| 2006-10-05 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | |
| | 1.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 2.)PRODUCT APPROVALS TO BE REVIEWED BY |
| | DESIGNER OF RECORD, FBC*106.3.3. |
| | |
| | 3.)A PRELIMINARY SURVEY WAS SUBMITTED, |
| | BUT APPEARS TO HAVE BEEN REPLACED BY A |
| | FINAL SURVEY.REMOVE THE PRELIMINARY |
| | FROM THE PACKAGE OR CLARIFY AS TO ITS |
| | PURPOSE AS THE INFORMATION ON IT IS |
| | INCOMPLETE. |
| | |
| | 4.)SHEET C7, PARKING IS TO COMPLY WITH |
| | CITY OF WEST PALM BEACH STANDARD, SEE |
| | ATTACHED. |
| | |
| | 5.)SEPARATE PERMIT REQUIRED FOR THE |
| | DUMPSTER ENCLOSURE.PLEASE COMPLETE A |
| | PERMIT APPLICATION; SEPARATE PLANS ARE |
| | NOT REQUIRED. |
| | |
| | 6.)PROVIDE MAXIMUM SLOPES FOR THE |
| | ACCESSIBLE ROUTE SHEET SP1 OR C5, |
| | FBC11-4.1.2(1). |
| | |
| | 7.)CODE DATE, SHEET G0-00-001, INCLUDE |
| | SPRINKLER INFORMATION (APPEARS TO BE |
| | FULLY SPRINKLED), BUILDING AREA |
| | (EXISTING, PROPOSED ADDITION, NEW |
| | TOTAL). |
| | |
| | 8.)A0-00-601 STATES THAT THE BUILDING |
| | IS 30FT FROM THE PROPERTY LINE, SP1 |
| | SHOWS A DISTANCE OF 27.97 ON THE SOUTH |
| | SIDE.IT APPEARS THAT NO FIRE |
| | RESISTANCE IS REQUIRED PER FBC TABLE |
| | 602, BUT PLEASE REVISE THE NOTE. |
| | |
| | 9.)SHOW SIDEWALK WIDTH AT ACCESSIBLE |
| | PARKING SPACE ON SHEET A0-00-601, |
| | FBC11-4.6.2(1).44IN MINIMUM REQUIRED. |
| | A DETAIL IS SHOWN ELSEWHERE ON THE PLAN |
| | BUT WHEN SCALED THE SIDEWALK APPEARS TO |
| | BE 24IN. |
| | |
| | 10.)SHEET A0-00-601 REFERS TO |
| | ASCE7-98, CORRECT REFERENCE IS 7-02, |
| | FBC35. |
| | |
| | 11.)SEE FBC313, FBC406.1.SHOW |
| | OCCUPANCY CLASSIFICATION FOR THE GARAGE, |
| | TOTAL SF FOR GARAGE AREA.IF OCCUPANCY |
| | SEPARATION IS USED, IT MUST BE IN |
| | COMPLIANCE WITH FBC TABLE 302.3.2, |
| | FBC406.2.7, PENETRATIONS IN COMPLIANCE |
| | WITH FBC712 (M1-01-101).REVISE |
| | BUILDING ALLOWABLE AREA CALCULATIONS, |
| | FBC 5. |
| | |
| | 12.)SEE FBC1013.2.THE LIFE SAFETY |
| | PLAN A0-00-601 SHOWS THE STAIR 2 |
| | TERMINATING IN THE COVERED PARKING AREA. |
| | NO DOORS SHOWN FROM THE GARAGE TO THE |
| | OUTSIDE, GATE DOES NOT COMPLY WITH |
| | FBC1008.1.2 EXCEPTIONS.THIS MAY SERVE |
| | AS EGRESS FROM THE PARKING GARAGE, SEE |
| | EXCEPTION 1, BUT NOT FROM THE BUSINESS |
| | AREA.ALSO SEE FBC1013.2 REGARDING |
| | EGRESS THROUGH INTERVENING SPACES. |
| | |
| | 13.)DETAIL 4-A2-02-001, THE SINK IS TO |
| | BE MOUNTED NO HIGHER THAN 34IN |
| | FBC11-4.24.2.PROVIDE A DETAIL FOR THE |
| | SINK, SEE FBC11-4.24.NOTE THAT CABINET |
| | DOORS NOT PERMITTED AS IT PREVENTS THE |
| | KNEE CLEARANCE REQUIRED BY FBC11-4.24.3. |
| | |
| | 14.)DETAILS 21 AND 13, SHEET |
| | A7-02-101, CABINET DOORS NOT PERMITTED |
| | AS IT PREVENTS THE SINK KNEE CLEARANCE |
| | REQUIRED BY FBC11-4.24.3 |
| | |
| | 15.)THE BUILDING APPEARS TO BE THREE |
| | STORIES IN THE STAIRWAY.SEE SHEET |
| | A6-00-101.TWO STORY BUILDING DECLARED |
| | ON A0-00-601. |
| | |
| | 16.)DECLARE AN OCCUPANT LOAD FOR THE |
| | ROOF TERRACE AND ROOF GARDEN AREAS. |
| | |
| | 17.)SECTION 2-A6-00-101, THE STAIR |
| | RAIL IS TO EITHER BE ROUNDED OR RETURN |
| | TO THE FLOOR, WALL, OR POST.A STRAIGHT |
| | EXTENSION IS SHOWN. |
| | |
| | 18.)SECTION 2-A6-00-101, THE AREA |
| | UNDER THE STAIR LACKS THE HEADROOM |
| | REQUIRED BY FBC11-4.4.2, BARRIER |
| | REQUIRED. |
| | |
| | 19.)A9-01-201 INDICATES THAT BATHROOM |
| | WALL FINISHES ARE TO BE DETERMINED.SEE |
| | FBC1210.2, HARD NONABSORBENT SURFACE |
| | REQUIRED. |
| | |
| | 20.)NO PENETRATIONS ALLOWED IN THE |
| | EXIT ENCLOSURE (STAIRS), FBC1-019.1.2, |
| | SEE MECHANICAL SHEETS. |
| | |
| | 21.)SPECIFY FIRE RATING FOR FIRE RATED |
| | DOORS, FC TABLE 715.3, SHEET A8-00-101. |
| | |
| | |
| | 22.)SPECIFY ANCHORING FOR THE |
| | GENERATOR, FBC1606.1.3, UNLESS THIS WILL |
| | BE ON A SEPARATE PERMIT. |
| | |
| | 23.)STRUCTURALS STATE THAT MRH IS |
| | 24FT.NOTE THAT THE STAIR ROOF IS AT |
| | APPROXIMATELY 37FT.DESIGN PRESSURES |
| | APPEAR COMPLIANT AS THE HIGHER SECTION |
| | IS A PITCHED ROOF, BUT PLEASE ADDRESS ON |
| | THE PLAN. |
| | |
| | 24.)ON THE YHS 50 STOREFRONT PRODUCT |
| | APPROVAL, INDICATE WHICH PRODUCT YOU ARE |
| | USING AS NOT ALL MEET WORST CASE FOR |
| | WIND LOADS. |
| | |
| | 25.)FOR THE MULLION PRODUCT APPROVAL, |
| | INDICATE WHICH PRODUCT YOU ARE |
| | INSTALLING. |
| | |
| | 26.)FOR THE PICTURE WINDOW PRODUCT |
| | APPROVAL, INDICATE WHICH PRODUCT YOU ARE |
| | INSTALLING. |
| | |
| | 27.)ANY PRODUCT APPROVALS REQUIRED BY |
| | FAC9B72 AND NOT SUBMITTED PRIOR TO |
| | PERMIT ISSUANCE WILL REQUIRE SEPARATE |
| | PERMITS; FOR INSTANCE, THE FLAT DECK |
| | ROOF AND THE EXTERIOR METAL DOORS.FOR |
| | THE FLAT DECK, INDICATE WHICH APPROVED |
| | ASSEMBLY YOU WILL BE USING. |
| | |
| | 28.)SHOW COMPLIANCE WITH FBC1014.2.1, |
| | EXCEPTION 2, EXITS TO BE LOCATED MORE |
| | THAN 1/3 THE DIAGONAL APART. |