| Plan Review Notes For Permit 06082089 |
| Permit Number |
06082089 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-02-06 17:57:41 | *****UNSAT****** | | | | | | RESPONSES TO THE PREVIOUS FIRE PLAN REVIEW OF 12/01/06 | | | RECEIVED AS FOLLOWS: | | | | | | | | | 2.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241.NFPA 241 WAS ADDED TO THE | | | SHEET G1.1 UNDER APPLICABLE CODES, HOWEVER IT IS NOT A | | | LIFE SAFETY CODE | | | | | | 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE | | | MATERIALS, DUST, AND DEBRIS SHALL BE | | | REMOVED FROM THE STRUCTURE AND ITS | | | IMMEDIATE VICINITY AT THE END OF EACH | | | SHIFT OR MORE FREQUENTLY AS NECESSARY | | | FOR SAFE OPERATIONS.YOUR RESPONSE TO MY COMMENT WAS | | | "SHALL INSTRUCT CONTRACTOR TO COMPLY."BETTER YET, ADD | | | IT TO THE PLAN | | | | | | *****REMINDER****** | | | | | | IN REFERENCE TO ADDRESS SIGNAGE (SEE SHEET LS1.1) | | | NUMERALS SHALL NOT BE LESS THAN 6 INCHES IN HEIGHT AND | | | NO LESS THAN 1 INCH IN WIDTH | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCL;UDE A | | | RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|