| Plan Review Notes For Permit 06081989 |
| Permit Number |
06081989 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-27 00:00:00 | | | | | | | DENIED | | | | | | 1) PROVIDE NEW NOA FOR TAMKO BUR PRODUCT | | | AS THE ONE SUBMITTED HAS EXPIRED | | | | | | 2) BE SURE TO CHOOSE A SYSTEM FROM THE | | | PRODUCT APPROVAL THAT WILL BE USED | | | | | | 3) PER 1609.6.1 THE SIMPLIFIED | | | CALCULATION METHOD FOR WIND LOADS SHALL | | | NOT BE USED TO DETERMINE WIND PRESSURES | | | FOR BUILDINGS OVER 60 FT IN HEIGHT. | | | PLEASE SUBMIT ENGINEERED CALCULATIONS | | | | | | 4) PROVIDE THE CALCULATIONS FOR THE | | | ENHANCED FASTENING THAT WILL BE USED FOR | | | THE PERIMETER AND CORNER ZONES | | | | | | ADRIAN MORSE | | | BLDG PLAN REVIEW | | | 561-805 6716 |
|