| Date |
Text |
| 2006-09-10 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN |
| | SUBMITED FOR "PLAN REVIEW" AND HAVE NOT |
| | BEEN SUBMITTED FOR PERMIT. |
| | |
| | ** PLEASE CORRECT ADDRESS AND SUITE/UNIT |
| | NUMBER ON ALL SHEETS IN CADD/PROGRAM. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES |
| | ARE REQUIRED AT A MINIMUM. |
| | 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003 |
| | NFPA-101. |
| | THESE SHOULDS ALSO BE LOCATED IN NOTE ON ELECTRICAL |
| | PLANS 16A. |
| | |
| | 2) NOTE: PLEASE BE SURE WHEN SUBMITTING |
| | PLANS TO ATTACH ALL SHEETS TOGETHER INTO |
| | TWO COMPLETE SETS. PLEASE SEE THAT PLANS |
| | WERE SUBMITTED AS LOOSE SHEETS AND WERE |
| | ATTACHED INTO SETS BY THIS OFFICE THIS |
| | TIME AS A COURTESY. |
| | FBC 106.1 ADMIN SECT. |
| | |
| | 3) NOTE: PLEASE CLARIFY TITLE BLOCKS FOR |
| | THE ARHCITECTURAL FIRM. PLEASE SEE COVER |
| | SHEET SHOWS "MBH " ARCHITECTS AND "A" |
| | SHEETS INDICATE "DH" ARCHITECTS?? |
| | PLEASE SEE MEP SHEETS DO INDICATE |
| | "MDH"??? |
| | PLEASE KNOW IN EITHER CASE, PLEASE SEE |
| | MISSING REQUIRED LICENSE NUMBERS FOR |
| | FIRM(S). PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G1-16.004ANF |
| | FLORIDA STATUS 481.219 FOR ARCHITECTURAL |
| | FIRMS REQUIRING A CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | PLEASE ALSO SEE THE TITLE BLOCKS MISSING |
| | THE REQUIRED PRINTED NAME AND LICENSE |
| | NUMBER FOR THE ARCHITECT OF RECORD. |
| | ** THIS IS REQUIRED ON ALL SHEETS AND |
| | FOR ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 4) NOTE: PLEASE SEE FS 481.221 WHICH |
| | REQUIRES THE ARCHITECT TO DATE SAID |
| | PLANS WHEN SIGNING AND SEALING |
| | DOCUMENTS. |
| | |
| | 5) NOTE: PLEASE CLARIFY ENGINEERING |
| | TITLE BLOCKS AND RESPONSIBLE PARTIES. |
| | PLEASE SEE COVERSHEET LIST "HBK |
| | ENGINEERING", YET MEP'S DO NOT CONTAIN |
| | THE SAME TITLE BLOCK?? |
| | PLEASE ALSO SEE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR SAID |
| | ENGINEERING FIRM. |
| | FAC 61G15-23.002, FS 471.023 |
| | |
| | 6) NOTE: PLEASE SEE LIGHTING CONTROL |
| | CONTACTORS ARE BEING SHOWN , HOWEVER |
| | COULD NOT LOCATE THE AUTOMATIC SHUT OFF |
| | FOR LIGHTING CONTROLS AS REQUIRED UNDER |
| | FBC 2004 CHAPTER 13. |
| | PLEASE SEE MISSING THE SCHEDULING, |
| | OVER-RIDE DEVICES. |
| | PLEASE SEE SEPARATE SPACES WITH FLR TO |
| | CEILING HEIGHT PARTITIONS WHICH REQUIRE |
| | OVER RIDES OF THE NORMAL LC SYSTEM. |
| | PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 |
| | AND .1.3. |
| | PLEASE SUPPLY THE LIGHTING POWER DENSITY CALCULATIONS |
| | AS SETFORTH IN |
| | 13-415.2.ABC.1 AND TABLE 415.2.B.1, |
| | 415.2.C.1 |
| | ** PLEASE KNOW OVER-RIDES SHALL BE |
| | LOCATED SO THE OCCUPANT CAN SEE LIGTHING |
| | BEING CONTROLLED FOR MAIN SYSTEM. |
| | PLEASE SPECIFY THE OVER-RIDE DEVICES, IF |
| | TIMER TYPE (4HRS MAX) , IF OCCUPANT |
| | SENSOR TYPE (30MINS MAX). |
| | ** PLEASE KNOW, ANY LIGHTING BEING LEFT |
| | IN THE "ON" POSITION INTENDED AS NIGHT |
| | LTS SHOULD BE KEPT TO A MINIMUM. PLEASE |
| | SEE THE STORE FRONT WOULD BE ACCEPTABLE |
| | , HOWEVER ALL OTHER TRACK LIGHTING |
| | SHOULD BE SHUT OFF WITH THE AUTOMATED |
| | LIGHTING |
| | CONTROLS. PLEASE SEE THAT THIS NUMBER OF |
| | FIXTURES CAN BE GONE OVER. THE AMOUNT OF |
| | FIXTURES SHOWN EXCEEDS THAT REQUIRED BY |
| | THE FEC FOR THIS AHJ'S INTERPRETATION. |
| | |
| | 7) NOTE: PLEASE SEE POSSIBLE NOTES FROM |
| | BUILDING/PLUMBING REVIEW AS THE ACCESS |
| | TO THE HC BATHS SEEMS TO BE LOCATED |
| | THROUGH THE "STOCKROOM". THIS IS NOT AN |
| | ELECTRICAL REVIEW NOTE, HOWEVER A CLEAR |
| | AND UNOBSTRUCTED PATH MAY NOT EXIST FOR |
| | FIRE EGRESS ETC.?? |
| | THIS IS ONLY NOTED. |
| | |
| | 8) NOTE: PLEASE SEE A SYMBOL IS BEING |
| | SHOWN ON THE LIGHTING PLAN E2.00, |
| | HOWEVER THIS SYMBOL COULD NOT BE LOCATED |
| | ON THE PLANS/SCHEDULE/SYMBOL LIST. |
| | THIS HAS BEEN REDLINED ON PLANS ON ONE |
| | SET TO CLARIFY?? |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 9) NOTE: PLEASE SEE THE TRANSFORMER IS |
| | BEING SHOWN ON THE RISER LOCATED ABOVE |
| | THE CEILING WHICH IS NOT PERMITTED PER |
| | 450.13B. |
| | PLEASE PROVIDE AN ALTERNATE LOCATION. |
| | PLEASE SEE 450.9, 450.21A |
| | ** PLEASE ALSO SUBMIT A STRUCTURAL |
| | ENGINEERING DETAIL FOR THE SUPPORT AND |
| | MOUNTING OF UNIT. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE KNOW, ANY LOCK-OFF |
| | DEVICE BEING PROPOSED FOR CIRCUITS, |
| | SHALL BE AN INTEGRAL PART OF THE BREAKER |
| | WHERE REQUIRED BY CODE. PLEASE KNOW THE |
| | DEVICE TYPE CAN NOT JUST SIMPLY FALL OFF |
| | UPON THE REMOVAL OF THE PANEL COVERS, OR |
| | SNAP ON TO THE BRKR. |
| | ** WHERE REQUIRED BY CODE FOR CIRCUITS, |
| | OPTIONAL CIRCUITS DO NOT APPLY. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |