| Plan Review Notes For Permit 06082000 |
| Permit Number |
06082000 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-02-12 18:16:19 | DENIED BY BUILDING | | | | | | 1) THE GENERATOR IS 115.2 INCHES LONG. THE ONLY PAD | | | LISTED ON THE ENGINEERING LARGE ENOUGH IS FRCC GEN 5. | | | THE CALCULATIONS FOR THIS PAD WERE NOT PROVIDED. | | | | | | 2)FS 471 REQUIRES EACH SHEET TO BE SIGNED AND SEALED | | | OR A SIGNED AND SEALED COVER OR INDEX SHEET SPECIFING | | | THE PAGES IN THE REPORT OR SPECIFICATIONS. ENGINEERING | | | SUBMITTED DOES NOT COMPLY. SEE FAC 61G15-23. | | | | | | 3)THE SIGNATURE IS REQUIRED TO BE ORIGINAL. COLOR | | | PHOTO COPIES ARE NOT ACCEPTABLE. ALSO THE DATE ON THE | | | ENGINEERING IS THE DATE OF WHEN THE RAISE SEAL IS | | | AFFIXED. SEE FS 471. | | | | | | 4) SUBMIT SIGNED AND SEALED PAD AND BOLT LAYOUTS AND | | | CONNECTION DETAIL DRAWINGS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|