| Plan Review Notes For Permit 06082000 |
| Permit Number |
06082000 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-28 08:34:21 | DENIED BY BUILDING (3RD REVIEW) | | | | | | 1) THE GENERATOR TO PAD ATTACHMENT IS SPECIFIED AS (4) | | | 1/4" X 2-1/4" TAP-CONS. THIS IS NOT ADEQUATE. SEE THE | | | SIGNED AND SEALED ENGINEERING FOR THE FEATHERLITE | | | GENERATOR PAD WHICH SPECIFIES ALL ANCHORS TO BE 3/8 " | | | DIAMETER GALVANIZED GRADE 2 BOLTS WITH GALVANIZED HEAVY | | | FENDER WASHERS ON THE BOTTOM OF THE PAD. PLEASE REVISE. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|