Date Text
2006-09-23 00:00:00DENIED;
 1.PLANS TO BE SEALED AND SIGNED, COPYS
 NOT PERMITED.
 2.PAGE A1.0 DEMO PLAN; PLEASE ADD NOTE
 TO PLAN (NO DEAD ENDS PERMITED IN THE
 PLUMBING SYSTER SECTION 704.5. PLUMBING
 DEMO INSPEDTION REQUIRED)
 3.SEPARATE TOILET FACILITIES REQUIRED.
 SEE FBC-2004 PLUMBING SECTION 403.2
 EXCEPTION 4. THE RETAIL SPACE IS OVER
 300 SQ. FT. BATHROOM MUST BE ACCESSABLE
 TO THE PUBLIC ALSO UNLESS THERE ARE
 PUBLIC FACILITIES TO COMPLY WITH SECTION
 403.6.
 4.PAGE A7.4 DETAIL 14; DRAWING SHOWS
 KICK PLAT AND DOORS WITH GARBAGE
 DISPOSAL. A FRONTAL APPROACH APPROACH IS
 REQUIRED SEE SECTION 11-4.21.3 KNEE
 CLEARANCE UNDER SINK ISA MIN. OF 19".
 SHOW CLEAR FLOOR SPACE ON FLOOR PLAN.
 5.PAGE P-1 PLUMBING FIXTURE SCHEDULE;
 TOILET SEAT TO BE OPEN FRONT WITHOUT LID
 IS REQUIRED FOR A PUBLIC TOILET.
 PLUMBING PLAN REVIEW BY;