2006-10-27 15:09:08DENIED BY BUILDING
  
 1) RECORDED COPY OF THE NOC WILL BE REQUIRED.
  
 2) PLANS ARE REQUIRED TO HAVE THE CITY PLACE APPROVAL
 STAMP ON THEM.
  
 3) THE CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED
 FOR THE ENGINEERING BUSINESS OF MICHAUD, COOLEY,
 ERICKSON WHICH APPEARS IN THE TITLE BLOCK. SEE FAC
 61G15-23.002 AND FS CHAPTER 471.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE STOREFRONT DOORS
 AND THE HOLLOW METAL EXTERIOR DOOR.
  
 5) THE FLORIDA PRODUCT APPROVAL COVER SHEET SUBMITTED
 FOR THE STOREFRONT IS FOR VISTAWALL GROUP AND THE NOA
 IS FOR VISTAWALL ARCHITECTURAL PRODUCTS. THESE ARE NOT
 THE SAME MANUFACTURERS. THERE IS NO FL PRODUCT APPROVAL
 FOR VISTAWALL ARCHITECTURAL PRODUCTS. HOWEVER, THE
 MIAMI DADE NOA IS ACCEPTABLE WITHOUT FL APPROVAL .
  
 6)THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT PER CITY ADMINISTRATIVE CODE 106.3.
  
 7) THE STOREFRONT SYSTEM IS SPECIFIED INCORRECTLY ON
 THE PLANS AS FG-500. THE PRODUCT APPROVAL IS FOR
 FG-5000. PLEASE CORRECT. SEE SHEETS A6.0, A6.10,
 A6.11.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714