| 2006-09-01 00:00:00 | *** DENIED *** |
| | 1) BUILDING 1315 APT.101 & 202 CAN BE ON |
| | THE SAME ENERGY CAL. BUT BUILDING 1309 |
| | MUST HAVE ITS OWN ENERGY CAL; PER 2004 |
| | FBC 13-101.2.5.1 . |
| | |
| | 2) ENERGY CAL'S NEED TO BE SIGNED BY THE |
| | PREPARER NOT STAMPED AND ALSO SIGNED BY |
| | THE OWNER/AGENT, PER 2004 FBC |
| | 13-600.ABC.1.1 . |
| | |
| | 3) ALL INFORMATION, DRAWINGS, (PLANS), |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. PER |
| | FBC 104.2.1 . |
| | |
| | 4) PLEASE SUBMIT MANUAL D CALCULATIONS |
| | FOR RESIDENTIAL DUCT DESIGN, PER 2004 |
| | FBC/R M1601.1 AND FBC 13-610.1.ABC.1 . |
| | |
| | 5) PLANS REFER TO THE SAME APT. AS 201 |
| | AND 202, PLEASE CORRECT. |
| | |
| | 6) WHITE OUT MAY NOT BE USED ON PLANS. |
| | |
| | 7) PLEASE SHOW AIR HANDLER UNIT CFM'S ON |
| | PLANS. |
| | |
| | 8) A/C #3, PLEASE PROVIED RETURN AIR FOR |
| | BEDROOMS, PER 2004 FBC/R M1602.4 . |
| | |
| | 9) A/C #3, IS 16" RETURN AIR DUCT GOING |
| | TO A SIDE WALL GRILL, PLEASE CLARIFY. |
| | |
| | 10) PLEASE SHOW SIZES OF SUPPLY AIR |
| | TRUNK LINES FOR AHU #1 AND #3. |
| | |
| | 11) DO BATHROOMS HAVE WINDOWS OR ARE |
| | EXHAUST FANS BEING INSTALLED, PLEASE |
| | CLARIFY. |
| | |
| | 12) NEED TO FILE A NOTICE OF |
| | COMMENCEMENT FOR WALLEN SERVICE CORP. AS |
| | THE CONTRACTOR AS INSTALLING NEW A/C |
| | SYSTEMS WAS NOT PART OF THE GENERAL |
| | REPAIRS PERMIT, PER F. S. 713.13 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |
| | |