| Plan Review Notes For Permit 06081976 |
| Permit Number |
06081976 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-27 15:09:08 | DENIED BY BUILDING | | | | | | 1) RECORDED COPY OF THE NOC WILL BE REQUIRED. | | | | | | 2) PLANS ARE REQUIRED TO HAVE THE CITY PLACE APPROVAL | | | STAMP ON THEM. | | | | | | 3) THE CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED | | | FOR THE ENGINEERING BUSINESS OF MICHAUD, COOLEY, | | | ERICKSON WHICH APPEARS IN THE TITLE BLOCK. SEE FAC | | | 61G15-23.002 AND FS CHAPTER 471. | | | | | | 4) SUBMIT PRODUCT APPROVALS FOR THE STOREFRONT DOORS | | | AND THE HOLLOW METAL EXTERIOR DOOR. | | | | | | 5) THE FLORIDA PRODUCT APPROVAL COVER SHEET SUBMITTED | | | FOR THE STOREFRONT IS FOR VISTAWALL GROUP AND THE NOA | | | IS FOR VISTAWALL ARCHITECTURAL PRODUCTS. THESE ARE NOT | | | THE SAME MANUFACTURERS. THERE IS NO FL PRODUCT APPROVAL | | | FOR VISTAWALL ARCHITECTURAL PRODUCTS. HOWEVER, THE | | | MIAMI DADE NOA IS ACCEPTABLE WITHOUT FL APPROVAL . | | | | | | 6)THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT PER CITY ADMINISTRATIVE CODE 106.3. | | | | | | 7) THE STOREFRONT SYSTEM IS SPECIFIED INCORRECTLY ON | | | THE PLANS AS FG-500. THE PRODUCT APPROVAL IS FOR | | | FG-5000. PLEASE CORRECT. SEE SHEETS A6.0, A6.10, | | | A6.11. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|