| Plan Review Notes For Permit 06082035 |
| Permit Number |
06082035 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-13 00:00:00 | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 106.3.5.1.2 FBC | | | | | | 1} PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL NEW AND ALL EXISTING LOADS | | | AND THE EXISTING SERVICE SPECIFICATIONS | | | PER 215.15. | | | | | | 2} INDICATE THE OCP, WIRE AND CONDUIT | | | SIZES FOR THE NEW FREEZER BRANCH | | | CIRCUITS. | | | | | | 3} INDICATE THE BRANCH CIRCUIT NUMBERS | | | FOR THE NEW CIRCUITS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | |
|