2006-09-10 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE BE SURE THE PERMIT
 APPLICATION CONTAINS THE APPLIED VALUW
 WHICH IS REQUIRED TO BE FILLED OUT BY
 THE CONTRACTOR. PLEASE SEE THAT THE
 RELEVANT SQ FOOTAGE SHOULD ALSO BE
 STATED ON APPLICATION.
  
 2) NOTE: PLEASE SEE THE FOLLOWING
 RELEVANT CODE BE PLACED ONELECTRICAL
 PLANS.
 2002 NFPA-70(NEC ALREADY ON A-COVER
 SHEET), 2002 NFPA-72 AND 2003 NFPA-101
  
 3) NOTE: PLEASE VERIFY THE LOAD AS SHOWN
 ON PANEL LP, PLEASE SEE LOAD SEEMS TO BE
 RIGHT ON THE BORDER OVER OVER LOADING
 THE PANEL FEEDER AND NO ROOM FOR ANY
 FUTURE EXPANSION IS PRESENT. PLEASE SEE
 90.8, AS THE LOADS HAVE BEEN INCREASED
 AND THE FEEDER NEEDS TO BE INCREASED
 FROM K-2.
 215.5,310.16,240.4
  
 4) NOTE: PLEASE SEE NEW ELECTRICAL ITEMS
 HAVE BEEN INCLUDED ON EXISTING PANELS,
 HOWEVER COMPLETED UPDATED LOAD
 CALCULATIONS NEED TO BE DONE.
 PLEASE SEE KITCHEN PANEL NEEDS TO
 INCLUDE NEW AND EXISTING LOADS ALONG
 WITH K-2.
 220, 215.5
 FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY LIGTING CONTROLS
 PER 13-415.1.ABC.1.1 FORNEW DINING ARE
 LIGHTING.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW