| Plan Review Notes For Permit 06082089 |
| Permit Number |
06082089 |
|
| Review Stop |
G |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-04-17 10:49:22 | REVISION DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. A UNION IS REQUIRED FOR THE REGULATOR. THE UNION CAN | | | NOT BE IN THE CEILING IF IT IS A DROPPED CEILING OR | | | HARD CEILING. | | | | | | 2, TALKED TO CONTRACTOR. A REGULATOR IS NOT REQUIRED IF | | | THE SECTION OF PIPE UPSTREAM OF THE SIX CHAMBER WOK | | | RANGE MAINTAINS 3" PIPE SIZE.TABLE 402.4(6). THE | | | CONTRACTOR INDICATED HE WILL DELETE THE REGULATOR AND | | | SHUT OFF VALVE AND MAINTAIN 3" PIPE TO THE WOK RANGE. | | | ITEM #41. | | | | | | 3. A NEW REVISION WILL BE REQUIRED SHOWING CHANGES. | | | (SHOWS EXISTING CHANGED FROM 4" TO 3" PIPE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|