Plan Review Notes
Plan Review Notes For Permit 06081976
Permit Number 06081976
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-09-22 00:00:00*****UNSAT******
  
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF THE
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 3.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTION SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES DURING ALTERATION.
  
 4.) WHEN IT IS NECESSARY TO SHUT DOWN A
 FIRE PROTECTION SYSTEM, THE FIRE
 DEPARTMENT WILL BE NOTIFIED WHEN THE
 SYSTEM IS SHUT DOWN AND WHEN IT IS
 RETURNED TO SERVICE.
  
 5.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF FIRE
 SPRINKLER OR FIRE ALARM SYSTEM, SEPARATE
 PERMIT AND SHOP DRAWINGS/PLANS ARE TO BE
 SUBMITTED.
  
 6.) EXPLAIN HOW EMERGENCY FIRE DEPARMENT
 RESPONSE CAN BE ACCOMPLISHED WHEN THE
 BARRICADE IS ERECTED. WILL ACCESS TO
 FIRE HYDRANT(S) OR OTHER FIRE DEPARTMENT
 CONNECTIONS BE HAMPERED/OBSTRUCTED?
  
 7.) NFPA 101,2003 EDITION, AND FLORIDA
 FIRE PREVENTION CODE, 2004 EDITION,
 SHALLBE REFERENCED.
  
 8.) ON THE APPROPIATE STOREFRONT &
 ELEVATION SHEET, SHOW/DISPLAY THE
 NUMERICAL ADDRESS ON THE STRUCTURE AS
 WELL AS THE STORE'S SUITE NUMBER. IF
 USED, HURRICANE SHUTTERS SHALL NOT BE
 PERMITTED TO COVER OR CONCEAL ADDRESS.
  
 9.) INTERIOR FINISH FOR WALLS AND
 CEILING IN EXIT CORRIDOR SHALL BE CLASS
 "A" OR CLASS "B".
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722