Plan Review Notes
Plan Review Notes For Permit 06081976
Permit Number 06081976
Review Stop E
Sequence Number 3
Notes
Date Text
2006-12-09 18:58:50** UNSAT 3RD REVIEW**
  
 1) NOTE: PLEASE SEE METHOD "B" CALCULATIONS FOR
 LIGHTING ALLOWANCES AND DESIGN WATTAGE AS SHOWN IS NOT
 YET CLEAR. PLEASE SEE MAXIMUM WATTAGE AS SHOWN FOR
 COMPLETE DESIGN IS STATED AS 7691.6 BASED ON TABLES IN
 THE FBC AND AS STATED ON PLANS. PLEASE EXPLAIN HOW THE
 DESIGN WATTAGE IS 11,354?
 PLEASE KNOW BASED ON METHOD "B" AND SQ FT ENTERED AS
 4310 THIS WILL SHOW AND INDICATE A "PASS" RESULT.
 PLEASE KNOW AS PER OUR CONVERSATIONS OVER THE PHONE
 AREAS OF TRADES OFFS WERE PERMITTED AS STATED IN
 13-415.2.B.1 ITEM (4), HOWEVER AS SHOWN THE WATTAGE
 STILL EXCEEDS ALLOWANCES AS NO AREAS SHOW AN DESIGN
 SUBSTANTIALLY LESS WHICH WOULD PERMIT ADDITIONAL
 WATTAGE IN OTHER AREAS. AS PER CONFERENCE CALLS, THE
 DESIGN WATTAGE TOTALS WOULD NOT EXCEED TOTAL ALLOWED.
 PLEASE SEE 13-415.2.B.2. PLEASE SEE IF THESE ARE BEING
 USED, THEN PLEASE KNOW THIS WILL NEED TO BE SHOWN ON
 PLANS UNLESS FIGURED AND SHOWN INTO METHOD "B". IT IS
 OUR UNDERSTANDING THAT METHOD "B" DOES NOT PERMIT THIS
 BREAK DOWN AS LISTED FOR ADDITIONAL POWER ALLOWANCES,
 THEREFORE A TABLE MAY BE USED ANDWILL BE REQUIRED TO
 BE PLACED ON PLANS WHICH PROVIDES A DETAILED BREAKDOWN
 OF AREAS ETC. ( SHEET E-4 , LOWER RIGHT HAND CORNER)
 PLEASE SEE SECTIONS: 1. , 2. , 3. (1)(2).
  
 2) NOTE: PLEASE BE SURE ALL RESPONSE LETTERS FROM
 DESIGN TEAM ARE DATED TO ALLEVIATE ANY CONFUSION OF
 WHICH NOTES ARE BEING REPLIED TO.
 THIS WILL SUBSTANTIALLY HELP IN THE REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-09 18:05:37PLANS REMOVED FROM INCOMING, WILL BE ROUTED BACK TO
 INCOMINGWAITING FOR BOB BOARD ONCE REVIEW IS DONE.