| Plan Review Notes For Permit 06082023 |
| Permit Number |
06082023 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-09 00:00:00 | DENIED; | | | 1. ADD NOTE TO PAGE A0.2; ALL PLUMBING | | | PIPES NOT BEING RE-USED MUST BE REMOVED, | | | AND A DEMO PLUMBING INSPECTION IS | | | REQUIRED.SEE FBC-2004 PLUMBING, SECTION | | | 704.5 NO DEAD ENDS. | | | 2.NO PLUMBING PAGES FOUND WITH THIS SET | | | OF PLANS. PLEASE PROVIDE WATER AND | | | SANITARY RISER DIAGRAMS SIZE ALL PIPE | | | SHOW LOCATION OF SHUTOFF VALVES AND | | | LOCATION OF WATER HAMMER ARRESTORS TO BE | | | INSTALLED. ALSO LOCATION OF WATER HEATER | | | LISTED ON ELECTRICAL DRAWINGS. | | | 3.MENS HANDICAP BATHROOM DOOR TO BE | | | DIAGONAL OF THE TOILET, SEE FBC-2004 | | | BUILDING CHAPTER 11 FIG. 30E NOTES. | | | 4. SHOW A DETAIL OF THE DRINKING | | | FOUNTAIN ON PAGE A3.3 WITH HANDICAP | | | REQUIREMENTS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|