| Plan Review Notes For Permit 06081976 |
| Permit Number |
06081976 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-23 00:00:00 | DENIED; | | | 1.PLANS TO BE SEALED AND SIGNED, COPYS | | | NOT PERMITED. | | | 2.PAGE A1.0 DEMO PLAN; PLEASE ADD NOTE | | | TO PLAN (NO DEAD ENDS PERMITED IN THE | | | PLUMBING SYSTER SECTION 704.5. PLUMBING | | | DEMO INSPEDTION REQUIRED) | | | 3.SEPARATE TOILET FACILITIES REQUIRED. | | | SEE FBC-2004 PLUMBING SECTION 403.2 | | | EXCEPTION 4. THE RETAIL SPACE IS OVER | | | 300 SQ. FT. BATHROOM MUST BE ACCESSABLE | | | TO THE PUBLIC ALSO UNLESS THERE ARE | | | PUBLIC FACILITIES TO COMPLY WITH SECTION | | | 403.6. | | | 4.PAGE A7.4 DETAIL 14; DRAWING SHOWS | | | KICK PLAT AND DOORS WITH GARBAGE | | | DISPOSAL. A FRONTAL APPROACH APPROACH IS | | | REQUIRED SEE SECTION 11-4.21.3 KNEE | | | CLEARANCE UNDER SINK ISA MIN. OF 19". | | | SHOW CLEAR FLOOR SPACE ON FLOOR PLAN. | | | 5.PAGE P-1 PLUMBING FIXTURE SCHEDULE; | | | TOILET SEAT TO BE OPEN FRONT WITHOUT LID | | | IS REQUIRED FOR A PUBLIC TOILET. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|