| Date |
Text |
| 2007-11-02 16:25:14 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | A SEPARATE GAS PERMIT IS REQUIRED |
| | |
| | FROM THE PREVIOUS REVIEWS: |
| | ****FROM PREVIOUS REVIEWS: |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE GAS PERMIT: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. TYPE OF GAS (NATURAL SHOWN ON |
| | GENERATOR SPECIFICATION SHEETS. INDICATE |
| | ON ISOMETRIC). |
| | ****RESPONSE NOTED, BUT THERE IS A CONFLICT OF |
| | INFORMATION SUBMITTED, APPLICATION AND PLANS INDICATE |
| | AND LP SYSTEM WITH AN UNDERGROUND 1000 GAL LP TANK. THE |
| | INFORMATION SUBMITTED UNDER THE RISER DIAGRAM STATES |
| | NATURAL GAS. PLEASE CLARIFY. |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | ****RESPONSE NOTED, BUT THE BTU'S INDICATED ON THE |
| | INFORMATION UNDER THE RISER DIAGRAM STATES 273,120 |
| | BTU"S/PER HR, BUT THE MANUF. SPECIFICATIONS SHEETS |
| | INDICATE 1,100 CUBIC FT/HR. . MANUF SPECIFICATION |
| | SHEETS ALSO INDICATE NATURAL GAS. NO LP GAS IS |
| | INDICATED. PLEASE CLARIFY. |
| | |
| | 5. OK |
| | 6.OK |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | INSTALLATION REQUIREMENTS SHALL BE |
| | SUBMITTED TO VERIFY CLEARANCES FROM |
| | ADJACENT STRUCTURES. |
| | ****INSTALLATION INSTRUCTIONS HAVE NOT BEEN SUBMITTED |
| | WITH THE MANUF. SPECIFICATION SHEETS. |
| | ******INSTALLATION INSTRUCTIONS WITH REQUIRED |
| | CLEARANCES HAV NOT BEEN SUBMITTED. |
| | |
| | ************NEW COMMENT************* |
| | |
| | 1B. OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |