Plan Review Notes
Plan Review Notes For Permit 06082182
Permit Number 06082182
Review Stop E
Sequence Number 3
Notes
Date Text
2007-01-24 10:22:58 
 THE FOLLOWING CODE ARTICLES MUST BE COMPLIED WITH
 REGARDING THIS INSTALLATION.
  
 (B) GROUNDED CONDUCTOR BROUGHT TO SERVICE EQUIPMENT.
 WHERE AN AC SYSTEM OPERATING AT LESS THAN 1000 VOLTS IS
 GROUNDED AT ANY POINT, THE GROUNDED CONDUCTOR(S) SHALL
 BE RUN TO EACH SERVICE DISCONNECTING MEANS AND SHALL BE
 BONDED TO EACH DISCONNECTING MEANS ENCLOSURE. THE
 GROUNDED CONDUCTOR(S) SHALL BE INSTALLED IN ACCORDANCE
 WITH 250.24(B)(1) THROUGH (B)(3).
  
 1) ROUTING AND SIZING. THIS CONDUCTOR SHALL BE ROUTED
 WITH THE PHASE CONDUCTORS AND SHALL NOT BE SMALLER THAN
 THE REQUIRED GROUNDING ELECTRODE CONDUCTOR SPECIFIED IN
 TABLE 250.66 BUT SHALL NOT BE REQUIRED TO BE LARGER
 THAN THE LARGEST UNGROUNDED SERVICE-ENTRANCE PHASE
 CONDUCTOR. IN ADDITION, FOR SERVICE-ENTRANCE PHASE
 CONDUCTORS LARGER THAN 1100 KCMIL COPPER OR 1750 KCMIL
 ALUMINUM, THE GROUNDED CONDUCTOR SHALL NOT BE SMALLER
 THAN 12? PERCENT OF THE AREA OF THE LARGEST
 SERVICE-ENTRANCE PHASE CONDUCTOR. THE GROUNDED SERVICE
 ENTRANCE CONDUCTOR OF A 3-PHASE, 3-WIRE DELTA SERVICE
 SHALL HAVE AN AMPACITY NOT LESS THAN THE UNGROUNDED
 CONDUCTORS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718