| Plan Review Notes For Permit 06082089 |
| Permit Number |
06082089 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-05 00:00:00 | *****DENIED***** | | | | | | | | | | | | | | | 1.) NFPA 101 - 2003 EDITION, AND FLORIDA | | | FIRE PREVENTION CODE - 2004 EDITION | | | SHALL BE REFERENCED. | | | | | | 2.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241. | | | | | | 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE | | | MATERIALS, DUST, AND DEBRIS SHALL BE | | | REMOVED FROM THE STRUCTURE AND ITS | | | IMMEDIATE VICINITY AT THE END OF EACH | | | SHIFT OR MORE FREQUENTLY AS NECESSARY | | | FOR SAFE OPERATIONS. | | | | | | 4.) IF THE SCOPE OF THE INTERIOR | | | BUILDOUT REQUIRES MODIFICATION OF THE | | | FIRE ALARM OR FIRE SPRINKLER SYSTEM, | | | SEPARATE PERMIT AND SHOP DRAWINGS/PLANS | | | ARE REQUIRED. | | | | | | 5.) ON SHEET E1.0 AT BAR AREA #1, PLEASE | | | EXPLAIN HOW THE SUPPORT COLUMN WILL | | | MAINTAIN ITS FIRE PROTECTION RATING IF | | | THE EXISTING BRICK AROUND THE COLUMN IS | | | REMOVED. | | | | | | 6.) PANIC HARDWARE IS REQUIRED ON EXIT | | | DOORS SERVING AN OCCUPANT LOAD GREATER | | | THAN ONE HUNDRED. | | | | | | 7.) ON SHEET LS1.1, THE AISLE CLEARANCE | | | OF 3'-0" (LOCATED AROUND DINING AREA | | | "C") EXITING BETWEEN BAR SEAT #20-21 AND | | | THE SUPPORT COLUMN IS TO NARROW. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|