Plan Review Notes
Plan Review Notes For Permit 06082089
Permit Number 06082089
Review Stop E
Sequence Number 3
Notes
Date Text
2007-01-13 20:08:12*** UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW(S) WHICH
 STILL NEED TO BE ADDRESSED.
 PLEASE SEE THE RESPONSE LETTER MENTIONS: "WILL COMPLY
 AND SEE REVISED SHEETS", HOWEVER COMPLIANCE HAS NOT
 BEEN DONE AND ELECTRICAL PLANS AND RISER FOR SERVICE
 HAVE NOW BEEN COMPLETELY CHANGED FROM THE PREVIOUS
 SUBMITTED PLANS.
 PLEASE SEE THERE ARE ALSO SOME NEW COMMENTS BASED ON
 THE REVISED RISER DIAGRAM AND PANEL SCHEDULES
 SUBMITTED.
  
  
 1) NOTE: PLEASE SEE THE SERVICE HAS NOW BEEN COMPLETELY
 BEEN REVISED. PLEASE SEE RISER NO SHOWS H1A AS A 400AMP
 PANEL. PLEASE KNOW THAT THE LOAD CALCULATIONS FOR
 SERVICE HAVE NOT YET BEEN UPDATED THROUGH-OUT THE
 SERVICE PROVIDED TO THE SPACE. PLEASE SEE "H1A" WHICH
 FEEDS ALL OTHER PANELS. PLEASE SEE THAT THERE ARE LOADS
 ON THIS PANEL WHICH ARE BLANK WITH ZERO LOADS SHOWN??
 HOW IS IT POSSIBLE THAT NO RECEPTACLE LOADS ARE PRESENT
 ON H1A, OR LOADS FOR LIGHTING ETC?
 PLEASE SEE PANEL SCHEDULE K-1 WHICH IS STILL NOT
 COMPLETE WITH THE LOAD CALCULATIONS AND SECTIONS ARE
 BLANK. PLEASE SEE OTHER LOADS THAT ARE SHOWN ON THE
 BOTTOM OF THE SCHEDULE FOR MANY ITEMS WHICHDO NOT
 CORRELATE WITH THE LOADS SHOWN AT THE RIGHT HAND SIDE
 OF THE SHEET WHICH STATE THEY ARE FOR K-1. ??
 SOME OF THIS VERBIAGE IS TAKEN FROM THE PREVIOUS REVIEW
 AS THE SAME COMMENT EXISTS.
 PLEASE UPDATE AS REQUESTED ON PREVIOUS REVIEW. WHEN
 ADDING OR INCREASING LOAD TO SERVICE, THIS WOULD AFFECT
 THE LOAD OF THE ENTIRE SERVICE WHICH IS EXISTING. 220,
 220.3, 220.10, 220.11, 220.13, CONTINUOUS LOADS PER
 215.3, 230.42
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH, SECTIONS, 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SEE NOW WITH THE NEW RISER BEING SHOWN;
 PLEASE CONFIRM THE 112.5 KVA TRANSFORMER BEING FED WITH
 A 200AMP BREAKER. PLEASE SEE 450.3 AS THE MAXIMUM OVER
 CURRENT PROTECTION SHALL BE SIZED AT 125%. PLEASE KNOW
 THAT ONLY IF MEETING THE EXCEPTION #3 WOULD A HIGHER
 OVER CURRENT PROTECTION BE PERMITTED. PLEASE SEE THAT
 THE MAXIMUM OCP SHOULD BE 175AMPS.IF MEETING THE
 EXCEPTION, PLEASE IDENTIFY THE TRANSFORMER WITH THE
 REQUIRED DETAILS FOR MEETING THIS.
  
 3) NOTE: PLEASE KNOW THAT DUE TO THE NUMBER OF CHANGES
 WHICH HAVE BEEN MADE TO THIS SERVICE AND INFORMATION
 SHOWN AND NOT SHOWN, PLEASE SUBMIT ALL FEEDERS ON
 RISER. PLEASE SHOW THE CONDUCTORS FROM THE PANEL H1A TO
 THE TRANSFORMER AND THE CONDUCTORS FROM THE TRANSFORMER
 TO THE PANEL K-1. PLEASE INCLUDE ALL CONDUCTOR SIZES
 FOR ALL NEW BRANCH CIRCUITS.
 240.4, 310.16, 240.21, 215.5, 215.3 ETC
 FBC 106.3.5.1.2, 106.1.2 ETC
  
 4) NOTE: PLEASE SEE NO DETAIL IS YET SHOWN FOR THE OC
 SENSOR DEVICE WHICH IS BEING SHOWN ON PLANS. THE ONLY
 MENTIONS IS THAT IS SHALL TURN OFF WITHIN 30MINS AFTER
 THE LAST SENSING OF THE OCCUPANT.
 PLEASE SEE THAT DUE TO THE CIRCUITS ON PLANS BEING
 SHOWN AND THE LOADS AS SHOWN, THE AMOUNT OF DEVICES AS
 SHOWN DO NOT APPEAR TO BE ABLE TO DO AS STATED. PLEASE
 SEE NO SPECIFIC ELECTRICAL DETAIL HAS BEEN SUBMITTED
 SHOWING IF NEW POWER PACKS ARE BEING INSTALLED? ARE
 THESE ARE 120V UNITS? MOTION, HEAT, ULTRASONIC? PLEASE
 KNOW ADDING NOTES ON PLANS IN LIEU OF SPECIFIC DETAIL
 AS REQUIRED FOR CODE COMPLIANCE IS NOT PERMITTED.
 PLEASE PROVIDE A DETAIL FOR THE "SYSTEM" WHICH IS BEING
 PROPOSED. PLEASE INDICATE THE TIMES, AND MAXIMUM
 OVER-RIDES TIME
 IF THE INTENT IS MEETING FBC CHAPTER 13, PLEASE SEE
 13-415.1.ABC.1.1, .1.2, .1.3
  
 5) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO THE DESIGN PROFESSIONAL(S) AND REPEAT
 COMMENTS FOR CODE COMPLIANCE. PLEASE SEE THAT A 4X FEE
 FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT FEE HAS
 NOW BEEN ASSESSED DUE TO REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS FEE OF $2,388 WILL BE DUE BEFORE PLANS
 ARE RESUBMITTED FOR REVIEW. PLEASE SEE THE ATTACHED
 SECTION WHICH IS TAKEN DIRECTLY FROM THE FLORIDA
 STATUTES.
  
 "(B)WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS' DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW".
  
 PLEASE KNOW THAT AT THIS TIME ONE COPY OF ALL THREE
 SETS OF ELECTRICAL PLANS ARE NOW BEING RETAINED BY THIS
 OFFICE FOR POSSIBLE PIER REVIEW FROM THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS.
 ** IF ANY PORTION OF THESE COMMENTS IS NOT UNDERSTOOD
 OR THERE ARE COMMENTS ON THIS REVIEW, IT IS IMPERATIVE
 TO CONTACT THIS OFFICE TO GO OVER COMMENTS. THISMAY
 HELP TO ALLEVIATE SUCH ACTIONS.
  
  
 ** PLEASE KNOW AT THIS TIME A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE DUE TO INFORMATION MISSING
 AND/OR INFORMATION WHICH HAS REPEATEDLY CHANGED FROM
 EACH REVISED SET OF PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]