2006-09-08 00:00:00***UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS SHALL INDICAT
 ETHE CURRENT CODE IN AFFECT.
 2002 NEC/ NFPA-70
  
 2) NOTE: PLEASE SEE VALUE SHALL BE BASED
 ON LABOUR AND MATERIALS EVEN IF ANY
 MATERIALS ARE OWNER SUPPLIED.
 FBC 108.3.
  
 3) NOTE: PLEASE SEE PLANS ARE REQUIRED
 TO BE SIGNED WIHT SIGNATURE AS
 RECOGNIZED ANDON FILE WITH THIS OFFICE
 FOR THE ENGINEER OF RECORD.
 FS 471.025
  
 4) NOTE: PLEASE PROVIDE THE GROUNDIGN
 ELECTRODE SYSTEM DETAIL, MUST ATTACH TO
 NEW FOOTER STEEL OF BLDG PER 250.50,
 MUST ALSO PROVIDE INFORMATION FOR GROUND
 RODS AS SHOWN.
 PLEASE KNOW, AS ANY COLD WATER FIRE
 SPRINKLER STAND PIPES WILL BE ON SITE,
 THIS SHALL ALSO BE SHOWN BODNED AS
 REQUIRED.
 250.104, 250.50.
  
 5) NOTE: PLEASE PROVIDE A GROUNDING
 ELECTRODE RISER FOR TRANSFORMERS ETC.
 250.30,250.20,250.58.
 SHOW ATTACHEMNTS AND SIZING FOR
 TRANSFORMERS.
 250.66
 GRN RISER SHALL BE COPPER.
  
 6) NOTE: PLEASE INDICATE THAT THE MDP AS
 SHOWN ONLY CONTAIN A MAX OF 6 SPACES AS
 PERMITTED PER 230.71. PLEAS KNOW, IF
 EQUIPMENT DOES CONTAIN MORE THAN 6
 SPACES EVEN FOR SP BRKERS, A MAIN WILL
 BE REQUIRED.
  
 7) NOTE: PLEASE PROVIDE AN OVERVIEW OF
 SITE WHERE EQUIPMENT WILL BE LOCATED ON
 GROUND LEVEL.
  
 8) NOTE: PLEASE PROVIDE INFORMATION FOR
 TRAILER HOOK UP FEEDERS, GROUNDING
 DISCONNECTS ETC AS THESE ARE NOT PART OF
 OTHER PERMITS AND THIS INFORMATION HAS
 NOT BEEN SHOWN HERE.
 FBC106.1.2, 2002 NEC.
  
 9) NOTE: PLEASE SUBMIT ALL INFORMATION
 FOR PROSED FIRE PUMP. IF THIS TEMPORARY?
 PLEASE INDICATE LOCKED ROTOR CURRENT
 ETC.
 PLEASE SUBMIT MANUFACTURE SPECS / CUT
 SHEETS FOR FIRE PUMP CONTROLLER / FIRE
 PUMP.
 PLANS MENTIONS FPC BY OTHERS HOWEVER IF
 HOOK UP IS BEING DONE UNDER THIS PERMIT
 , THIS INFORMATION MUST BE PROVIDED AT
 THIS TIME.
 ** PLEASE ALSO KNOW, THE INSTALLATION OF
 THE FIRE PUMP SHALL BE PERMITTED BY THE
 LICENSED CONTRACTOR QUALIFIED FOR THIS
 TYPE OF INSTALLATION.
  
 10) NOTE: PLEASE SEE PLANS INDICATE ALL
 ELECTRICAL FEEDERS, SEC'S ETC BEING
 INSTALLED IN CONDUIT?? PLEASE VERIFY AND
 CONFIRM ON PLANS TYPE OF CONDUIT. PLEASE
 KNOW AS THIS IS ON AN CONSTRUCTION SITE,
 FOR CONSTRUCTION PURPOSE AND IF USING
 PVC, SCH 80 WILL BE REQUIRED.
 IF USING ANY KIND OF CORDS/CABLES TYPE
 SHALL BE INDICATED FOR EXTRA HARD
 SERVICE.
 527, 352 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  