| Date |
Text |
| 2006-09-22 00:00:00 | *****UNSAT****** |
| | |
| | |
| | |
| | |
| | |
| | 1.) STRUCTURES UNDERGOING CONSTRUCTION, |
| | ALTERATION, OR DEMOLITION OPERATIONS |
| | SHALL COMPLY WITH NFPA 241. |
| | |
| | 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE |
| | MATERIAL AND DUST DEBRIS SHALL BE |
| | REMOVED FROM THE STRUCTURE AND ITS |
| | IMMEDIATE VICINITY AT THE END OF THE |
| | SHIFT OR MORE FREQUENTLY AS NECESSARY |
| | FOR SAFE OPERATIONS. |
| | |
| | 3.) WHERE THE BUILDING IS PROTECTED BY |
| | FIRE PROTECTION SYSTEMS, SUCH SYSTEMS |
| | SHALL BE MAINTAINED OPERATIONAL AT ALL |
| | TIMES DURING ALTERATION. |
| | |
| | 4.) WHEN IT IS NECESSARY TO SHUT DOWN A |
| | FIRE PROTECTION SYSTEM, THE FIRE |
| | DEPARTMENT WILL BE NOTIFIED WHEN THE |
| | SYSTEM IS SHUT DOWN AND WHEN IT IS |
| | RETURNED TO SERVICE. |
| | |
| | 5.) IF THE SCOPE OF THE INTERIOR |
| | BUILDOUT REQUIRES MODIFICATION OF FIRE |
| | SPRINKLER OR FIRE ALARM SYSTEM, SEPARATE |
| | PERMIT AND SHOP DRAWINGS/PLANS ARE TO BE |
| | SUBMITTED. |
| | |
| | 6.) EXPLAIN HOW EMERGENCY FIRE DEPARMENT |
| | RESPONSE CAN BE ACCOMPLISHED WHEN THE |
| | BARRICADE IS ERECTED. WILL ACCESS TO |
| | FIRE HYDRANT(S) OR OTHER FIRE DEPARTMENT |
| | CONNECTIONS BE HAMPERED/OBSTRUCTED? |
| | |
| | 7.) NFPA 101,2003 EDITION, AND FLORIDA |
| | FIRE PREVENTION CODE, 2004 EDITION, |
| | SHALLBE REFERENCED. |
| | |
| | 8.) ON THE APPROPIATE STOREFRONT & |
| | ELEVATION SHEET, SHOW/DISPLAY THE |
| | NUMERICAL ADDRESS ON THE STRUCTURE AS |
| | WELL AS THE STORE'S SUITE NUMBER. IF |
| | USED, HURRICANE SHUTTERS SHALL NOT BE |
| | PERMITTED TO COVER OR CONCEAL ADDRESS. |
| | |
| | 9.) INTERIOR FINISH FOR WALLS AND |
| | CEILING IN EXIT CORRIDOR SHALL BE CLASS |
| | "A" OR CLASS "B". |
| | |
| | |
| | |
| | |
| | |
| | |
| | LT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |