Plan Review Notes
Plan Review Notes For Permit 06081976
Permit Number 06081976
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-24 20:17:14**** UNSAT2ND REVIEW***
  
 ** IMPORTANT**
 PLEASE KNOW, ANY AND ALL PLANS FOR ANY WORK BEING
 PERFORMED ON "CITY PLACE" PROPERTY IS REQUIRED TO
 CONTAIN THE "CITY PLACE" APPROVAL STAMP , SIGNED BEFORE
 PLANS ARE SUBMITTED OR CAN BE ISSED FOR PERMIT.
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW COMMENTS BASED ON CHANGES ON
 PLANS.
  
 PLEASE ALSO SEE NEW NOTES FOR ELECTRICAL ITEMS WHICH
 WERE MISSED BY THIS REVIEWER ON PREVIOUS REVIEW,
 HOWEVER THESE ARE NOW COMMENTED ON THIS REVIEW. CODE
 COMPLIANCE IS STILL REQUIRED WHETHER OR NOT COMMENT WAS
 MADE ON PREVIOUS REVIEW.
  
 ** PLEASE SEE COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND NEW NOTES ADDED TO BOTTOM.
  
  
 1) NOTE: NO/ OK. PLEASE SEE "A" SHEETS IF PRACTICING AS
 AN INDIVIDUAL THEN A CA# IS NOT REQUIRED. PLEASE SEE
 HOWEVER ALL SHEETS ARE REQUIRED TO CONTAIN THE PRINTED
 LICENSE NUMBER FOR SAID INDIVIDUAL. THIS IS REQUIRED ON
 ALL SHEETS AND FOR ALL TRADES WHICH CONTAIN THE TITLE
 BLOCK FOR ARCHITECT.
 PLEASE SEE BASED ON PREVIOUS REVIEWIT WAS NOT TYPED
 FOR THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER FOR
 ENGINEERING FIRM. IN ERROR IT WAS TYPED UP FOR THE
 ARCHITECTURAL FIRM. PLEASE SEE THE SECTIONS WHICH
 SHOULD HAVE BEEN NOTED ARE FAC 61G15-23.002 ANDFS
 471.023 FOR ENGINEERS AND FIRMS. PLEASE SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER AND PLEASE SEE
 MISSING THE PRINTED NAME OF THE INDIVIDUAL AND LICENSE
 NUMBER FOR EACH OF THE SIGNED AND SEALED DOCUMENTS.
 THIS IS REQUIRED ON ALL ENGINEERING SHEETS AND SHEETS
 CONTAINING THE TITLE BLOCK FOR ENGINEERING
 FIRM.(INCLUDING THE CA # ON "A" SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCK FOR
 ARCHITECTURAL FIRM. PLEASE SEE MISSING
 REQUIRED LICENSE NUMBER FOR THE FIRM.
 (CERTIFICATE OF AUTHORIZATION NUMBER).
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUES 481.219.
 **THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
  
 2) NOTE: OK, HOWEVER SEE NEW NOTES PER PLANS
 SUBMITTED.
  
 3) NOTE: OK, NEW SEAL PROVIDED, HOWEVER SEE NEW NOTES
 PER PLANS SUBMITTED.
  
 4) NOTE:NO,PLEASE SEE MULTIPLE SETS OF CALCULATIONS
 ARE SUBMITTED. PLEASE ONLY SUBMITTED THE RELEVANT CALCS
 FOR SCOPE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FLORIDA ENERGY EFF.
 FORMS SENT IN ARE NOT SIGNED, DATED AND
 SEALED BY THE ENGINEER/RESPONSIBLE
 DESIGNER OF RECORD./ PLEASE KNOW, THESE
 MAY NOT CONTAIN PHOTO-COPIED SIGNATURES
 AS SUBMITTED.
 PLEASE ALSO SEE THREE SETS OF ENERGY
 CALCULATIONS WERE SUBMITTED. METHODS A ,
 B AND C???
 PLEASE SEE FBC CHAPTER 13 FOR PERMITTED
 METHOD ONLY PERMITTED IN THE SCOPE OF
 WORK BEING DONE.
 13-101.1.3, 13-415.1.AB.1
  
