| Date |
Text |
| 2006-09-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT G1.1 PER TABLE 403.1 & SECTION |
| | 403.1.1 ASSEMBLY OCCUPANCIESD REQUIRE A |
| | 3:2 RATIO OF W/C'S PROVIDED FOR WOMEN AS |
| | COMBINED W/C'S AND URINALS PROVIDED FOR |
| | MEN. SINCE 2 W/C'S & 1 URINAL, (3), ARE |
| | PROVIDED FOR MEN, 3X1.66 (3:2 RATIO), 5 |
| | W/C'S ARE REQUIRED FOR WOMEN. |
| | |
| | 2. SHT FP1.0 DEMO NOTES 7 AND 11 WERE |
| | NOT FOUND ON THE FLOOR PLAN. PLESASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 3. ALL SHEETS KEY PLAN INDICATES SCOPE |
| | OF WORK TO BE OUTSIDE THE KITCHEN AREA. |
| | WORK IS INDICATED IN THE KITCHEN AREA. |
| | CHANGE KEY PLAN TO REFLECT SCOPE OF WORK |
| | TO ALL AREAS WHERE WORK IS BEING DONE. |
| | SECTION 106.1.1. |
| | |
| | 4. PLANS SHALL BE ROUTED TO DBPR HOTEL |
| | AND RESTURANT DIVISION FOR REVIEW. |
| | MINIMUM TWO SETS OF STAMPED PLANS WITH |
| | TWO PAGE "WORK SHEETS" ATTACHED SHALL BE RESUBMITTED |
| | FOR REVIEW. SECTION 102.2.1. |
| | |
| | 5. SUBMIT AN EXISTING FLOOR PLAN FOR THE |
| | KITCHEN AREA TO DETERMINE ACTUAL CHANGES |
| | TO THE KITCHEN AND EQUIPMINT. SECTION |
| | 106.1.1. |
| | |
| | 6. SHT FP1.1 KITCHEN EQUIPMENT |
| | CONNECTION SCHEDUL. THE FOLLOWING ITEMS |
| | WERE NOT FOUND OR INDICATED ON THE FLOOR |
| | PLAN. NUMBERS 8, 12, 31, 32, 75, B02, |
| | B10 AND B11. PLEASE INDICATE LOCATION ON |
| | THE FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 7. SHT FP1.1 NOTE 12 NOT FOUND. NUMBERED |
| | WRONG AS NUMBER 2? PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 8. SHT FP1.1 FLOOR PLAN SHOW A FLOOR |
| | SINK TO REMAIN THAT IS NOT LOCATED UNDER |
| | A PLUMBING FIXTURE. FLOOR SINKS ARE |
| | NORMALLY INSTALLED 1" ABOVE FINISHED |
| | FLOOR. WILL THE FLOOR BE BUILD UP FOR |
| | THIS TO BE USED AS A FLOOR DRAIN? |
| | SECTION 106.1.1. |
| | |
| | 9. SHT FP1.2 WATER RISER IN THE NEW COOK |
| | AREA DOES NOT REFLECT THE FLOOR PLAN. |
| | PLEASE CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 106.1.1. |
| | |
| | 10. SHT FP1.2 THE FOLLOWING INFORMATION |
| | IS REQUIRED FOR GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. SHOW ALL CUT SECTION |
| | LENGHTS. INDICATE VALVE SIZE. (TO BE |
| | FULL SIZE AS REQUIRED PIPE SIZE TO |
| | APPLIANCE). |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. SHT |
| | FP1.1 INDICATES 1PSI OR LESS. IF NATURAL |
| | GAS, PROVIDER PROVIDES 1/2PSI, 2PSI OR |
| | 5PSI ONLY. PLEASE CONFIRM INLET PRESSURE |
| | PRIOR TO RESUBMITTING. IF 2PSI, INDICATE |
| | THE LOCATION OF THE 2PI TO 1/2PSI |
| | REGULATORS, AND SUBMIT THE MANUF. |
| | SPECIFICATION SHEETS FOR THE REGULATORS |
| | AND INDICATE THE MODEL NUMBER. |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | F. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | G. SUBMIT GAS TABLE USED FOR SIZING GAS |
| | PIPE PER FBC-2004 FUEL GAS, OR INDICATE |
| | THE SOURCE OF THE GAS TABLE USED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |