Plan Review Notes
Plan Review Notes For Permit 06082089
Permit Number 06082089
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-09 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT G1.1 PER TABLE 403.1 & SECTION
 403.1.1 ASSEMBLY OCCUPANCIESD REQUIRE A
 3:2 RATIO OF W/C'S PROVIDED FOR WOMEN AS
 COMBINED W/C'S AND URINALS PROVIDED FOR
 MEN. SINCE 2 W/C'S & 1 URINAL, (3), ARE
 PROVIDED FOR MEN, 3X1.66 (3:2 RATIO), 5
 W/C'S ARE REQUIRED FOR WOMEN.
  
 2. SHT FP1.0 DEMO NOTES 7 AND 11 WERE
 NOT FOUND ON THE FLOOR PLAN. PLESASE
 CLARIFY. SECTION 106.1.1.
  
 3. ALL SHEETS KEY PLAN INDICATES SCOPE
 OF WORK TO BE OUTSIDE THE KITCHEN AREA.
 WORK IS INDICATED IN THE KITCHEN AREA.
 CHANGE KEY PLAN TO REFLECT SCOPE OF WORK
 TO ALL AREAS WHERE WORK IS BEING DONE.
 SECTION 106.1.1.
  
 4. PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 MINIMUM TWO SETS OF STAMPED PLANS WITH
 TWO PAGE "WORK SHEETS" ATTACHED SHALL BE RESUBMITTED
 FOR REVIEW. SECTION 102.2.1.
  
 5. SUBMIT AN EXISTING FLOOR PLAN FOR THE
 KITCHEN AREA TO DETERMINE ACTUAL CHANGES
 TO THE KITCHEN AND EQUIPMINT. SECTION
 106.1.1.
  
 6. SHT FP1.1 KITCHEN EQUIPMENT
 CONNECTION SCHEDUL. THE FOLLOWING ITEMS
 WERE NOT FOUND OR INDICATED ON THE FLOOR
 PLAN. NUMBERS 8, 12, 31, 32, 75, B02,
 B10 AND B11. PLEASE INDICATE LOCATION ON
 THE FLOOR PLAN. SECTION 106.1.1.
  
 7. SHT FP1.1 NOTE 12 NOT FOUND. NUMBERED
 WRONG AS NUMBER 2? PLEASE CLARIFY.
 SECTION 106.1.1.
  
 8. SHT FP1.1 FLOOR PLAN SHOW A FLOOR
 SINK TO REMAIN THAT IS NOT LOCATED UNDER
 A PLUMBING FIXTURE. FLOOR SINKS ARE
 NORMALLY INSTALLED 1" ABOVE FINISHED
 FLOOR. WILL THE FLOOR BE BUILD UP FOR
 THIS TO BE USED AS A FLOOR DRAIN?
 SECTION 106.1.1.
  
 9. SHT FP1.2 WATER RISER IN THE NEW COOK
 AREA DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1.
  
 10. SHT FP1.2 THE FOLLOWING INFORMATION
 IS REQUIRED FOR GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SHOW ALL CUT SECTION
 LENGHTS. INDICATE VALVE SIZE. (TO BE
 FULL SIZE AS REQUIRED PIPE SIZE TO
 APPLIANCE).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. SHT
 FP1.1 INDICATES 1PSI OR LESS. IF NATURAL
 GAS, PROVIDER PROVIDES 1/2PSI, 2PSI OR
 5PSI ONLY. PLEASE CONFIRM INLET PRESSURE
 PRIOR TO RESUBMITTING. IF 2PSI, INDICATE
 THE LOCATION OF THE 2PI TO 1/2PSI
 REGULATORS, AND SUBMIT THE MANUF.
 SPECIFICATION SHEETS FOR THE REGULATORS
 AND INDICATE THE MODEL NUMBER.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 G. SUBMIT GAS TABLE USED FOR SIZING GAS
 PIPE PER FBC-2004 FUEL GAS, OR INDICATE
 THE SOURCE OF THE GAS TABLE USED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved