| Plan Review Notes For Permit 06082182 |
| Permit Number |
06082182 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-07 00:00:00 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE 3/0 CONDUCTORS DO NOT HAVE THE | | | AMPACITY FOR A 225 AMPERE FEED. 310.16. | | | IT WOULD APPEAR THAT A TAP RULE IS BEING | | | INVOKED, BUT THERE ARE NO ARTICLES FOR | | | TAP RULES FOR SERVICE CONDUCTORS, ONLY | | | FEEDERS,AND BRANCH CIRCUITS,240.21(A) | | | THROUGH (G), WHICH DOES NOT APPLY. | | | | | | 2} A DISCONNECING MEANS IS REQUIRED FOR | | | THE SERVICE CONDUCTORS PER 230.70 AND | | | LOCATED PER 230.70(A). | | | | | | 3} THERE IS NO OVERCURRENT PROTECTION | | | FOR THE SERVICE CONDUCTORS PER 230.90, | | | 240.21. | | | | | | 4} THE GROUNDING ELECTRODE CONDUCTOR | | | MUST COMPLY WITH 250.66, 1/0 FOR 500 MCM | | | SERVICE CONDUCTORS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|