| Plan Review Notes For Permit 06082089 |
| Permit Number |
06082089 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-01 11:31:31 | *****UNSAT****** | | | | | | RESPONSES TO THE PREVIOUS FIRE PLAN REVIEW OF 10/05/06 | | | RECEIVED AS FOLLOWS: | | | | | | 1.) NFPA 101 - 2003 EDITION, AND FLORIDA | | | FIRE PREVENTION CODE - 2004 EDITION | | | SHALL BE REFERENCED. NFPA 101 IS A LIFE SAFETY CODE, | | | NOT AN ELECTRICAL CODE.ALSO MAKE REFERENCE TO FL. | | | FIRE PREVENTION CODE UNDER APPLICABLE CODES, SHEET | | | G1.1 | | | | | | 2.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241.SHOULD BE ADDED TO THE | | | SHEET G1.1 UNDER APPLICABLE CODES | | | | | | 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE | | | MATERIALS, DUST, AND DEBRIS SHALL BE | | | REMOVED FROM THE STRUCTURE AND ITS | | | IMMEDIATE VICINITY AT THE END OF EACH | | | SHIFT OR MORE FREQUENTLY AS NECESSARY | | | FOR SAFE OPERATIONS. SHOULD BE ADDED IN THE PLANS | | | | | | 4.)OK | | | | | | 5.)OK | | | | | | 6.) PANIC HARDWARE IS REQUIRED ON EXIT | | | DOORS SERVING AN OCCUPANT LOAD GREATER | | | THAN ONE HUNDRED.SHOULD BE ADDED IN THE PLANS | | | | | | 7.)OK | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCL;UDE A | | | RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|