2006-09-11 00:00:00*** DENIED ***
 1) PLANS SHOW USABLE SPACE AS 4310 SQ.
 FT., ENERGY CAL'S. SHOW CONDITIONED AREA
 AS 5304 SQ. FT., THE TWO MUST COINCIDE
 PLEASE CORRECT.
  
 2) PLANS SHOW 20.5 TONS OF A/C, ENERGY
 CAL'S. SHOW 5.5 TON OF A/C, THE TWO MUST
 COINCIDE PLEASE CORRECT.
  
 3) SEE ENERGY CAL'S. FORM 'A' SYSTEM
 REPORT COMP. FCU-1 IS LESS THAN 65,000
 BTU'S., PLANS SHOW THAT FCU-1 IS 134,900
 TOTAL BTU'S. PLEASE CORRECT.
  
 4) SEE ELECTRICAL REVIEW NOTES 1,2,3,
 AND *4* PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  