC.1 AND TABLES
 415.2.C.1 AND 415.2.B.1
  
 18) NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE DETAIL FOR THE GROUNDING
 ELECTRODE SYSTEM. PLEASE SEE MISSING NEW
 FOOTER STEEL ETC
 250.50
  
 20) NOTE: PLEASE SEE 250.66 FOR MIN
 SIZING OF THE GEC. APPEARS THIS SHOULD
 BE 2/0 MIN.
  
 21) NOTE: PLEASE CLARIFY THE SEPARATION
 OF TENANTS. PLEASE SEE PLANS AS SHOWN
 HAS CIRCUITING FROM EACH TENANT SERVICE
 CROSSING OVER INTO OTHER TENANT'S AREAS
 AND ROOMS. IF THEBUILDINGS GOING TO
 HAVE "HOUSE" POWER THESE MAY NOT FEED
 INTO TENANT SPACES. PLEASE ALSO SEE
 CIRCUITS FOR UPPER TENANT MAY NOT FEED
 AREAS IN LOWER TENANTS. PLEASE SEE PROPER
 TENANT SEPARATION AND CROSSING OVER OF
 CIRCUITS AND COMMON AREAS. PLEASE ADJUST CIRCUITING ON
 PLANS.
 PLEASE SEE "HOUSE" PANELS LOCATED ON
 FIRST FLR TENANTS SPACE?
 THIS IS UNCLEAR WHAT IS BEING PROPOSED
 IN THIS DESIGN
  
 22) NOTE: PLEASE SEE AS KNOW "SCHEDULE
 WAS SUBMITTED FOR THE 800A
 BUS/METER CENTER, PLEASE INDICATE THE
 CONDUCTORS FROM THE MAIN BUS TO EACH OF
 THE ATS UNITS.
 215.5, 240.4,310.16
  
 23) NOTE: PLEASE KNOW , DEPENDING ON
 OUTCOME OF SERVICE, PLEASE BE SURE TO
 LABEL MAINS.
 230.2E ETC
  
 24) NOTE: PLEASE VERIFY NEW OR EXISTING
 REQUIRED SIGN CIRCUIT PER 600.5
  
 25) NOTE: PLEASE VERIFY AND SHOW LOAD
 CALCULATIONS FOR SERVICE AND GENERATOR.
 PLEASE SEE 220.3,220.10,220.11,220.13,
 ETC
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.215.3,230.42
  
 26) NOTE: PLEASE INDICATE THE GROUNDING
 ELECTRODE SYSTEM AT THE GENERATOR.
 250.30,250.20, 250.50
  
 27) NOTE: PLEASE INDICATE THE OCP AT THE GENERATOR.
 106.1.2, 700,701, 702
  
 28) NOTE: PLEASE SEE POSSIBLE FIRE AND
 BUILDING REVIEW COMMENTS AS IT DID NOT
 SEEM PLANS WERE SUBMITTED FOR ANY
 BUILDING FIRE ALARM SYSTEM?
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 ** PLEASE KNOW AS THERE ARE ITEMS WHICH
 WERE NOT SUBMITTED FOR REVIEW AND
 POSSIBLE CHANGES IN DESIGN, THERE MAY BE
 OTHER COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved