2007-02-06 17:57:41*****UNSAT******
  
 RESPONSES TO THE PREVIOUS FIRE PLAN REVIEW OF 12/01/06
 RECEIVED AS FOLLOWS:
  
  
 2.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.NFPA 241 WAS ADDED TO THE
 SHEET G1.1 UNDER APPLICABLE CODES, HOWEVER IT IS NOT A
 LIFE SAFETY CODE
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIALS, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.YOUR RESPONSE TO MY COMMENT WAS
 "SHALL INSTRUCT CONTRACTOR TO COMPLY."BETTER YET, ADD
 IT TO THE PLAN
  
 *****REMINDER******
  
 IN REFERENCE TO ADDRESS SIGNAGE (SEE SHEET LS1.1)
 NUMERALS SHALL NOT BE LESS THAN 6 INCHES IN HEIGHT AND
 NO LESS THAN 1 INCH IN WIDTH
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCL;UDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS
 ADDRESSED
  
  