| Notes |
| Date |
Text |
| 2006-09-11 00:00:00 | *** DENIED *** | | | 1) PLANS SHOW USABLE SPACE AS 4310 SQ. | | | FT., ENERGY CAL'S. SHOW CONDITIONED AREA | | | AS 5304 SQ. FT., THE TWO MUST COINCIDE | | | PLEASE CORRECT. | | | | | | 2) PLANS SHOW 20.5 TONS OF A/C, ENERGY | | | CAL'S. SHOW 5.5 TON OF A/C, THE TWO MUST | | | COINCIDE PLEASE CORRECT. | | | | | | 3) SEE ENERGY CAL'S. FORM 'A' SYSTEM | | | REPORT COMP. FCU-1 IS LESS THAN 65,000 | | | BTU'S., PLANS SHOW THAT FCU-1 IS 134,900 | | | TOTAL BTU'S. PLEASE CORRECT. | | | | | | 4) SEE ELECTRICAL REVIEW NOTES 1,2,3, | | | AND *4* PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|