| Plan Review Notes For Permit 06082089 |
| Permit Number |
06082089 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-30 00:00:00 | ----------------DENIED------------------ | | | | | | 1. PROVIDE DETAILED DRAWINGS SHOWING | | | SIZES/LOCATIONS/SPECS OF EXISTING | | | EQUIPMENT AND DUCTWORK ALONG WITH WORK | | | BEING PERFORMED TO FACILITATE RELOCATION | | | OF DIFFUSERS AS INDICATED ON PAGE M1.1 | | | KEYNOTE #2 - PER FBC 106.1.1 | | | | | | 2. PROVIDE FRESH AIR CALCULATIONS BASED | | | ON OCCUPANCY CLASSIFICATION AND OCCUPANT | | | LOAD PER FBC,M 403.3 | | | | | | 3. IF TOILET ROOMS ARE TO BE MODIFIED | | | PER PLUMBING REVIEW COMMENT #1, VERIFY | | | AND PROVIDE INFORMATION NEEDED TO SHOW | | | EXHAUST OF TOILET ROOMS IN COMPLIANCE | | | WITH FBC,M TABLE 403.3 | | | | | | 4. PAGE M1.1 KEYNOTE #5: ANY MOVEMENT OR | | | ADJUSTMENT OF TYPE I KITCHEN HOODS WILL | | | REQUIRE SEPERATE PERMITS FOR BOTH THE | | | HOODS AND HOOD SUPPRESSION SYSTEMS. | | | | | | 5. DRAWING SC-1 SHEET FS500 SHOWS 6" PVC | | | CHASES FOR SODA FOUNTAINS TO BE | | | INSTALLED ABOVE CEILING. DO THESE CHASES | | | TRAVEL THROUGH ANY RETURN AIR PLENUMS? | | | NO COMBUSTIBLE MATERIALS CAN BE EXPOSED | | | IN RETURN AIR PLENUMS.THIS APPLIES TO | | | ALL COMBUSTIBLES, NOT JUST THE SODA | | | CHASES. FBC,M 602.2.1 | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU | | | HAVE ANY QUESTIONS. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|