Plan Review Notes
Plan Review Notes For Permit 06082089
Permit Number 06082089
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-12-01 11:31:31*****UNSAT******
  
 RESPONSES TO THE PREVIOUS FIRE PLAN REVIEW OF 10/05/06
 RECEIVED AS FOLLOWS:
  
 1.) NFPA 101 - 2003 EDITION, AND FLORIDA
 FIRE PREVENTION CODE - 2004 EDITION
 SHALL BE REFERENCED. NFPA 101 IS A LIFE SAFETY CODE,
 NOT AN ELECTRICAL CODE.ALSO MAKE REFERENCE TO FL.
 FIRE PREVENTION CODE UNDER APPLICABLE CODES, SHEET
 G1.1
  
 2.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.SHOULD BE ADDED TO THE
 SHEET G1.1 UNDER APPLICABLE CODES
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIALS, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS. SHOULD BE ADDED IN THE PLANS
  
 4.)OK
  
 5.)OK
  
 6.) PANIC HARDWARE IS REQUIRED ON EXIT
 DOORS SERVING AN OCCUPANT LOAD GREATER
 THAN ONE HUNDRED.SHOULD BE ADDED IN THE PLANS
  
 7.)OK
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCL;UDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722