| 2007-03-25 09:15:02 | |
| | |
| | ****** UNSAT 3ND REVIEW****** |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | ** PLEASE SEE THAT THERE COMMENTS MADE TO SHEETS OTHER |
| | THAN ELECTRICAL BY THIS REVIEW. THESE COMMENTS ARE |
| | REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| | TRADE. |
| | |
| | ** IMPORTANT** |
| | DUE TO MANY OF THE COMMENTS BELOW ONE COMPLETE SET OF |
| | EACH PLAN SUBMITTED ARE BEING RETAINED BY THIS OFFICE. |
| | PLEASE ALSO SEE THAT COMMENTS FROM PREVIOUS REVIEW |
| | STILL NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS DUE |
| | TO PLANS CHANGING. |
| | |
| | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS WITH |
| | ALL INFORMATION IN TWO NEAT AND ORDERLY SETS. PLEASE |
| | SEE THE SHEETS SUBMITTED ARE IN COMPLETE DISARRAY WITH |
| | MANY SHEETS LOOSE AND NOT IN ANY SETS OR BOUND |
| | TOGETHER?? |
| | ** PLEASE SEE THERE IS MULTIPLE ELECTRICAL RISERS YET |
| | SOME CONTAIN THE SAME DATE OF THE PREVIOUS RISER |
| | DIAGRAM SUBMITTED. PLEASE CORRELATE ALL PLANS, SHEETS, |
| | DATE THE REVISED SHEETS. THE PLANS WHICH SEEMED TO BE |
| | REVISED SHEETS CONTAIN A DATE OF JANUARY 10, 2007 |
| | HOWEVER THAT DATESBEFORE THE LAST ELECTRICAL REVIEW |
| | WHICH WAS DONE ON 2/2/07.THE PREVIOUS REVIEWED PLANS |
| | ALSO CONTAINED A DATE OF 1/10/07??? |
| | FBC 106.3 |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS SUBMITTED STILL DO NOT |
| | INDICATE THE CORRECT CODES RELEVANT TO THE PLANS AND |
| | DESIGNS AT A MINIMUM AS REQUESTED ON THE TWO PREVIOUS |
| | REVIEWS. PLEASE SEE THE CODES REQUESTED ARE FOR THIS |
| | REVIEWER ONLY AND OTHER CODES FROM OTHER TRADES MAY BE |
| | NEEDED. |
| | |
| | 3) NOTE: PLEASE SEE THE REQUIRED GAS RISER PLANS WERE |
| | NOT SUBMITTED IN PACKAGE FOR PLUMBING REVIEW. SEE |
| | PLUMBING REVIEW COMMENTS. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THE MODEL OF THE GENERATOR IS STILL |
| | NOT INDICATED ON THE MANUFACTURES SPECS/CUT SHEETS |
| | SUBMITTED AND NOW THE BREAKER ON THE RISER DIAGRAM ON |
| | THE GENERATOR HAS NOW INCREASED WHICH NOW CORRELATES TO |
| | THE SINGLE PHASE GENERATOR ON SPECS? |
| | PLEASE SPECIFY WHICH UNIT IS BEING INSTALLED, PLEASE |
| | HIGHLIGHT UNIT, PLEASE REVISE RISER IF INDEED THIS IS |
| | NOW THE SINGLE PHASE UNIT AS IT SEEMS.PLEASE SEE THE |
| | FOLLOWING COMMENT #5. |
| | 110.3, 90.7 |
| | FBC 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE CONDUCTORS ARE NOT THE CORRECT |
| | SIZE FROM THE GENERATOR TO THE MTS PER 310.16 BASED ON |
| | THE NEW 350AMP OVER CURRENT PROTECTION AS SHOWN. PLEASE |
| | SEE THE 300MCM IS ONLY RATED AT 285AMPS. |
| | 240.4, 310.16. |
| | |
| | 6) NOTE: PLEASE SEE A COMPLETE READABLE LAYOUT FOR ALL |
| | EQUIPMENT, LOCATIONS, SET-BACKS ETC WAS NOT SUBMITTED. |
| | THE DETAILS ON THE SHEETS ARE TOO SMALL, ARE NOT CLEAR |
| | AND DO NOT PROVIDE THE LOCATIONS OF ALL EQUIPMENT. |
| | AS THE NOW MTS IS NOT CLEAR IF IT IS SERVICE ENTRANCE |
| | RATED DUE THE SPECS WHICH MENTIONS EQUIPMENT RATED TO |
| | GO TO THE SERVICE ENTRANCE EQUIPMENT, IS THE EXISTING |
| | PANEL LOCATED IN CLOSE PROXIMITY AND DOES IT CONTAIN |
| | OVER CURRENT PROTECTION? |
| | IS THIS MTS SERVICE ENTRANCE RATE AND CONTAIN OVER |
| | CURRENT PROTECTION. THE SPECS MENTIONS FUSES AS PART OF |
| | THE FEATURES HOWEVER THE NOTES ON SAME SHEET SEEM TO |
| | CONTRADICT THIS. |
| | PLEASE SEE 230.76, 230.79, 230.70, 71, 230.90 ETC. |
| | IS THERE ANY FURTHER SPECS/CUT SHEETS WHICH INDICATE |
| | THE INTERNAL WIRING AND INFORMATION ON UNIT? |
| | 110.3, 90.7. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE SEE NFPA-110 CHAPTER 7 AND BUILDING |
| | CODE REQUIREMENTS WHICH REQUIRE THIS UNIT TO BE MOUNTED |
| | A MINIMUM OF 6INCHES ABOVE THE BFE. THE PLANS/SHEETS |
| | SUBMITTED DO NOT INDICATE THE ELEVATIONS AND SO ON. SEE |
| | THE BUILDING REVIEW COMMENTS FOR THIS ALSO. |
| | |
| | 8) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED ARE |
| | THE SAME AS SUBMITTED FROM PREVIOUS REVIEWED PLANS |
| | WHICH ARE FOR A RESIDENTIAL APPLICATION. |
| | PLEASE SUBMIT THE LOADS INTENDED FOR THIS UNIT AS |
| | COMMERCIAL.PLEASE ALSO SEE THAT BASED ON NOW A SINGLE |
| | PHASE UNIT BEING INSTALLED, THIS WILL REVISE SHEETS. |
| | PLEASE COORDINATE ALL SHEETS, PLANS, ETC. |
| | 220.3,220.10,220.11,220.13, 220.35 ETC |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE WHAT APPEARS TO BE THE LATEST RISER |
| | DOES NOT CONTAIN AN CONDUCTOR SIZES FROM THE METER TO |
| | THE MTS?? |
| | PLEASE COMPLETE RISER. |
| | PLEASE SEE 310.16, 240.4. |
| | |
| | 10) NOTE: PLEASE KNOW SINCE THERE WERE COMMENTS AND |
| | PLANS HAVE FAILED THREE TIME FOR SOME OF THE SAME |
| | NOTES, THE PREVIOUS REVIEW MENTIONED FS 553.80(2)(B) |
| | WITH RESPECT TO REPEAT COMMENTS. A FEE IS NOW ASSESSED |
| | IN THE AMOUNT OF $771.50 WHICH WILL BE REQUIRED TO BE |
| | PAID BEFORE THE NEXT RE-SUBMITTAL. |
| | |
| | 11) NOTE: PLEASE SEE AS NOTED ON THE PREVIOUS REVIEW |
| | THE NOC WILL NEED TO BE RE-RECORDED AS IT HAS EXPIRED |
| | PER FS 713.13(2). |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCEA ND THESE SHEETS SHOULD BE ATTACHED IN |
| | ONE SET AND LABLED OLD/VOIDED SHEETS. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |