| 2006-12-14 10:31:37 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | *****FROM PREVIOUS REVIEW***** |
| | |
| | 1. OK - EXISTING TOILET ROOMS |
| | 2. OK SHEET NOT RESUBMITTED (N0 FP SHEETS) |
| | 3. OK |
| | |
| | 4. PLANS SHALL BE ROUTED TO DBPR HOTEL |
| | AND RESTURANT DIVISION FOR REVIEW. |
| | MINIMUM TWO SETS OF STAMPED PLANS WITH |
| | TWO PAGE "WORK SHEETS" ATTACHED SHALL BE RESUBMITTED |
| | FOR REVIEW. SECTION 102.2.1. |
| | ****RESPONSE FROM ENGINEER NOTED, BUT ARCHITECT DID NOT |
| | RESPOND AND COMMENT NOT ADDRESSED. |
| | |
| | 5. SUBMIT AN EXISTING FLOOR PLAN FOR THE |
| | KITCHEN AREA TO DETERMINE ACTUAL CHANGES |
| | TO THE KITCHEN AND EQUIPMINT. SECTION |
| | 106.1.1. |
| | ****RESPONSE FROM ENGINEER NOTED, BUT COMMENT NOT |
| | ADDRESSED BY KITCHEN EQUIPMENT CONTRACTOR. |
| | |
| | 6. SHT FP1.1 KITCHEN EQUIPMENT |
| | CONNECTION SCHEDULE. THE FOLLOWING ITEMS |
| | WERE NOT FOUND OR INDICATED ON THE FLOOR |
| | PLAN. NUMBERS 8, 12, 31, 32, 75, B02, |
| | B10 AND B11. PLEASE INDICATE LOCATION ON |
| | THE FLOOR PLAN. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT NOW FLOOR PLAN DOES NOT SHOW |
| | ITEMS #4, & #8. EXISTING ITEM #87 NOT SHOWN ON THE |
| | SCHEDULE.PLEASE CLARIFY.- SHEET NUMBER CHANGED |
| | WITHOUT NOTICE. |
| | |
| | 7. OK - SHEET NUMBER CHANGED WITHOUT NOTICE. |
| | 8. OK - SHEET NUMBER CHANGED WITHOUT NOTICE. |
| | |
| | 9. SHT FP1.2 WATER RISER IN THE NEW COOK |
| | AREA DOES NOT REFLECT THE FLOOR PLAN. |
| | PLEASE CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE RISER W4 DOES NOT REFLECT |
| | THE FLOOR PLAN FOR ITEMS 92 & 73. - SHEET CHANGED |
| | NUMBER WITHOUT NOTICE. |
| | |
| | 10. SHT FP1.2 THE FOLLOWING INFORMATION |
| | IS REQUIRED FOR GAS PERMIT: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE FROM ENGINEER NOTED, BUT NO MANUF. |
| | SPECIFICATION SHEETS SHOWING THE LISTING, THE MODEL |
| | NUMBER, OR THE BTU LOAD INDICATED HAS BEEN SUBMITTED. |
| | |
| | F. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****RESPONSE NOTED, BUT ONLY ONE VALVE IS SHOWN ON THE |
| | RISER DIAGRAM. IT IS NOT INDICATED IF IT IS THE MANUAL |
| | SHUT OFF VALVE OR THE EMERGENCY SHUT OFF VALVE. BOTH |
| | VALVES ARE REQUIRED. ALSO NO UNION IS INDICATED |
| | DOWNSTREAM OF THE MANUAL AS REQUIRED. |
| | |
| | G. OK - USING 402.4(6) BECAUSE 402.4(2) ONLY GOES UP TO |
| | 200 FT, AND THE DEVELOPED LENGTH IS 238.5 FT. MINIMUM |
| | 2-1/2" IS REQUIRED UP TO THE FIRST ITEM #29 PER THE |
| | TABLE. 2" IS INDICATED. PLEASE CHANGE PIPE SIZE. |
| | |
| | **************NEW COMMENTS************* |
| | |
| | 1B. SHT P1.1 KEY NOTES #11 INDICATES "NOT USED", BUT |
| | THERE ARE TWO NUMBER 11'S IN THE BAR AREA. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 2B. SHT P1.1 KEY NOTES #10 INDICATES "EXISTING URINAL", |
| | BUT IT SHOWS #10 TWICE AND BOTH ARE NOT URINALS. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 3B. SHT P1.1 W1/FP1.2 THRU W5/FP1.2 REFERENCES FOR THE |
| | WATER RISER DIAGRAMS REFER TO A SHEET THAT HAS NOT BEEN |
| | SUBMITTED. PLEASE CORRELATE THE REFERENCE TO THE |
| | CORRECT SHEET WITH THE WATER RISERS ON THEM. SECTION |
| | 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |