2007-05-17 16:47:59** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE GO OVER LOAD CALCULATIONS ON SHEET AND
 LOADS ON PANELS AS THESE DO NOT CORRELATE.
 PLEASE COORDINATE THESE LOADS AND VERIFY THE LOAD ON
 THE TRANSFORMER AS IT SEEM TO BE NOW SHOWN RIGHT AT ITS
 MAXIMUM RATING WITHOUT ANY ROOM FOR EXPANSION. PLEASE
 SEE LOADS AS SHOWN ON THIS DOES NOT LEAVE ROOM FOR THE
 ADDITION OF ONE CIRCUIT OR ANY LOAD AS REQUIRED PER
 90.8.
 PLEASE SEE 220 AND GO OVER ALL LOAD CALCULATIONS PER
 NEC AND COORDINATE.
  
 2) NOTE: PLEASE SEE THE VALUE FROM THE ORIGINAL APPLIED
 SCOPE OF WORK HAS SUBSTANTIALLY INCREASED AND FEES ARE
 DUE FOR INCREASED CONTRACT VALUE PER FBC 108.3
 THIS VALUE INCREASE IS BASED ON THE LAST SET OF
 BUILDING REVISIONS WHICH INCREASED SCOPE OF WORK.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  