2008-05-21 11:13:12REVIEW #: REVISION
 ACTION: DENIED
  
 CODES:
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGES M-0, M-3 AND M-4 WERE SUBMITTED AS PART OF
 THIS REVISION BUT DO NOT SHOW ANY CHANGES. WHEN
 RESUBMITTING, PLEASE PROVIDE ONLY THOSE PAGES WHICH
 HAVE CHANGES TO BE UPDATED IN THE PERMIT RECORD.
  
 2. PG M-2: HOOD-3 IS BEING REMOVED FROM PLANS. IF THERE
 IS AN OVEN AT THIS LOCATION, IT STILL REQUIRES EITHER A
 TYPE I OR TYPE II HOOD IN ACCORDANCE WITH FBCM 507.2.
 PLEASE SHOW HOW COMPLIANCE WITH THIS CODE SECTION SHALL
 BE ACHIEVED.
  
 3. PG M-2: THE 10X10 GREASE DUCT ASSOCIATED WITH HOOD-3
 IS BEING REPLACED WITH AN 8 INCH ROUND DUCT. KEY NOTE
 #4 CALLS THIS A GREASE DUCT WHILE KEY NOTE #39 CALLS IT
 A PRE-FAB DIRECT-VENT EXHAUST DUCT. PLEASE CLARIFY BY
 ELIMINATING CONFLICTING INFORMATION IN THE KEY NOTES.
 ALSO, IF THE OVEN IS A DIRCT-VENT APPLIANCE AS
 INDICATED BY KEY NOTE #19, IT REQUIRES COMBUSTION AIR
 DIRECTLY FROM THE OUTDOORS. SEE DEFINITION OF
 DIRECT-VENT IN FBCFG SECTION 202. SHOW THE SOURCE OF
 DIRECT COMBUSTION AIR IF THIS IS A DIRECT-VENT
 APPLIANCE.
  
 4. PG M-2: KEY NOTE #4 INDICATES THE 8 INCH ROUND DUCT
 IN THE SHAFT IS EXISTING. THIS IS NOT ACCURATE AS THE
 EXHAUST DUCTS IN THE SHAFT WERE INSTALLED UNDER
 SEPARATE PERMIT #07010023 AND THERE WAS NO 8 INCH ROUND
 DUCT ON PLANS OR ASSOCIATED WITH THAT PERMIT. PLEASE
 CORRECT AND SHOW THE 8 INCH ROUND DUCT AS NEW WORK PART
 OF THIS PERMIT. FBCB 106.1.1.
  
 5. THE KITCHEN HOODS AND GREASE DUCTS ARE ALSO UNDER A
 SEPARATE PERMIT #08010158. IF HOOD-3, RELATED DUCTWORK
 AND FANS ARE TO BE ELIMINATED, PLANS FOR PERMIT
 #08010158 SHALL ALSO BE REVISED. ALL WORK SHALL BE DONE
 IN ACCORDANCE WITH PERMITTED CONSTRUCTION DOCUMENTS AND
 ANY CHANGES SHALL BE SUBMITTED FOR REVIEW IN ACCORDANCE
 WITH FBCB 106.4.
  