| Plan Review Notes For Permit 06082057 |
| Permit Number |
06082057 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-02 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1 INDICATES FLEX DUCT | | | PENETRATING THROUGH RATED PARTITIONS. | | | PER 2004 FMC 603.5.5, FLEXIBLE AIR DUCTS | | | & CONNECTORS SHALL NOT PASS THROUGH ANY | | | FIRE RESISTANCE RATED ASSEMBLY. | | | | | | 2.PLESE CLARIFY EXUST 10" X 7" EXHAUST | | | DUCT RISER CONNECTING TO NEW EF-1.IS | | | THIS A SHAFT INTO WHICH THE EF-1 | | | TERMIATES, PLEASE INDICATE IF THIS IS A | | | SUB-DUCT METHOD. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected] |
|