| 2006-11-16 10:43:33 | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH |
| | STILL NEEDS TO BE ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SEE LOAD CALCULATIONS FOR SERVICE HAS |
| | NOT YET BEEN UPDATED THROUGH-OUT THE SERVICE PROVIDED |
| | TO THE SPACE. PLEASE SEE "H1A" WHICH FEEDS ALL OTHER |
| | PANELS. PLEASE SEE THE LOADS ON THIS PANEL ARE BLANK |
| | WITH ZERO LOADS SHOWN?? |
| | PLEASE UPDATE AS REQUESTED ON PREVIOUS REVIEW. WHEN |
| | ADDING OR INCREASING LOAD TO SERVICE, THIS WOULD AFFECT |
| | THE LOAD OF THE ENTIRE SERVICE WHICH IS EXISTING. |
| | 220.3, 220.10, 220.11, 220.13, CONTINUOUS LOADS PER |
| | 215.3, 230.42 |
| | FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF |
| | WEST PALM BEACH, SECTIONS, 106.1.2, 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE SEE THE RESPONSE ON LIGHTING CONTROLS |
| | FOR DINING AREA WAS DONE BY ADDING A NOTE ON PLANS FOR |
| | A TIMER AND AUTO-SHUT REQUIRED. |
| | PLEASE KNOW ADDING NOTES ON PLANS IN LIEU OF SPECIFIC |
| | DETAIL AS REQUIRED FOR CODE COMPLIANCE IS NOT |
| | PERMITTED. |
| | PLEASE PROVIDE A DETAIL FOR THE "SYSTEM" WHICH IS BEING |
| | PROPOSED. PLEASE INDICATE THE TIMES,AND MAXIMUM |
| | OVER-RIDES TIME |
| | IF THE INTENT IS MEETING FBC CHAPTER 13, PLEASE SEE |
| | 13-415.1.ABC.1.1, .1.2, .1.3 |
| | |
| | 3) NOTE: PLEASE SEE POSSIBLE MISPRINT WHEN ADDING THE |
| | RELEVANT CODE ON SHEET G1.1. |
| | PLEASE SEE NFPA-72 IS BEING REFERENCED AS THE NATIONAL |
| | ELECTRICAL CODE, WHEN 72 IS ACTUALLY THE NATION FIRE |
| | ALARM CODE.(.2002) |
| | THIS COULD HAVE BEEN RED-LINED; HOWEVER PLANS ARE |
| | COMING BACK FOR CORRECTIONS. |
| | |
| | 4) NOTE: PLEASE SEE RESPONSE LETTER FROM DESIGN TEAM |
| | FOR MEP'S REFLECT OCI AND ASSOCIATES, YET PLANS DO NOT |
| | CONTAIN ANY TITLE BLOCKS FOR OCI?? |
| | THIS ONLY IN QUESTION AT THIS TIME AND PLANS MAY BE |
| | DIRECTLY DONE AS LISTED BY THE SOLE ENGINEER OF |
| | RECORD. |
| | |
| | FAC 61G15-23.002/ FS 471.023 |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF |
| | THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE |
| | NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO |
| | NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |