| 2006-09-09 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE KEY PLAN AND WINDOWS AND |
| | DOORS SIZES. TO VERIFY EGRESS |
| | COMPLIANCE. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 2- PROVIDE OPENING PROTECTION (SHUTTERS |
| | OR ANY OTHER MEANS OF GLAZING |
| | PROTECTION) AS REQUIRED BY SECTION 507.3 |
| | FBC 2004, EXISTING BUILDING. |
| | PROVIDE PRODUCT APPROVAL, KEY PLAN AND A |
| | COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE OF INSTALLATION SCHEDULE |
| | FROM THE CITY IMPLEMENTATION STANDARD |
| | FOR WIND-BORNE DEBRIS IMPACT PROTECTION. |
| | |
| | 3- ACCORDING TO INSPECTOR'S |
| | PRE-INSPECTION AND PICTURES BUILDING HAS |
| | ROTTEN AREAS AT OPENINGS FRAMING. NEED |
| | TO REPLACE FRAMING AS REQUIRED. PROVIDE |
| | COMPLETE STRUCTURAL FRAMING DETAILS FOR |
| | DOORS AND WINDOWS INSTALLATION. SEC. |
| | 106.1.2 OF CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- THIS PERMIT APPLICATION IS FOR DOORS |
| | AND WINDOWS REPLACEMENT ONLY. ACCORDING |
| | TO THE INSPECTOR'S PICTURES THERE IS |
| | CONSIDERABLE STRUCTURAL DAMAGE TO THE |
| | HOUSE. PROVIDE COMPLETE ENGINEERING AND |
| | STRUCTURAL PLANS TO PERFORM ALL |
| | STRUCTURAL REPAIRS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 5- THERE ARE 2 DIFFERENT PRODUCT |
| | APPROVALS FOR DOORS SUBMITTED. SUBMIT |
| | ONLY THE ONE FOR THE SPECIFIC DOOR TO BE |
| | INSTALLED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |