2007-04-17 10:49:22REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A UNION IS REQUIRED FOR THE REGULATOR. THE UNION CAN
 NOT BE IN THE CEILING IF IT IS A DROPPED CEILING OR
 HARD CEILING.
  
 2, TALKED TO CONTRACTOR. A REGULATOR IS NOT REQUIRED IF
 THE SECTION OF PIPE UPSTREAM OF THE SIX CHAMBER WOK
 RANGE MAINTAINS 3" PIPE SIZE.TABLE 402.4(6). THE
 CONTRACTOR INDICATED HE WILL DELETE THE REGULATOR AND
 SHUT OFF VALVE AND MAINTAIN 3" PIPE TO THE WOK RANGE.
 ITEM #41.
  
 3. A NEW REVISION WILL BE REQUIRED SHOWING CHANGES.
 (SHOWS EXISTING CHANGED FROM 4" TO 3" PIPE.
  