| 2006-12-09 18:58:50 | ** UNSAT 3RD REVIEW** |
| | |
| | 1) NOTE: PLEASE SEE METHOD "B" CALCULATIONS FOR |
| | LIGHTING ALLOWANCES AND DESIGN WATTAGE AS SHOWN IS NOT |
| | YET CLEAR. PLEASE SEE MAXIMUM WATTAGE AS SHOWN FOR |
| | COMPLETE DESIGN IS STATED AS 7691.6 BASED ON TABLES IN |
| | THE FBC AND AS STATED ON PLANS. PLEASE EXPLAIN HOW THE |
| | DESIGN WATTAGE IS 11,354? |
| | PLEASE KNOW BASED ON METHOD "B" AND SQ FT ENTERED AS |
| | 4310 THIS WILL SHOW AND INDICATE A "PASS" RESULT. |
| | PLEASE KNOW AS PER OUR CONVERSATIONS OVER THE PHONE |
| | AREAS OF TRADES OFFS WERE PERMITTED AS STATED IN |
| | 13-415.2.B.1 ITEM (4), HOWEVER AS SHOWN THE WATTAGE |
| | STILL EXCEEDS ALLOWANCES AS NO AREAS SHOW AN DESIGN |
| | SUBSTANTIALLY LESS WHICH WOULD PERMIT ADDITIONAL |
| | WATTAGE IN OTHER AREAS. AS PER CONFERENCE CALLS, THE |
| | DESIGN WATTAGE TOTALS WOULD NOT EXCEED TOTAL ALLOWED. |
| | PLEASE SEE 13-415.2.B.2. PLEASE SEE IF THESE ARE BEING |
| | USED, THEN PLEASE KNOW THIS WILL NEED TO BE SHOWN ON |
| | PLANS UNLESS FIGURED AND SHOWN INTO METHOD "B". IT IS |
| | OUR UNDERSTANDING THAT METHOD "B" DOES NOT PERMIT THIS |
| | BREAK DOWN AS LISTED FOR ADDITIONAL POWER ALLOWANCES, |
| | THEREFORE A TABLE MAY BE USED ANDWILL BE REQUIRED TO |
| | BE PLACED ON PLANS WHICH PROVIDES A DETAILED BREAKDOWN |
| | OF AREAS ETC. ( SHEET E-4 , LOWER RIGHT HAND CORNER) |
| | PLEASE SEE SECTIONS: 1. , 2. , 3. (1)(2). |
| | |
| | 2) NOTE: PLEASE BE SURE ALL RESPONSE LETTERS FROM |
| | DESIGN TEAM ARE DATED TO ALLEVIATE ANY CONFUSION OF |
| | WHICH NOTES ARE BEING REPLIED TO. |
| | THIS WILL SUBSTANTIALLY HELP IN THE REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |