Plan Review Notes
Plan Review Notes For Permit 06081940
Permit Number 06081940
Review Stop P
Sequence Number 3
Notes
Date Text
2007-06-01 16:20:33DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CITY CODE
  
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. GREASE INTERCEPTOR SHALL BE SIZED BY
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE
 MANAGER. CONTACT LYNN BY PHONE (561)
 822-2271, OR BY FAX (561) 822-2279, OR
 E-MAIL [email protected]. MUNICIPAL CODE
 SECTION 3434.
 ****RESPONSE NOTED, BUT NO FEEDBACK FROM ENVIRONMENTAL
 COMPLIANCE AS OF YET.
 *******RESPONSE FROM RODNEY COMPO IS IN CONFLICT WITH
 INFORMATION SUBMITTED FROM ED SAMOUR. THE TABLES AND
 BENCH SEATING ARE APPROX. 152 SEATS, AND THE OCCUPANCY
 INDICATES APPROX. 200. SEE COPY OF ATTACHED SHEET FROM
 ENVIRONMENTAL COMPLIANCE REQUIRING 3, 1250 GAL GREASE
 INTERCEPTORS.
  
 5. OK
 6. OK
 7. OK
 8. OK
 A. OK
 B. OK
 C. OK
 D. OK
 E. N/A
 F. N/A
 G. OK
  
 **********NEW COMMENT*************
  
 1B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]