| Date |
Text |
| 2007-02-02 11:08:08 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 10. SHT FP1.2 THE FOLLOWING INFORMATION |
| | IS REQUIRED FOR GAS PERMIT: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE FROM ENGINEER NOTED, BUT NO MANUF. |
| | SPECIFICATION SHEETS SHOWING THE LISTING, THE MODEL |
| | NUMBER, OR THE BTU LOAD INDICATED HAS BEEN SUBMITTED. |
| | ******RESPONSE NOTED, BUT ITEM 41 CHAMBER WOK. INDICATE |
| | WHICH MODEL "RINGS, TIP, TIP VERTICAL SHIELD/TIP ANGLE |
| | SHIELD, TIP NO CLOG WILL BE USED TO ADD UP TO 450,000 |
| | BTU.--ITEM 45 INDICATES 6 BURNER RANGE/CONVECTION |
| | OVENS ON THE KITCHEN EQUIPMENT CONNECTION SCHEDULE, BUT |
| | MANUF. SPECIFICATION SHEET INDICATES STAKEHOUSE |
| | BROILERS, AND THE BTU'S DO NOT REFLECT THE EQUIPMENT |
| | CONNECTION SCHEDULE. PLEASE CORRELATE INFORMATION. |
| | |
| | F. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****RESPONSE NOTED, BUT ONLY ONE VALVE IS SHOWN ON THE |
| | RISER DIAGRAM. IT IS NOT INDICATED IF IT IS THE MANUAL |
| | SHUT OFF VALVE OR THE EMERGENCY SHUT OFF VALVE. BOTH |
| | VALVES ARE REQUIRED. ALSO NO UNION IS INDICATED |
| | DOWNSTREAM OF THE MANUAL AS REQUIRED. ******RESPONSE |
| | NOTED, BUT THE MANUAL SHUT OFF VALVE SHOWN IN THE |
| | CEILING IS NOT REQUIRED. BECAUSE THE EXISTING MANUAL |
| | SHUT OFF VALVE BELOW THE CEILING UPSTREAM OF THE |
| | SOLENOID WAS NOT INDICATED ON THE PREVIOUS SUBMITTALS, |
| | THE REQUIREMENT FOR THE MANUAL SHUT OFF VALVE WAS |
| | INDICATED. |
| | |
| | G. OK - USING 402.4(6) BECAUSE 402.4(2) ONLY GOES UP TO |
| | 200 FT, AND THE DEVELOPED LENGTH IS 238.5 FT. MINIMUM |
| | 2-1/2" IS REQUIRED UP TO THE FIRST ITEM #29 PER THE |
| | TABLE. 2" IS INDICATED. PLEASE CHANGE PIPE SIZE. |
| | |
| | I. (NEW GAS COMMENT)BTU LOAD OF EACH APPLIANCE AND |
| | THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | J. (NEW GAS COMMENT) THE DRIPS INSTALLED AT THE ENDS OF |
| | THE GAS LINES SHOULD BE INSTALLED, (1), AT THE BOTTOM |
| | OF THE DROP WHERE THE GAS LINE SPLITS INTO TWO LINES TO |
| | KEEP THE MOISTURE OUT OF THE GAS EQUIPMENT. SECTION |
| | 408.2. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |