Plan Review Notes
Plan Review Notes For Permit 06082089
Permit Number 06082089
Review Stop G
Sequence Number 2
Notes
Date Text
2006-12-14 10:41:06DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT FP1.2 THE FOLLOWING INFORMATION
 IS REQUIRED FOR GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM ENGINEER NOTED, BUT NO MANUF.
 SPECIFICATION SHEETS SHOWING THE LISTING, THE MODEL
 NUMBER, OR THE BTU LOAD INDICATED HAS BEEN SUBMITTED.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT ONLY ONE VALVE IS SHOWN ON THE
 RISER DIAGRAM. IT IS NOT INDICATED IF IT IS THE MANUAL
 SHUT OFF VALVE OR THE EMERGENCY SHUT OFF VALVE. BOTH
 VALVES ARE REQUIRED. ALSO NO UNION IS INDICATED
 DOWNSTREAM OF THE MANUAL AS REQUIRED.
  
 G. OK - USING 402.4(6) BECAUSE 402.4(2) ONLY GOES UP TO
 200 FT, AND THE DEVELOPED LENGTH IS 238.5 FT. MINIMUM
 2-1/2" IS REQUIRED UP TO THE FIRST ITEM #29 PER THE
 TABLE. 2" IS INDICATED. PLEASE CHANGE PIPE SIZE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]