Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 2.)PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
 3.)A PRELIMINARY SURVEY WAS SUBMITTED,
 BUT APPEARS TO HAVE BEEN REPLACED BY A
 FINAL SURVEY.REMOVE THE PRELIMINARY
 FROM THE PACKAGE OR CLARIFY AS TO ITS
 PURPOSE AS THE INFORMATION ON IT IS
 INCOMPLETE.
  
 4.)SHEET C7, PARKING IS TO COMPLY WITH
 CITY OF WEST PALM BEACH STANDARD, SEE
 ATTACHED.
  
 5.)SEPARATE PERMIT REQUIRED FOR THE
 DUMPSTER ENCLOSURE.PLEASE COMPLETE A
 PERMIT APPLICATION; SEPARATE PLANS ARE
 NOT REQUIRED.
  
 6.)PROVIDE MAXIMUM SLOPES FOR THE
 ACCESSIBLE ROUTE SHEET SP1 OR C5,
 FBC11-4.1.2(1).
  
 7.)CODE DATE, SHEET G0-00-001, INCLUDE
 SPRINKLER INFORMATION (APPEARS TO BE
 FULLY SPRINKLED), BUILDING AREA
 (EXISTING, PROPOSED ADDITION, NEW
 TOTAL).
  
 8.)A0-00-601 STATES THAT THE BUILDING
 IS 30FT FROM THE PROPERTY LINE, SP1
 SHOWS A DISTANCE OF 27.97 ON THE SOUTH
 SIDE.IT APPEARS THAT NO FIRE
 RESISTANCE IS REQUIRED PER FBC TABLE
 602, BUT PLEASE REVISE THE NOTE.
  
 9.)SHOW SIDEWALK WIDTH AT ACCESSIBLE
 PARKING SPACE ON SHEET A0-00-601,
 FBC11-4.6.2(1).44IN MINIMUM REQUIRED.
 A DETAIL IS SHOWN ELSEWHERE ON THE PLAN
 BUT WHEN SCALED THE SIDEWALK APPEARS TO
 BE 24IN.
  
 10.)SHEET A0-00-601 REFERS TO
 ASCE7-98, CORRECT REFERENCE IS 7-02,
 FBC35.
  
 11.)SEE FBC313, FBC406.1.SHOW
 OCCUPANCY CLASSIFICATION FOR THE GARAGE,
 TOTAL SF FOR GARAGE AREA.IF OCCUPANCY
 SEPARATION IS USED, IT MUST BE IN
 COMPLIANCE WITH FBC TABLE 302.3.2,
 FBC406.2.7, PENETRATIONS IN COMPLIANCE
 WITH FBC712 (M1-01-101).REVISE
 BUILDING ALLOWABLE AREA CALCULATIONS,
 FBC 5.
  
 12.)SEE FBC1013.2.THE LIFE SAFETY
 PLAN A0-00-601 SHOWS THE STAIR 2
 TERMINATING IN THE COVERED PARKING AREA.
 NO DOORS SHOWN FROM THE GARAGE TO THE
 OUTSIDE, GATE DOES NOT COMPLY WITH
 FBC1008.1.2 EXCEPTIONS.THIS MAY SERVE
 AS EGRESS FROM THE PARKING GARAGE, SEE
 EXCEPTION 1, BUT NOT FROM THE BUSINESS
 AREA.ALSO SEE FBC1013.2 REGARDING
 EGRESS THROUGH INTERVENING SPACES.
  
 13.)DETAIL 4-A2-02-001, THE SINK IS TO
 BE MOUNTED NO HIGHER THAN 34IN
 FBC11-4.24.2.PROVIDE A DETAIL FOR THE
 SINK, SEE FBC11-4.24.NOTE THAT CABINET
 DOORS NOT PERMITTED AS IT PREVENTS THE
 KNEE CLEARANCE REQUIRED BY FBC11-4.24.3.
  
 14.)DETAILS 21 AND 13, SHEET
 A7-02-101, CABINET DOORS NOT PERMITTED
 AS IT PREVENTS THE SINK KNEE CLEARANCE
 REQUIRED BY FBC11-4.24.3
  
 15.)THE BUILDING APPEARS TO BE THREE
 STORIES IN THE STAIRWAY.SEE SHEET
 A6-00-101.TWO STORY BUILDING DECLARED
 ON A0-00-601.
  
 16.)DECLARE AN OCCUPANT LOAD FOR THE
 ROOF TERRACE AND ROOF GARDEN AREAS.
  
 17.)SECTION 2-A6-00-101, THE STAIR
 RAIL IS TO EITHER BE ROUNDED OR RETURN
 TO THE FLOOR, WALL, OR POST.A STRAIGHT
 EXTENSION IS SHOWN.
  
 18.)SECTION 2-A6-00-101, THE AREA
 UNDER THE STAIR LACKS THE HEADROOM
 REQUIRED BY FBC11-4.4.2, BARRIER
 REQUIRED.
  
 19.)A9-01-201 INDICATES THAT BATHROOM
 WALL FINISHES ARE TO BE DETERMINED.SEE
 FBC1210.2, HARD NONABSORBENT SURFACE
 REQUIRED.
  
 20.)NO PENETRATIONS ALLOWED IN THE
 EXIT ENCLOSURE (STAIRS), FBC1-019.1.2,
 SEE MECHANICAL SHEETS.
  
 21.)SPECIFY FIRE RATING FOR FIRE RATED
 DOORS, FC TABLE 715.3, SHEET A8-00-101.
  
  
 22.)SPECIFY ANCHORING FOR THE
 GENERATOR, FBC1606.1.3, UNLESS THIS WILL
 BE ON A SEPARATE PERMIT.
  
 23.)STRUCTURALS STATE THAT MRH IS
 24FT.NOTE THAT THE STAIR ROOF IS AT
 APPROXIMATELY 37FT.DESIGN PRESSURES
 APPEAR COMPLIANT AS THE HIGHER SECTION
 IS A PITCHED ROOF, BUT PLEASE ADDRESS ON
 THE PLAN.
  
 24.)ON THE YHS 50 STOREFRONT PRODUCT
 APPROVAL, INDICATE WHICH PRODUCT YOU ARE
 USING AS NOT ALL MEET WORST CASE FOR
 WIND LOADS.
  
 25.)FOR THE MULLION PRODUCT APPROVAL,
 INDICATE WHICH PRODUCT YOU ARE
 INSTALLING.
  
 26.)FOR THE PICTURE WINDOW PRODUCT
 APPROVAL, INDICATE WHICH PRODUCT YOU ARE
 INSTALLING.
  
 27.)ANY PRODUCT APPROVALS REQUIRED BY
 FAC9B72 AND NOT SUBMITTED PRIOR TO
 PERMIT ISSUANCE WILL REQUIRE SEPARATE
 PERMITS; FOR INSTANCE, THE FLAT DECK
 ROOF AND THE EXTERIOR METAL DOORS.FOR
 THE FLAT DECK, INDICATE WHICH APPROVED
 ASSEMBLY YOU WILL BE USING.
  
 28.)SHOW COMPLIANCE WITH FBC1014.2.1,
 EXCEPTION 2, EXITS TO BE LOCATED MORE
 THAN 1/3 THE DIAGONAL APART.