| 2007-01-13 20:08:12 | *** UNSAT 3RD REVIEW *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW(S) WHICH |
| | STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE THE RESPONSE LETTER MENTIONS: "WILL COMPLY |
| | AND SEE REVISED SHEETS", HOWEVER COMPLIANCE HAS NOT |
| | BEEN DONE AND ELECTRICAL PLANS AND RISER FOR SERVICE |
| | HAVE NOW BEEN COMPLETELY CHANGED FROM THE PREVIOUS |
| | SUBMITTED PLANS. |
| | PLEASE SEE THERE ARE ALSO SOME NEW COMMENTS BASED ON |
| | THE REVISED RISER DIAGRAM AND PANEL SCHEDULES |
| | SUBMITTED. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SERVICE HAS NOW BEEN COMPLETELY |
| | BEEN REVISED. PLEASE SEE RISER NO SHOWS H1A AS A 400AMP |
| | PANEL. PLEASE KNOW THAT THE LOAD CALCULATIONS FOR |
| | SERVICE HAVE NOT YET BEEN UPDATED THROUGH-OUT THE |
| | SERVICE PROVIDED TO THE SPACE. PLEASE SEE "H1A" WHICH |
| | FEEDS ALL OTHER PANELS. PLEASE SEE THAT THERE ARE LOADS |
| | ON THIS PANEL WHICH ARE BLANK WITH ZERO LOADS SHOWN?? |
| | HOW IS IT POSSIBLE THAT NO RECEPTACLE LOADS ARE PRESENT |
| | ON H1A, OR LOADS FOR LIGHTING ETC? |
| | PLEASE SEE PANEL SCHEDULE K-1 WHICH IS STILL NOT |
| | COMPLETE WITH THE LOAD CALCULATIONS AND SECTIONS ARE |
| | BLANK. PLEASE SEE OTHER LOADS THAT ARE SHOWN ON THE |
| | BOTTOM OF THE SCHEDULE FOR MANY ITEMS WHICHDO NOT |
| | CORRELATE WITH THE LOADS SHOWN AT THE RIGHT HAND SIDE |
| | OF THE SHEET WHICH STATE THEY ARE FOR K-1. ?? |
| | SOME OF THIS VERBIAGE IS TAKEN FROM THE PREVIOUS REVIEW |
| | AS THE SAME COMMENT EXISTS. |
| | PLEASE UPDATE AS REQUESTED ON PREVIOUS REVIEW. WHEN |
| | ADDING OR INCREASING LOAD TO SERVICE, THIS WOULD AFFECT |
| | THE LOAD OF THE ENTIRE SERVICE WHICH IS EXISTING. 220, |
| | 220.3, 220.10, 220.11, 220.13, CONTINUOUS LOADS PER |
| | 215.3, 230.42 |
| | FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF |
| | WEST PALM BEACH, SECTIONS, 106.1.2, 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE SEE NOW WITH THE NEW RISER BEING SHOWN; |
| | PLEASE CONFIRM THE 112.5 KVA TRANSFORMER BEING FED WITH |
| | A 200AMP BREAKER. PLEASE SEE 450.3 AS THE MAXIMUM OVER |
| | CURRENT PROTECTION SHALL BE SIZED AT 125%. PLEASE KNOW |
| | THAT ONLY IF MEETING THE EXCEPTION #3 WOULD A HIGHER |
| | OVER CURRENT PROTECTION BE PERMITTED. PLEASE SEE THAT |
| | THE MAXIMUM OCP SHOULD BE 175AMPS.IF MEETING THE |
| | EXCEPTION, PLEASE IDENTIFY THE TRANSFORMER WITH THE |
| | REQUIRED DETAILS FOR MEETING THIS. |
| | |
| | 3) NOTE: PLEASE KNOW THAT DUE TO THE NUMBER OF CHANGES |
| | WHICH HAVE BEEN MADE TO THIS SERVICE AND INFORMATION |
| | SHOWN AND NOT SHOWN, PLEASE SUBMIT ALL FEEDERS ON |
| | RISER. PLEASE SHOW THE CONDUCTORS FROM THE PANEL H1A TO |
| | THE TRANSFORMER AND THE CONDUCTORS FROM THE TRANSFORMER |
| | TO THE PANEL K-1. PLEASE INCLUDE ALL CONDUCTOR SIZES |
| | FOR ALL NEW BRANCH CIRCUITS. |
| | 240.4, 310.16, 240.21, 215.5, 215.3 ETC |
| | FBC 106.3.5.1.2, 106.1.2 ETC |
| | |
| | 4) NOTE: PLEASE SEE NO DETAIL IS YET SHOWN FOR THE OC |
| | SENSOR DEVICE WHICH IS BEING SHOWN ON PLANS. THE ONLY |
| | MENTIONS IS THAT IS SHALL TURN OFF WITHIN 30MINS AFTER |
| | THE LAST SENSING OF THE OCCUPANT. |
| | PLEASE SEE THAT DUE TO THE CIRCUITS ON PLANS BEING |
| | SHOWN AND THE LOADS AS SHOWN, THE AMOUNT OF DEVICES AS |
| | SHOWN DO NOT APPEAR TO BE ABLE TO DO AS STATED. PLEASE |
| | SEE NO SPECIFIC ELECTRICAL DETAIL HAS BEEN SUBMITTED |
| | SHOWING IF NEW POWER PACKS ARE BEING INSTALLED? ARE |
| | THESE ARE 120V UNITS? MOTION, HEAT, ULTRASONIC? PLEASE |
| | KNOW ADDING NOTES ON PLANS IN LIEU OF SPECIFIC DETAIL |
| | AS REQUIRED FOR CODE COMPLIANCE IS NOT PERMITTED. |
| | PLEASE PROVIDE A DETAIL FOR THE "SYSTEM" WHICH IS BEING |
| | PROPOSED. PLEASE INDICATE THE TIMES, AND MAXIMUM |
| | OVER-RIDES TIME |
| | IF THE INTENT IS MEETING FBC CHAPTER 13, PLEASE SEE |
| | 13-415.1.ABC.1.1, .1.2, .1.3 |
| | |
| | 5) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO THE DESIGN PROFESSIONAL(S) AND REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. PLEASE SEE THAT A 4X FEE |
| | FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT FEE HAS |
| | NOW BEEN ASSESSED DUE TO REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. THIS FEE OF $2,388 WILL BE DUE BEFORE PLANS |
| | ARE RESUBMITTED FOR REVIEW. PLEASE SEE THE ATTACHED |
| | SECTION WHICH IS TAKEN DIRECTLY FROM THE FLORIDA |
| | STATUTES. |
| | |
| | "(B)WITH RESPECT TO EVALUATION OF DESIGN |
| | PROFESSIONALS' DOCUMENTS, IF A LOCAL GOVERNMENT FINDS |
| | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE |
| | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| | REVIEW". |
| | |
| | PLEASE KNOW THAT AT THIS TIME ONE COPY OF ALL THREE |
| | SETS OF ELECTRICAL PLANS ARE NOW BEING RETAINED BY THIS |
| | OFFICE FOR POSSIBLE PIER REVIEW FROM THE FLORIDA BOARD |
| | OF PROFESSIONAL ENGINEERS. |
| | ** IF ANY PORTION OF THESE COMMENTS IS NOT UNDERSTOOD |
| | OR THERE ARE COMMENTS ON THIS REVIEW, IT IS IMPERATIVE |
| | TO CONTACT THIS OFFICE TO GO OVER COMMENTS. THISMAY |
| | HELP TO ALLEVIATE SUCH ACTIONS. |
| | |
| | |
| | ** PLEASE KNOW AT THIS TIME A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE CAN NOT BE DONE DUE TO INFORMATION MISSING |
| | AND/OR INFORMATION WHICH HAS REPEATEDLY CHANGED FROM |
| | EACH REVISED SET OF PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |