| 2007-09-22 12:12:38 | |
| | ** DENIED 4TH REVIEW** |
| | |
| | ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | PLEASE KNOW THERE ARE SOME ITEMS WHICH COULD BE |
| | REDLINED. |
| | |
| | 1) NOTE: PLEASE SEE CODE STATED IN THE 2005 WHEN |
| | PROJECT IS UNDER 2002 NEC> ALSO STATES 220.83 WHICH IS |
| | FOR RESIDENTIAL. |
| | THESE COULD BE REDLINED HOWEVER COMMENTS ARE MADE AT |
| | THIS TIME FOR OTHER ITEMS. |
| | |
| | 2) NOTE: PLEASE SEE THE LOAD BASED ON ONE YEAR IS |
| | ACTUALLY HIGHER THAN THE RATING OF THE GENERATOR. |
| | HOW WILL THIS BE ADDRESSED? WILL LOADS BE SHED? |
| | 702.5, 220.87 |
| | |
| | 3) NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS REVIEW. |
| | PLEASE PROVIDE DOCUMENTATION FOR THE NEW MTSAND |
| | WHETHER OR NOT THIS IS SERVICE ENTRANCE RATED. BASED ON |
| | THE MANUFACTURES SPECS/CUT SHEETS SUBMITTED THERE IS |
| | NOT INFORMATION ON THIS. |
| | 230, 110.3, 90.7, 230.76, 230.79 ETC, |
| | |
| | 4) NOTE: PLEASE SEE THE RISER INDICATES *EQUIPMENT |
| | GROUNDING CONDUCTORS* FROM METER TO THE MTS. IF THE MTS |
| | IS SERVICE ENTRANCE RATED AND IS THE FIRST MEANS OF |
| | DISCONNECT, AN *EGC* IS NOT PERMITTED BEFORE THE FIRST |
| | MEANS OF DISCONNECT. |
| | THIS COULD BE REDLINED HOWEVER PLANS HAVE OTHER NOTES. |
| | |
| | 5) NOTE: PLEASE CLARIFY WHERE THE ELEVATION OF NEW SLAB |
| | IS LOCATED ON PLANS? |
| | PLEASE SEE BUILDING REVIEW COMMENTS ALSO, AS THIS IS |
| | REQUIRED TO BE 6INCHES ABOVE ANY BASE FLOOD ELEVATION |
| | IF THIS IS LOCATED IN A FLOOD ZONE A. |
| | ** IT WAS NOTED THE RESPONSE MENTIONS AN ELEVATION |
| | CERTIFICATE WILL BE SUBMITTED HOWEVER IT IS THE |
| | UNDERSTANDING THE ELEVATION WILL BE NEEDED ON SHEETS. |
| | ** SEE BUILDING REVIEW NOTES** |
| | |
| | 6) NOTE: PLEASE SEE NO VALUE FOR GAS SCOPE OF WORK |
| | APPLICATION IS STATED. |
| | PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF WORK |
| | MUST INCLUDE ALL LABOR AND MATERIALS, INCLUDING |
| | EQUIPMENT ETC |
| | FBC 108.3 |
| | AS THE SCOPE OF WORK HAS INCREASED SINCE ORIGINAL |
| | PERMIT APPLICATION, PLEASE ADJUST. |
| | |
| | 7) NOTE: THE NOTICE OF COMMENCEMENT WHICH WAS SUBMITTED |
| | RECORDED ON 3/14/07 HAS BECOME VOID PER FS 713.13(2). |
| | WHEN WORK HAS NOT COMMENCES WITHIN 90DAYS OF RECORDING |
| | THE NOC, THE NOC BECOMES VOID. |
| | **THIS WILL ONLY NEED TO BE RE-RECORDED AND SUBMITTED |
| | PRIOR TO PICKING UP THE PERMIT ONCE ISSUED. |
| | |
| | 8) NOTE: PLANS NOW MENTIONS BUILDING OF NEW WALL, |
| | HOWEVER NO PLANS FOR WALL ETC WAS SUBMITTED. PLEASE SEE |
| | COMMENTS FROM OTHER TRADES AS THIS IS NOT AND |
| | ELECTRICAL REVIEW ITEM. PLEASE ONLY KNOW THE |
| | CONSTRUCTION OF WALL MAY NOT BE DONE UNDER THE |
| | ELECTRICAL U LICENSE. |
| | |
| | ** PLEASE KNOW SOME OF THE ABOVE ITEMS COULD HAVE BEEN |
| | REDLINED, HOWEVER PLANS NEEDED SOME OTHER ITEMS TO BE |
| | ADDRESSED AT THIS TIME. |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT ELECTRICAL PLANS OR DESIGN. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| | THIS REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |