2006-12-14 10:31:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 *****FROM PREVIOUS REVIEW*****
  
 1. OK - EXISTING TOILET ROOMS
 2. OK SHEET NOT RESUBMITTED (N0 FP SHEETS)
 3. OK
  
 4. PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 MINIMUM TWO SETS OF STAMPED PLANS WITH
 TWO PAGE "WORK SHEETS" ATTACHED SHALL BE RESUBMITTED
 FOR REVIEW. SECTION 102.2.1.
 ****RESPONSE FROM ENGINEER NOTED, BUT ARCHITECT DID NOT
 RESPOND AND COMMENT NOT ADDRESSED.
  
 5. SUBMIT AN EXISTING FLOOR PLAN FOR THE
 KITCHEN AREA TO DETERMINE ACTUAL CHANGES
 TO THE KITCHEN AND EQUIPMINT. SECTION
 106.1.1.
 ****RESPONSE FROM ENGINEER NOTED, BUT COMMENT NOT
 ADDRESSED BY KITCHEN EQUIPMENT CONTRACTOR.
  
 6. SHT FP1.1 KITCHEN EQUIPMENT
 CONNECTION SCHEDULE. THE FOLLOWING ITEMS
 WERE NOT FOUND OR INDICATED ON THE FLOOR
 PLAN. NUMBERS 8, 12, 31, 32, 75, B02,
 B10 AND B11. PLEASE INDICATE LOCATION ON
 THE FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NOW FLOOR PLAN DOES NOT SHOW
 ITEMS #4, & #8. EXISTING ITEM #87 NOT SHOWN ON THE
 SCHEDULE.PLEASE CLARIFY.- SHEET NUMBER CHANGED
 WITHOUT NOTICE.
  
 7. OK - SHEET NUMBER CHANGED WITHOUT NOTICE.
 8. OK - SHEET NUMBER CHANGED WITHOUT NOTICE.
  
 9. SHT FP1.2 WATER RISER IN THE NEW COOK
 AREA DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE RISER W4 DOES NOT REFLECT
 THE FLOOR PLAN FOR ITEMS 92 & 73. - SHEET CHANGED
 NUMBER WITHOUT NOTICE.
  
 10. SHT FP1.2 THE FOLLOWING INFORMATION
 IS REQUIRED FOR GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM ENGINEER NOTED, BUT NO MANUF.
 SPECIFICATION SHEETS SHOWING THE LISTING, THE MODEL
 NUMBER, OR THE BTU LOAD INDICATED HAS BEEN SUBMITTED.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT ONLY ONE VALVE IS SHOWN ON THE
 RISER DIAGRAM. IT IS NOT INDICATED IF IT IS THE MANUAL
 SHUT OFF VALVE OR THE EMERGENCY SHUT OFF VALVE. BOTH
 VALVES ARE REQUIRED. ALSO NO UNION IS INDICATED
 DOWNSTREAM OF THE MANUAL AS REQUIRED.
  
 G. OK - USING 402.4(6) BECAUSE 402.4(2) ONLY GOES UP TO
 200 FT, AND THE DEVELOPED LENGTH IS 238.5 FT. MINIMUM
 2-1/2" IS REQUIRED UP TO THE FIRST ITEM #29 PER THE
 TABLE. 2" IS INDICATED. PLEASE CHANGE PIPE SIZE.
  
 **************NEW COMMENTS*************
  
 1B. SHT P1.1 KEY NOTES #11 INDICATES "NOT USED", BUT
 THERE ARE TWO NUMBER 11'S IN THE BAR AREA. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 2B. SHT P1.1 KEY NOTES #10 INDICATES "EXISTING URINAL",
 BUT IT SHOWS #10 TWICE AND BOTH ARE NOT URINALS. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 3B. SHT P1.1 W1/FP1.2 THRU W5/FP1.2 REFERENCES FOR THE
 WATER RISER DIAGRAMS REFER TO A SHEET THAT HAS NOT BEEN
 SUBMITTED. PLEASE CORRELATE THE REFERENCE TO THE
 CORRECT SHEET WITH THE WATER RISERS ON THEM. SECTION
 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RESUBMIT ONE COPY OF THE PLANS SUBMITTED FOR
 THIS REVIEW FOR REFERENCE AND COMPARISON.
  