Plan Review Notes
Plan Review Notes For Permit 06082057
Permit Number 06082057
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-09 00:00:00 
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) 11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED
 SHALL BE AS SHOWN IN FIGURE 11-25 . THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR.
 MINIMUM CLARENCE IS 18". SEE PREP ROOM
 DOOR. SHEET A-2.
  
 2) DOOR ENCROACHMENT
 1005.2 DOOR ENCROACHMENT .
 DOORS OPENING INTO THE PATH OF EGRESS
 TRAVEL SHALL NOT REDUCE THE REQUIRED
 WIDTH TO LESS THAN ONE-HALF DURING THE
 COURSE OF THE SWING. WHEN FULLY OPEN,
 THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES (178 MM) INTO THE REQUIRED WIDTH.
  
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
  
 A) THE DESIGN OCCUPANT LOAD, SEE 1004.
 -------------------------------------
  
 4) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE BUILDING OFFICIAL
 (SEE ALSO SECTION 106.3.5). THE SYMBOL
 IN THE LEGEND FOR THE 1-HR RATED
 PARTITION LOOKS THE SAME FOR THE
 EXISTING AND NEW 1-HR RATED WALL. THE
 NEW RATED WALL NEEDS TO BE DESTINTIVE
 FROM THE EXISTING RATED WALL, SO WE CAN
 IDENTIFY THE NEW 1-HR RATED WALLS.
  
 5) ON PAGES A-5 AND A-6 THE NEW WALLS
 NEED TO BE CLEARLY IDENTIFY FROM THE
 EXISTING WALLS.
  
 6) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SSYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
 EMAIL: [email protected]
  
  
  