| Plan Review Notes For Permit 06082089 |
| Permit Number |
06082089 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-14 10:41:06 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHT FP1.2 THE FOLLOWING INFORMATION | | | IS REQUIRED FOR GAS PERMIT: | | | | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE FROM ENGINEER NOTED, BUT NO MANUF. | | | SPECIFICATION SHEETS SHOWING THE LISTING, THE MODEL | | | NUMBER, OR THE BTU LOAD INDICATED HAS BEEN SUBMITTED. | | | | | | F. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, BUT ONLY ONE VALVE IS SHOWN ON THE | | | RISER DIAGRAM. IT IS NOT INDICATED IF IT IS THE MANUAL | | | SHUT OFF VALVE OR THE EMERGENCY SHUT OFF VALVE. BOTH | | | VALVES ARE REQUIRED. ALSO NO UNION IS INDICATED | | | DOWNSTREAM OF THE MANUAL AS REQUIRED. | | | | | | G. OK - USING 402.4(6) BECAUSE 402.4(2) ONLY GOES UP TO | | | 200 FT, AND THE DEVELOPED LENGTH IS 238.5 FT. MINIMUM | | | 2-1/2" IS REQUIRED UP TO THE FIRST ITEM #29 PER THE | | | TABLE. 2" IS INDICATED. PLEASE CHANGE PIPE SIZE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|