Plan Review Notes
Plan Review Notes For Permit 06082182
Permit Number 06082182
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-07 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 3/0 CONDUCTORS DO NOT HAVE THE
 AMPACITY FOR A 225 AMPERE FEED. 310.16.
 IT WOULD APPEAR THAT A TAP RULE IS BEING
 INVOKED, BUT THERE ARE NO ARTICLES FOR
 TAP RULES FOR SERVICE CONDUCTORS, ONLY
 FEEDERS,AND BRANCH CIRCUITS,240.21(A)
 THROUGH (G), WHICH DOES NOT APPLY.
  
 2} A DISCONNECING MEANS IS REQUIRED FOR
 THE SERVICE CONDUCTORS PER 230.70 AND
 LOCATED PER 230.70(A).
  
 3} THERE IS NO OVERCURRENT PROTECTION
 FOR THE SERVICE CONDUCTORS PER 230.90,
 240.21.
  
 4} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH 250.66, 1/0 FOR 500 MCM
 SERVICE CONDUCTORS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  