| 2006-09-21 00:00:00 | DENIED BY BUILDING |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE TITLE BLOCK IS MISSING THE FIRM |
| | NUMBER FOR THE ARCHITECT BUSINESS. SEE |
| | FAC 61G1-16.004. |
| | |
| | 3) FBC 13-400.3.ABC.1THE FLA/COM |
| | PERFORMANCE CALCULATION PROCEDURES |
| | DEMONSTRATING CODE COMPLIANCE FOR |
| | METHODS A AND B, AND FORM 400C |
| | DEMONSTRATING CODE COMPLIANCE FOR METHOD |
| | C SHALL BE PREPARED, SIGNED AND SEALED |
| | BY AN ARCHITECT OR ENGINEER REGISTERED |
| | IN THE STATE OF FLORIDA. THE FORMS |
| | REQUIRE THE RAISED SEAL AND ORIGINAL |
| | SIGNATURE OF THE ARCHITECT OR ENGINEER. |
| | NOTE: ONLY ONE OF THE METHODS LISTED |
| | ABOVE IS REQUIRED TO BE SUBMITTED (TWO |
| | COPIES). |
| | |
| | 4) FBC 13-400.3.ABC.2 THE BUILDING?S |
| | OWNER, THE OWNER?S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY |
| | THE OWNER SHALL CERTIFY TO THE BUILDING |
| | OFFICIAL THAT THE BUILDING IS IN |
| | COMPLIANCE WITH THE REQUIREMENTS OF |
| | CHAPTER 13 OF THIS CODE PRIOR TO |
| | RECEIVING THE PERMIT TO BEGIN |
| | CONSTRUCTION OR RENOVATION. |
| | |
| | 5) SPECIFY THE LEVEL OF ALTERATION, AS |
| | SPECIFIED IN THE 2004 FBC EXISTING |
| | BUILDING CODE, FOR THE PROJECT ON THE |
| | PLANS. |
| | |
| | 6) SPECIFY THE BUILDINGS CONSTRUCTION |
| | TYPE USING THE 2004 FBC DESIGNATIONS. |
| | SPECIFY A OR B. |
| | |
| | 7) ON SHEET A0.0 THE EGRESS WIDTH INCHES |
| | PER OCCUPANT FOR THE DOOR AND STAIR |
| | WIDTHS ARE INCORRECT. THEY ARE 0.2 FOR |
| | DOORS AND 0.3 FOR STAIRWAYS. SEE FBC |
| | TABLE 1005.1. |
| | |
| | 8) SUBMIT PRODUCT APPROVALS FOR EXTERIOR |
| | DOORS, STOREFRONTS, WINDOWS, ETC. |
| | PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE |
| | REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 9 )W P B ADMINISTRTIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10) INDICATE THE REQUIRED CLEAR FLOOR |
| | SPACES FOR ALL FIXTURES ON THE PLANS |
| | WITH LINES. FBC 11-4.2.4 & 11-4.22.3. |
| | |
| | 11) FBC 11-4.22.2ALL DOORS TO |
| | ACCESSIBLE TOILET ROOMS SHALL COMPLY |
| | WITH SECTION 11-4.13 . DOORS SHALL NOT |
| | SWING INTO THE CLEAR FLOOR SPACE |
| | REQUIRED FOR ANY FIXTURE. |
| | |
| | 12) CONSTRUCTION BARRICADE MUST COMPLY |
| | WITH FBC 3306.5 AND 3306.6. |
| | |
| | 13) SUBMIT INFORMATION INDICATING THE |
| | FLAME RESISTANCE OF THE FABRIC AWNING |
| | MATERIAL. FBC 3105.3.1 |
| | |
| | 14) FABRIC SHALL BE QUICK REMOVAL OR |
| | BREAKAWAY DESIGN. SEE FBC 3105.4.2.1. |
| | |
| | 15) ALL EXTERIOR SIGNS WILL REQUIRE |
| | SEPARATE PERMITS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |