| 2006-09-05 00:00:00 | ********** UNSAT ************* |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS WHICH |
| | REFLECT THE 2002 NFPA-70 (NEC), THE 2002 |
| | NFPA-110, 2004 FBC. |
| | |
| | 2) NOTE: PLEASE CORRELATE SLAB DETAIL |
| | AND SPECS FROM MANUFACTURE. PLEASE SEE |
| | SIZE INDICATED FOR THIS 80KW UNIT DOES |
| | NOT EXIST ON SHEETS FROM THIS |
| | MANUFACTURE AND HAS NOT BEEN LOCATED ON |
| | THEIR WEBSITE. |
| | PLEASE SEE NFPA-110 CHPATER 7 FOR |
| | MOUNTING AND LOCATIONS OF GEN.. |
| | FBC CHAPTER 27. 2004. |
| | ** PLEASE SEE BUILDING REVIEW COMMENTS |
| | AS UNIT IS BEING PROPOSED IN A FLOOD |
| | ZONE "A", WHICH WILL REQUIRE UNIT AT A |
| | MIN OF 6" ABOVE BFE. PLEASE KNOW, |
| | ENGINEERING ON SLAB, FOUNDATION AND |
| | MOUNTING IS NEEDED AS THE INFORMATION |
| | SUBMITTED IS NOT SUFFICIENT. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE RISER SUBMITTED IS |
| | SHOWING SEC'S AND FEEDERS WHICH ARE NOT |
| | LARGE ENOUGH FOR THE GENERATOR FEEDERS |
| | OR THE 600A SERVICE BEING SHOWN. |
| | PLEASE SEE 240.4,310.16 AND ADJUST. |
| | |
| | 4) NOTE: PLEASE SEE RISER IS SHOWING AN |
| | " EQUIPMENT GROUNDING CONDUCTOR" FROM |
| | METER TO MAIN/FIRST MEANS OF DISCONNECT |
| | WHICH WILL CREATE OBJECTIONAL CURRENTS. 250.6,250.24B |
| | |
| | 5) NOTE: PLEASE BE SURE UNIT IS BEING |
| | SHOWN ON SITE/SURVEY PLANS SHOWING THE |
| | EXACT LOCATIONS AND SETBACKS FROM ALL |
| | SURROUNDING STRUCTURAL WALLS, FENCES |
| | ETC. |
| | PLEASE OBTAIN INFORMATION FROM GENERATOR MANUFACTURE |
| | WHICH SPECIFIES THE MIN |
| | CLEARENCES. PLEASE KNOW, AS THE SPEC FOR |
| | THE GEN WAS NOT SUBMITTED, IT IS BEING |
| | ASSUMED THIS UNIT IS A GENERAC UNIT, AND |
| | THE INFORMATION OBTAINED FROM THIS |
| | OFFICE IS THAT THEY REQUIRE A MIN OF 5FT |
| | FOR THE LARGER LIQUID COOLED UNITS. |
| | 110.3,90.7 |
| | |
| | 6) NOTE: PLEASE KNOW AS TO DATE THE |
| | SUBMITTED GENERATOR PACKAGE MUST CONTAIN |
| | THE GAS INFORMATION RISER ETC, PLEASE |
| | SEE PLUMB REVIEW COMMENTS. |
| | |
| | 7) NOTE: PLEASE PROVIDE A |
| | LAYOUT/OVERVIEW ON PLANS WHICH SHOWS THE |
| | LOCATIONS OF ALL SERVICE EQUIPMENT AS |
| | SHWON ON RISER DIAGRAM. |
| | PLEASE SEE SPECS FOR ATS DO NOT SEEM TO |
| | INDICATE THE NEMA RATING IF THE ATS IS |
| | OUTSIDE. |
| | PLEASE ALSO HIGH-LIGHT UNIT. |
| | FBC 106.1.2, 110.3 |
| | |
| | 8) NOTE: PLEASE SEE NO DISCONNECT |
| | GROUPED WITH THE EXISTING MAIN COULD BE |
| | LOCATED ON PLANS OR ON RISER. PLEASE SEE 225.31-225.39, |
| | 230.72. |
| | PLEASE KNOW THE BREAKER LOCATED INSIDE |
| | THE GENERATOR IS NOT ACCEPTABLE FOR |
| | THIS. |
| | PLEASE KNOW THE ATS AS SUBMITTED DEOS |
| | NOT CONTAIN A MAIN DISCONNECT RATED FOR |
| | THE LOAD SERVED AS REQUIRED FOR THE |
| | FEEDERS COMING FROM THE GENERATOR. THIS |
| | TYPE UNIT MAY ONLY CONTAINA "TOGGLE" |
| | TYPE DEVICE WHICH IS NOT RATED. |
| | |
| | 9) NOTE: PLEASE SUBMIT COMPLETE |
| | ELECTRICAL LOAD CALCULATIONS FOR THIS |
| | COMMERCIAL BUILDING. PLEASE SEE THE LOAD |
| | CALCS SUBMITTED ARE FOR A RESIDENTIAL |
| | HOUSE WHEN THIS IS A COMM BLDG.???? |
| | 220.3,220.10,220.11,220.13, ETC |
| | CONTINUOUS LOADS AT 125% 215.3,230.42 |
| | ETC. |
| | |
| | 10) NOTE: WHEN SUBMITTING PLANS/DESIGNS |
| | WHICH ARE NOT DONE BY AN ENGINEER, |
| | PLEASE SEE THAT ALL PLANS/DESIGNS MUST |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBEL FOR PLANS AND |
| | DESIGNS. |
| | FBC 106.1.2 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |