| 2008-05-21 11:13:12 | REVIEW #: REVISION |
| | ACTION: DENIED |
| | |
| | CODES: |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGES M-0, M-3 AND M-4 WERE SUBMITTED AS PART OF |
| | THIS REVISION BUT DO NOT SHOW ANY CHANGES. WHEN |
| | RESUBMITTING, PLEASE PROVIDE ONLY THOSE PAGES WHICH |
| | HAVE CHANGES TO BE UPDATED IN THE PERMIT RECORD. |
| | |
| | 2. PG M-2: HOOD-3 IS BEING REMOVED FROM PLANS. IF THERE |
| | IS AN OVEN AT THIS LOCATION, IT STILL REQUIRES EITHER A |
| | TYPE I OR TYPE II HOOD IN ACCORDANCE WITH FBCM 507.2. |
| | PLEASE SHOW HOW COMPLIANCE WITH THIS CODE SECTION SHALL |
| | BE ACHIEVED. |
| | |
| | 3. PG M-2: THE 10X10 GREASE DUCT ASSOCIATED WITH HOOD-3 |
| | IS BEING REPLACED WITH AN 8 INCH ROUND DUCT. KEY NOTE |
| | #4 CALLS THIS A GREASE DUCT WHILE KEY NOTE #39 CALLS IT |
| | A PRE-FAB DIRECT-VENT EXHAUST DUCT. PLEASE CLARIFY BY |
| | ELIMINATING CONFLICTING INFORMATION IN THE KEY NOTES. |
| | ALSO, IF THE OVEN IS A DIRCT-VENT APPLIANCE AS |
| | INDICATED BY KEY NOTE #19, IT REQUIRES COMBUSTION AIR |
| | DIRECTLY FROM THE OUTDOORS. SEE DEFINITION OF |
| | DIRECT-VENT IN FBCFG SECTION 202. SHOW THE SOURCE OF |
| | DIRECT COMBUSTION AIR IF THIS IS A DIRECT-VENT |
| | APPLIANCE. |
| | |
| | 4. PG M-2: KEY NOTE #4 INDICATES THE 8 INCH ROUND DUCT |
| | IN THE SHAFT IS EXISTING. THIS IS NOT ACCURATE AS THE |
| | EXHAUST DUCTS IN THE SHAFT WERE INSTALLED UNDER |
| | SEPARATE PERMIT #07010023 AND THERE WAS NO 8 INCH ROUND |
| | DUCT ON PLANS OR ASSOCIATED WITH THAT PERMIT. PLEASE |
| | CORRECT AND SHOW THE 8 INCH ROUND DUCT AS NEW WORK PART |
| | OF THIS PERMIT. FBCB 106.1.1. |
| | |
| | 5. THE KITCHEN HOODS AND GREASE DUCTS ARE ALSO UNDER A |
| | SEPARATE PERMIT #08010158. IF HOOD-3, RELATED DUCTWORK |
| | AND FANS ARE TO BE ELIMINATED, PLANS FOR PERMIT |
| | #08010158 SHALL ALSO BE REVISED. ALL WORK SHALL BE DONE |
| | IN ACCORDANCE WITH PERMITTED CONSTRUCTION DOCUMENTS AND |
| | ANY CHANGES SHALL BE SUBMITTED FOR REVIEW IN ACCORDANCE |
| | WITH FBCB 106.4. |
| | |