2006-10-02 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES FLEX DUCT
 PENETRATING THROUGH RATED PARTITIONS.
 PER 2004 FMC 603.5.5, FLEXIBLE AIR DUCTS
 & CONNECTORS SHALL NOT PASS THROUGH ANY
 FIRE RESISTANCE RATED ASSEMBLY.
  
 2.PLESE CLARIFY EXUST 10" X 7" EXHAUST
 DUCT RISER CONNECTING TO NEW EF-1.IS
 THIS A SHAFT INTO WHICH THE EF-1
 TERMIATES, PLEASE INDICATE IF THIS IS A
 SUB-DUCT METHOD.
  