 5) NOTE:NO,PLEASE SEE SCHEDULING WAS NOT INDICATED.
 PLEASE SEE NO MAX OVER TIMES SHOWN FOR THE DEVICES
 CHOSEN AND SHOWNON PLANS. PLEASE SEE "OCCUPANT
 SENSOR" TYPE DEVICES REQUIRES A MAX OF 30MINS WHERE
 NOTE #8 MENTIONS 4HRS. PLEASE ALSO BE SURE TO CORRELATE
 THE SYMBOLS ON PLANS WITH THE SYMBOL LEGEND FOR TYPE OF
 DEVICE.
 PLEASE SEE NO PERFORMANCE CALCULATIONS WERE SUBMITTED
 BASED ON TABLES AND PERMITTED MAXIMUM WATTAGE PERMITTED
 FOR ACTUAL SPACE. PLEASE SEE SPACE DETERMINATION FOR
 SOME AREAS AS"FINE STORAGE" DOES NOT FIT FOR USE AND
 ITEMS IN STORAGE. PLEASE PROVIDE A SPACE BY SPACE
 CONSIDERATION. THIS MAY BE PLACED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE DETAILS FOR
 THE LIGHTING CONTROL SYSTEM BEING
 PROPOSED AND COMPLIANCE WITH
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SEPARATE SPACES CONTAINING
 FLOOR TO CEILING HEIGHT PARTITIONS AND
 SEPARATE CONTROLS/OVER-RIDES REQUIRED.
 PLEASE KNOW, THE OVER RIDES SHALL BE
 LOCATED SUCH AS THE OCCUPANT VISUALLY
 SEE THE LIGHTING BEING CONTROLLED.
 PLEASE SPECIFY THE TYPE AND TIMES
 PERMITTED ON THE OVER RIDE DEVICES.
 (4HRS MAX TIMER TYPE AND 30MINS MAX ON
 OCCUPANT SENSOR TYPE).
 PLEASE PROVIDE SCHEDULING FOR SYSTEM.
 PLEASE SEE POINTS OF INGRESS AND EGRESS
 FOR CONTROL.
 PLEASE PROVIDE LIGHTING POWER DENSITIES
 PER THE TABLES IN CHAPTER
 13.415.2.ABC.1, 415.2.C.1, 415.2.B.1
  
 6) NOTE: OK.
  
 7) NOTE:NO, RESPONSE MENTIONS PLANS DESIGN PER
 CODES, HOWEVER THE CODES ARE REQUIRED TO BE STATED ON
 PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE FOLLOWING
 CODES ARE REFLECTED AS RELEVANT TO PLANS
 AND DESIGN.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101 AND 2004 FBC.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 ** NEW NOTES ***
  
 13) NOTE: PLEASE SEE WHEN SIGNING AND SEALING PLANS
 THEY ARE ALSO REQUIRED TO BE DATED PER FS 471.025.
 PLEASE SEE OTHER SHEETS AND TRADES ALSO.
  
 14) NOTE: PLEASE CORRELATE RISER WITH PANELS. PLEASE
 SEE PANEL "A" IS BEING SHOWN AS 225A MCB YET RISER
 SHOWS 400A MCB.
  
 15) NOTE: PLEASE KNOW, IF INDEED THIS PANEL "A" IS 400A
 MCB?, PLEASE SEE 240.21C AS THE CONDUCTORS ARE RATED
 FOR 380A'S PER 310.16 FOR 500MCM'S. WHEN ON THE
 SECONDARY SIDE OF A TRANSFORMER , IT MUST TERMINATE IN
 OCP WHICH LIMITS THE AMPERAGE ON THE CONDUCTOR. PLEASE
 SEE 310.16,240.21,110.14 ETC. IT APPEARS HOWEVER THAT
 BASED ON PANEL "A" BEING SHOWN AS 225A'S, THE 500'S AS
 SHOWN WOULD BE OVER.
  
 16) NOTE: PLEASE SEE MAX OCP FOR THE FEEDING THE
 TRANSFORMER IS BASED ON 450.3 TABLES (125%). PLEASE SEE
 NEXT SIZE UP WOULD BE 175A PER 240.6. PLEASE SEE THE
 200A OCP IS TOO HIGH. (PLEASE SEE THERE ARE EXCEPTIONS,
 HOWEVER TRANSFORMER AS SHOWN DOES NOT MEET THEM).
  
 17) NOTE: PLEASE VERIFY THE FEED AND OCP AT THE
 EXISTING MAIN WHICH FEEDS PANEL "H". PLEASE SEE THIS
 PANEL LOAD EXCEEDS WHAT APPEARS TO BE A 150A OCP
 DEVICE, ALTHOUGH 200A RATED FEEDERS ARE FEEDING THIS.
 PLEASE CLARIFY THIS?
 240.4,240,310.16,408. ETC
  
  
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENT FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICAL PLANS/ DESIGN.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-10-24 19:01:25IN ELEC FOR REVIEW


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved